Schneider Electric
LC1D40BD
IEC contactor, TeSys D, nonreversing, 40A, 30HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 24VDC coil, open style
- Erhalten Sie bis zu 90 Tage Zahlungsziele von 500+ Lieferanten
- Wiederverkaufsrabatte bis zu 40%!
1535,85 zł
1
Zahlungsmöglichkeiten:
Produktbedingungen:
Angebot mit Herstellervorlaufzeit
Lieferung:Auf Anfrage
Bester Preis:
Preisanfrage senden
Additional Information
- Part Number
- LC1D40BD
- UNSPSC
- 39121529
- Tariff Code
- 8536410045
- Country of Origin
- CZ
Environment
- Product Certifications
- GOST || BV || CSA || CCC || RINA || GL || UL || LROS (Lloyds register of shipping) || DNV || UKCA
- Height
- 127 mm
- Standards
- CSA C22.2 No 14 || IEC 60947-4-1 || UL 508 || EN 60947-4-1 || IEC 60947-5-1 || EN 60947-5-1
- Climatic Withstand
- IACS E10 exposure to damp heat
- Net Weight
- 2.185 kg
- Flame Retardance
- V1 conforming to UL 94
- Ip Degree Of Protection
- IP2X IEC 60529 || IP2X VDE 0106
- Mechanical Robustness
- shocks contactor opened 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms) || vibrations contactor opened 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz)
- Operating Altitude
- 0...9842.52 ft (0...3000 m)
- Fire Resistance
- 850 °C IEC 60695-2-1
- Width
- 85 mm
- Depth
- 176 mm
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP110205EN
- Sustainable Offer Status
- Green Premium product
- Pvc Free
- Yes
- Toxic Heavy Metal Free
- Yes
- Reach Regulation
- Free of Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
- Reach Free Of Svhc
- Yes
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Circularity Profile
- N/A
- Eu Rohs Directive
- Compliant
Complementary
- Non-Overlap Time
- 1.5 ms on de-energisation between NC and NO contacts || 1.5 ms on energisation between NC and NO contacts
- Minimum Switching Current
- 5 mA for control circuit
- Power Dissipation Per Pole
- 5.4 W AC-1 || 2.4 W AC-3 || 2.4 W AC-3e
- Auxiliary Contact Composition
- 1 NO + 1 NC
- [Ith] Conventional Free Air Thermal Current
- 10 A (at 60 °C) for control circuit || 60 A (at 60 °C) for power circuit
- Control Circuit Voltage Limits
- 0.1...0.3 Uc -40-70 °C drop-out DC || 0.75...1.25 Uc -40-60 °C operational DC || 1...1.25 Uc 60-70 °C operational DC
- Mounting Support
- rail || plate
- Control Circuit Type
- DC standard
- Safety Reliability Level
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Hold-In Power Consumption In W
- 7.4-7.4 W 20 °C
- Insulation Resistance
- > 10 MOhm for control circuit
- Rated Breaking Capacity
- 800 A at 440 V for power circuit conforming to IEC 60947
- Irms Rated Making Capacity
- 250 A DC for control circuit conforming to IEC 60947-5-1 || 800 A at 440 V for power circuit conforming to IEC 60947
- Associated Fuse Rating
- 10 A gG for control circuit conforming to IEC 60947-5-1 || 80 A gG at <= 690 V coordination type 1 for power circuit || 80 A gG at <= 690 V coordination type 2 for power circuit
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV IEC 60947
- Pole Contact Composition
- 3 NO
- Connections - Terminals
- control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: rigid || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: rigid || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || power circuit: screw terminals 1 2.5-25 mm² - cable stiffness: rigid || power circuit: screw terminals 2 2.5-16 mm² - cable stiffness: rigid || power circuit: screw terminals 1 2.5-25 mm² - cable stiffness: flexible without cable end || power circuit: screw terminals 2 2.5-16 mm² - cable stiffness: flexible without cable end || power circuit: screw terminals 1 2.5-25 mm² - cable stiffness: flexible with cable end || power circuit: screw terminals 2 2.5-10 mm² - cable stiffness: flexible with cable end
- Coil Technology
- built-in bidirectional peak limiting diode suppressor
- Time Constant
- 34 ms
- Operating Time
- 20 ms opening || 50 ms closing
- Minimum Switching Voltage
- 17 V for control circuit
- Maximum Operating Rate
- 3600 cyc/h 60 °C
- Tightening Torque
- control circuit 1.7 N.m screw clamp terminal flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminal Philips No 2 || power circuit 5 N.m screw terminal flat Ø 6 to Ø 8 mm || control circuit 1.7 N.m screw clamp terminal pozidriv No 2
- Mechanical Durability
- 10000000 cycles
- Inrush Power In W
- 19-19 W 20 °C)
- Auxiliary Contacts Type
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Compatibility Code
- LC1D
- Overvoltage Category
- III
- Maximum Horse Power Rating
- 3 hp at 115 V AC 60 Hz for 1 phase motors || 5 hp at 230/240 V AC 60 Hz for 1 phase motors || 10 hp at 200/208 V AC 60 Hz for 3 phase motors || 10 hp at 230/240 V AC 60 Hz for 3 phase motors || 30 hp at 460/480 V AC 60 Hz for 3 phase motors || 30 hp at 575/600 V AC 60 Hz for 3 phase motors
- Motor Power Kw
- 18.5 kW at 380...400 V AC 50 Hz (AC-3) || 22 kW at 500 V AC 50 Hz (AC-3) || 30 kW at 660...690 V AC 50 Hz (AC-3) || 22 kW at 1000 V AC 50 Hz (AC-3) || 22 kW at 415 V AC 50 Hz (AC-3) || 22 kW at 440 V AC 50 Hz (AC-3) || 11 kW at 220...230 V AC 50 Hz (AC-3) || 9 kW at 400 V AC 50 Hz (AC-4) || 18.5 kW at 380...400 V AC 50 Hz (AC-3e) || 22 kW at 500 V AC 50 Hz (AC-3e) || 30 kW at 660...690 V AC 50 Hz (AC-3e) || 22 kW at 1000 V AC 50 Hz (AC-3e) || 22 kW at 415 V AC 50 Hz (AC-3e) || 22 kW at 440 V AC 50 Hz (AC-3e) || 11 kW at 220...230 V AC 50 Hz (AC-3e)
- [Ui] Rated Insulation Voltage
- control circuit 600 V CSA || control circuit 600 V UL || power circuit 600 V CSA || power circuit 600 V UL || control circuit 690 V IEC 60947-1 || power circuit 690 V IEC 60947-1 || power circuit 1000 V IEC 60947-4-1
- Rated Operational Power In W
- 14 W 24 V DC-13 10000000 cycles - control circuit || 48 W 24 V DC-13 3000000 cycles - control circuit || 96 W 24 V DC-13 1000000 cycles - control circuit
- Protective Cover
- with
Specifications
- [Uc] Control Circuit Voltage
- 24 V DC
- [Ue] Rated Operational Voltage
- power circuit <= 690 V AC 25...400 Hz
- Range Of Product
- TeSys Deca
- Contactor Application
- resistive load || motor control
- Product Or Component Type
- contactor
- Range
- TeSys
- Utilisation Category
- AC-2 || AC-3 || AC-1 || AC-4 || AC-3e
- [Ie] Rated Operational Current
- 40 A (at <60 °C) at <= 440 V AC AC-3 for power circuit || 60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit || 40 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
- Poles Description
- 3P
- Device Short Name
- LC1D
Dokumente
Data Sheet
HerunterladenCAD Models
traceparts
HerunterladenAndere Kategorien
AktuatorenBlöckeKabel, Rohre & SchläucheKompressorenKontrolleKupplungen & FittingsZylinder & KolbenElektronikFilterHVACIndustrie-PCs & HMIsBeleuchtungLineartechnikMotorenStromversorgungLeistungsübertragungPumpen & VentileErneuerbare energieRobotikDichtungen, Ringe & VerbinderSensoren und MessgeräteWerkzeuge und ZubehörCNCSonstiges