- Mounting Mode
- unit mount lug)
- Network Frequency
- 50/60 Hz
- Terminal Identifier
- AL250JD
- [Ics] Rated Service Breaking Capacity
- 65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Trip Unit Technology
- thermal-magnetic
- Height
- 191 mm
- [Ue] Rated Operational Voltage
- 600 V AC 50/60 Hz IEC 60947-3
- Tightening Torque
- 25-25 N.m 95-185 mm² (AWG 3/0...350 kcmil)
- Mounting Support
- lug
- Breaking Capacity Code
- G
- Magnetic Tripping Current
- 2000-2000 A
- Local Signalling
- switched off (OFF) 1 trip indicator green)
- Number Of Slots
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Electrical Connection
- lugs, line || lugs, load
- Mounting Height
- 4.5 in
- Net Weight
- 2.4 kg
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV IEC 60947-2
- Magnetic Hold Current
- 1000 A
- Control Type
- toggle
- Circuit Breaker Application
- HACR rated
- Wire Stripping Length
- 25 mm
- Line Rated Current
- 200-200 A
- Utilisation Category
- category A
- Long Time Pick-Up Adjustment Range
- 0.25...1 x In
- Continuous Current Rating
- 80 %
- Breaking Capacity
- 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
- [Ui] Rated Insulation Voltage
- 750 V IEC 60947-2
- Suitability For Isolation
- yes IEC 60947-2
- Communication Interface
- Modbus || Ethernet
- Poles Description
- 3P
- Protection Type
- overload protection || short-circuit protection
- Awg Gauge
- AWG 3/0...350 kcmil aluminium/copper terminals
- Width
- 104 mm
- Depth
- 86 mm
- Phase Connection
- ABC