- Product Certifications
- UL || CCC || RMRoS || DNV || RINA || LROS (Lloyds register of shipping) || ABS || BV || CB || UKCA
- Power Dissipation Per Pole
- 15 W AC-1 || 5 W AC-3
- Average Impedance
- 0.37 mOhm - Ith 200 A 50 Hz
- [Ith] Conventional Free Air Thermal Current
- 200 A 40 °C
- Control Circuit Voltage Limits
- operational 0.85...1.1 Uc 50/60 Hz 55 °C) || drop-out 0.35...0.55 Uc 50/60 Hz 55 °C)
- Standards
- EN 60947-4-1 || IEC 60947-1 || IEC 60947-4-1 || JIS C8201-4-1 || EN 60947-1
- Mounting Support
- plate
- Control Circuit Type
- AC 50 Hz
- Rated Breaking Capacity
- 920 A IEC 60947-4-1
- Associated Fuse Rating
- 125 A aM <= 440 V || 200 A gG <= 440 V
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV
- Inrush Power In Va
- 550-550 VA, 50 Hz 0.3 20 °C)
- Connections - Terminals
- power circuit bar 2 20 x 3 mm || power circuit lugs-ring terminals 1 95-95 mm² || power circuit connector 1 95-95 mm² || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit bolted connection
- Pole Contact Composition
- 3 NO
- Operating Time
- 23...35 ms closing || 5...15 ms opening
- Maximum Operating Rate
- 2400 cyc/h 55 °C
- Mechanical Durability
- 10 Mcycles
- Tightening Torque
- power circuit 10 N.m || control circuit 1.2 N.m
- Compatibility Code
- LC1F
- Hold-In Power Consumption In Va
- 45-45 VA, 50 Hz 0.3 20 °C)
- Overvoltage Category
- III
- Motor Power Kw
- 55 kW 380...400 V AC 50/60 Hz AC-3) || 59 kW 415 V AC 50/60 Hz AC-3) || 59 kW 440 V AC 50/60 Hz AC-3) || 75 kW 500 V AC 50/60 Hz AC-3) || 80 kW 660...690 V AC 50/60 Hz AC-3) || 30 kW 220...230 V AC 50/60 Hz AC-3) || 18.5 kW 400 V AC 50/60 Hz AC-4)
- [Ui] Rated Insulation Voltage
- 1000 V IEC 60947-4-1 || 1500 V VDE 0110 group C
- [Icw] Rated Short-Time Withstand Current
- 1100 A 40 °C - 10 s || 640 A 40 °C - 30 s || 520 A 40 °C - 1 min || 400 A 40 °C - 3 min || 320 A 40 °C - 10 min
- Heat Dissipation
- 12-16 W