1 / 1
thumbnail

Beschreibung

Aktiv Reif
TeSys D Green contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 12A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 3HP at 200-208VAC, 3HP at 240VAC, 7.5HP at 480VAC and 10HP at 600VAC three phase. Contactor is also rated for 0.5HP at 115VAC and 2HP at 240VAC single phase. When used with a 480VAC up to 35A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 30A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Equipped with an electronic coil, wide band voltage 100-250V, AC/DC compatible, low consumption. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.82 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
Country of Origin
FR
Part Number
LC1D12KUE
Tariff Code
85364900
EAN
3606480987687
UNSPSC
39121529
£82.83
net
1
Zahlungsmethoden:
Bestes Angebot von:
GBVertrauenswürdiger Automa.Net Lieferant
Verfügbarkeit:
1 Stk.
Auf Lager
Aktualisiert am: 09-11-2024
Geschätzte Lieferung:
Auf Anfrage
Zustand:
Neu versiegelt ab Werk
Neu versiegelt ab Werk - Ein brandneuer, unbenutzter, ungeöffneter, unbeschädigter Artikel in seiner original vom Hersteller versiegelten Verpackung.
Insgesamt 25 Parts In-Stock von 12 Distributors
Sicherer Zahlungsprozess
Rückgabe- und Erstattungsrichtlinien
Versandrichtlinien
Garantiebedingungen

Verfügbare Angebote (12)

LC1D12KUE product image
Schneider Electric

LC1D12KUE

Zustand:
Neu versiegelt ab Werk
Verfügbar:
1 Stk.
Auf Lager
Aktualisiert am: 09-11-2024
Angebot von:
NLVertrauenswürdiger Automa.Net Lieferant
Geschätzte Lieferung:
Auf Anfrage
1
€102.22
net
LC1D12KUE product image
Schneider Electric

LC1D12KUE

Zustand:
Neu versiegelt ab Werk
Verfügbar:
1 Stk.
Auf Lager
Aktualisiert am: 09-11-2024
Angebot von:
DEVertrauenswürdiger Automa.Net Lieferant
Geschätzte Lieferung:
Auf Anfrage
1
€104.00
net
LC1D12KUE product image
Schneider Electric

LC1D12KUE

Zustand:
Neu versiegelt ab Werk
Verfügbar:
1 Stk.
Auf Lager
Aktualisiert am: 09-11-2024
Angebot von:
ITVertrauenswürdiger Automa.Net Lieferant
Geschätzte Lieferung:
Auf Anfrage
1
€125.40
net
LC1D12KUE product image
Schneider Electric

LC1D12KUE

Zustand:
Neu versiegelt ab Werk
Verfügbar:
1 Stk.
Auf Lager
Aktualisiert am: 09-11-2024
Angebot von:
ESVertrauenswürdiger Automa.Net Lieferant
Geschätzte Lieferung:
Auf Anfrage
1
€132.62
net
LC1D12KUE product image
Schneider Electric

LC1D12KUE

Zustand:
Neu versiegelt ab Werk
Verfügbar:
1 Stk.
Auf Lager
Aktualisiert am: 09-11-2024
Angebot von:
FRVertrauenswürdiger Automa.Net Lieferant
Geschätzte Lieferung:
Auf Anfrage
1
€184.61
net
Angebot mit Herstellervorlaufzeit
Lieferung:Auf Anfrage
Bester Preis:
€27.16

Environment

Product Certifications
CCC || CSA || EAC || UL || KC || DNV-GL || LROS (Lloyds register of shipping) || UKCA
Height
77 mm
Standards
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || IEC 60335-1
Climatic Withstand
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Net Weight
0.373 kg
Flame Retardance
V1 conforming to UL 94
Ip Degree Of Protection
IP20 front face IEC 60529
Mechanical Robustness
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
Operating Altitude
0...9842.52 ft (0...3000 m)
Fire Resistance
850 °C IEC 60695-2-1
Width
45 mm
Depth
86 mm
Permissible Ambient Air Temperature Around The Device
-40-60 °C || 60-70 °C with derating

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1609001EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI1609001EN
Eu Rohs Directive
Compliant with Exemptions
Halogen Content Performance
Halogen free plastic parts & cables product

Complementary

Non-Overlap Time
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Minimum Switching Current
5 mA for signalling circuit
Power Dissipation Per Pole
1.56 W AC-1 || 0.36 W AC-3 || 0.36 W AC-3e
Average Impedance
2.5 mOhm - Ith 25 A 50 Hz for power circuit
Auxiliary Contact Composition
1 NO + 1 NC
[Ith] Conventional Free Air Thermal Current
10 A (at 60 °C) for signalling circuit || 25 A (at 60 °C) for power circuit
Control Circuit Voltage Limits
<= 0.1 Uc -40-70 °C drop-out AC/DC || 0.85...1.1 Uc -40-60 °C operational AC/DC || 1...1.1 Uc 60-70 °C operational AC/DC
Mounting Support
rail || plate
Control Circuit Type
AC/DC 50/60 Hz AC/DC electronic
Safety Reliability Level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Pollution Degree
3
Hold-In Power Consumption In W
1.1-1.1 W 20 °C
Insulation Resistance
> 10 MOhm for signalling circuit
Rated Breaking Capacity
250 A at 440 V for power circuit conforming to IEC 60947
Irms Rated Making Capacity
250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for signalling circuit conforming to IEC 60947-5-1 || 250 A DC for signalling circuit conforming to IEC 60947-5-1
Associated Fuse Rating
10 A gG for signalling circuit conforming to IEC 60947-5-1 || 40 A gG at <= 690 V coordination type 1 for power circuit || 25 A gG at <= 690 V coordination type 2 for power circuit
Inrush Power In Va
25-25 VA 50/60 Hz (at 20 °C)
[Uimp] Rated Impulse Withstand Voltage
6 kV IEC 60947
Pole Contact Composition
3 NO
Connections - Terminals
control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid || power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end || power circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid || power circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid
Coil Technology
built-in bidirectional peak limiting
Operating Time
45...55 ms closing || 20...90 ms opening
Minimum Switching Voltage
17 V for signalling circuit
Maximum Operating Rate
3600 cyc/h 60 °C
Signalling Circuit Frequency
25...400 Hz
Tightening Torque
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 1.7 N.m screw clamp terminals pozidriv No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2
Electrical Durability
2.3 Mcycles 11 A AC-3 <= 440 V || 0.8 Mcycles 25 A AC-1 <= 440 V || 2.3 Mcycles 11 A AC-3e <= 440 V
Mechanical Durability
15 Mcycles
Inrush Power In W
18-18 W 20 °C)
Auxiliary Contacts Type
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Compatibility Code
LC1D
Hold-In Power Consumption In Va
1.6-1.6 VA 50/60 Hz (at 20 °C)
Overvoltage Category
III
Maximum Horse Power Rating
0.5 hp at 115 V AC 60 Hz for 1 phase motors || 2 hp at 230/240 V AC 60 Hz for 1 phase motors || 3 hp at 200/208 V AC 60 Hz for 3 phase motors || 3 hp at 230/240 V AC 60 Hz for 3 phase motors || 7.5 hp at 460/480 V AC 60 Hz for 3 phase motors || 10 hp at 575/600 V AC 60 Hz for 3 phase motors
Motor Power Kw
3 kW at 220...230 V AC 50 Hz (AC-3) || 5.5 kW at 380...400 V AC 50 Hz (AC-3) || 5.5 kW at 415 V AC 50 Hz (AC-3) || 5.5 kW at 440 V AC 50 Hz (AC-3) || 7.5 kW at 500 V AC 50 Hz (AC-3) || 7.5 kW at 660...690 V AC 50 Hz (AC-3) || 3 kW at 220...230 V AC 50 Hz (AC-3e) || 5.5 kW at 380...400 V AC 50 Hz (AC-3e) || 5.5 kW at 415 V AC 50 Hz (AC-3e) || 5.5 kW at 440 V AC 50 Hz (AC-3e) || 7.5 kW at 500 V AC 50 Hz (AC-3e) || 7.5 kW at 660...690 V AC 50 Hz (AC-3e)
[Ui] Rated Insulation Voltage
power circuit 690 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-1
[Icw] Rated Short-Time Withstand Current
100 A - 1 s for signalling circuit || 120 A - 500 ms for signalling circuit || 140 A - 100 ms for signalling circuit || 30 A 40 °C - 10 min for power circuit || 61 A 40 °C - 1 min for power circuit || 105 A 40 °C - 10 s for power circuit || 210 A 40 °C - 1 s for power circuit
Heat Dissipation
1.1-1.1 W at 50/60 Hz
Protective Cover
with

Specifications

[Uc] Control Circuit Voltage
100...250 V AC 50/60 Hz || 100...250 V DC
[Ue] Rated Operational Voltage
power circuit <= 690 V AC 25...400 Hz
Range Of Product
TeSys Deca
Contactor Application
motor control || resistive load
Product Or Component Type
contactor
Range
TeSys || TeSys Deca
Utilisation Category
AC-1 || AC-3 || AC-3e
[Ie] Rated Operational Current
25 A (at <60 °C) at <= 440 V AC-1 for power circuit || 12 A (at <60 °C) at <= 440 V AC-3 for power circuit || 12 A (at <60 °C) at <= 440 V AC-3e for power circuit
Poles Description
3P
Device Short Name
LC1D

CAD Models

traceparts
traceparts
Herunterladen