1 / 1
thumbnail

Beschreibung

Aktiv Reif
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 12A reversing inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 3HP at 200-208VAC, 3HP at 240VAC, 7.5HP at 480VAC and 10HP at 600VAC three phase. Contactor is also rated for 1HP at 115VAC and 2HP at 240VAC single phase. Contactor is supplied with a 120 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 3.54 inches wide and 3.39 inches deep. It weighs 1.54 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
Country of Origin
FR
Part Number
LC2D12G7V
Tariff Code
85364900
EAN
3389110410884
UNSPSC
39121529
Zahlungsmethoden:
Bestes Angebot von:
DEVertrauenswürdiger Automa.Net Lieferant
Verfügbarkeit:
1 Stk.
Auf Lager
Aktualisiert am: 08-11-2024
Garantie:
12 Monate
Geschätzte Lieferung:
Auf Anfrage
Zustand:
Neuer Überschuss
Neuer Überschuss - Ein neuer, unbenutzter, unbeschädigter Artikel ohne Herstellergarantie. Der Artikel kann ohne Originalverpackung oder in Ersatzverpackung geliefert werden. Wenn vorhanden, könnte die Verpackung geöffnet worden sein.
Sicherer Zahlungsprozess
Rückgabe- und Erstattungsrichtlinien
Versandrichtlinien
Garantiebedingungen

Environment

Mechanical Robustness
vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
Ambient Air Temperature For Operation
-40-60 °C || 60-70 °C with derating
Height
77 mm
Climatic Withstand
IACS E10 || IEC 60947-1 Annex Q category D
Pollution Degree
3
Net Weight
0.697 kg
Flame Retardance
V1 conforming to UL 94
Ambient Air Temperature For Storage
-60-80 °C
Protective Treatment
TH IEC 60068-2-30
Ip Degree Of Protection
IP20 front face IEC 60529
Operating Altitude
0...9842.52 ft (0...3000 m)
Fire Resistance
850 °C IEC 60695-2-1
Width
90 mm
Depth
86 mm

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1501004
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Toxic Heavy Metal Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Pro-active China RoHS declaration (out of China RoHS legal scope)
Circularity Profile
ENVEOLI1501004
Eu Rohs Directive
Compliant

Complementary

Non-Overlap Time
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Minimum Switching Current
5 mA for signalling circuit
Control Circuit Voltage Limits
0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz
Insulation Resistance
> 10 MOhm for signalling circuit
Inrush Power In Va
70-70 VA 60 Hz cos phi 0.75 (at 20 °C) || 70-70 VA 50 Hz cos phi 0.75 (at 20 °C)
Coil Technology
without built-in suppressor module
Minimum Switching Voltage
17 V for signalling circuit
Signalling Circuit Frequency
25...400 Hz
Auxiliary Contacts Type
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Hold-In Power Consumption In Va
7.5-7.5 VA 60 Hz cos phi 0.3 (at 20 °C) || 7-7 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat Dissipation
2-3 W 50/60 Hz

Specifications

Product Certifications
DNV || CSA || CCC || UL || GL || LROS (Lloyds register of shipping) || BV || RINA || GOST || UKCA
Interlocking Type
electrical and mechanical
[Uc] Control Circuit Voltage
120 V AC 50/60 Hz
[Ue] Rated Operational Voltage
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Power Dissipation Per Pole
1.56 W AC-1 || 0.36 W AC-3
Average Impedance
2.5 mOhm - Ith 25 A 50 Hz for power circuit
Auxiliary Contact Composition
1 NO + 1 NC
[Ith] Conventional Free Air Thermal Current
10 A (at 60 °C) for signalling circuit || 25 A (at 60 °C) for power circuit
Mounting Support
plate || rail
Control Circuit Type
AC 50/60 Hz
Standards
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Safety Reliability Level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Contactor Application
resistive load || motor control
Rated Breaking Capacity
250 A at 440 V for power circuit conforming to IEC 60947
Product Or Component Type
reversing contactor
Irms Rated Making Capacity
250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for signalling circuit conforming to IEC 60947-5-1 || 250 A DC for signalling circuit conforming to IEC 60947-5-1
Product Name
TeSys D || TeSys Deca
Associated Fuse Rating
10 A gG for signalling circuit conforming to IEC 60947-5-1 || 40 A gG at <= 690 V coordination type 1 for power circuit || 25 A gG at <= 690 V coordination type 2 for power circuit
[Uimp] Rated Impulse Withstand Voltage
6 kV IEC 60947
Connections - Terminals
power circuit screw clamp terminals 1 1-4 mm²flexible without cable end || power circuit screw clamp terminals 2 1-4 mm²flexible without cable end || power circuit screw clamp terminals 1 1-4 mm²flexible with cable end || power circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || power circuit screw clamp terminals 1 1-4 mm²solid || power circuit screw clamp terminals 2 1-4 mm²solid || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid || control circuit screw clamp terminals 2 1-4 mm²solid
Range
TeSys || TeSys Deca
Pole Contact Composition
3 NO
Device Presentation
preassembled with reversing power busbar
Utilisation Category
AC-3 || AC-1
[Ie] Rated Operational Current
25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit || 12 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
Maximum Operating Rate
3600 cyc/h 60 °C
Tightening Torque
power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw clamp terminals pozidriv No 2
Electrical Durability
2 Mcycles 12 A AC-3 <= 440 V || 0.8 Mcycles 25 A AC-1 <= 440 V
Mechanical Durability
15 Mcycles
Poles Description
3P
Operating Time
12...22 ms closing || 4...19 ms opening
Overvoltage Category
III
Motor Power Kw
3 kW at 220...230 V AC 50 Hz || 5.5 kW at 380...400 V AC 50 Hz || 5.5 kW at 415...440 V AC 50 Hz || 7.5 kW at 500 V AC 50 Hz || 7.5 kW at 660...690 V AC 50 Hz
Maximum Horse Power Rating
1 hp at 115 V AC 60 Hz for 1 phase motors || 2 hp at 230/240 V AC 60 Hz for 1 phase motors || 3 hp at 200/208 V AC 60 Hz for 3 phase motors || 3 hp at 230/240 V AC 60 Hz for 3 phase motors || 7.5 hp at 460/480 V AC 60 Hz for 3 phase motors || 10 hp at 575/600 V AC 60 Hz for 3 phase motors
[Ui] Rated Insulation Voltage
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
Device Short Name
LC2D
[Icw] Rated Short-Time Withstand Current
30 A 40 °C - 10 min for power circuit || 61 A 40 °C - 1 min for power circuit || 105 A 40 °C - 10 s for power circuit || 210 A 40 °C - 1 s for power circuit || 100 A - 1 s for signalling circuit || 120 A - 500 ms for signalling circuit || 140 A - 100 ms for signalling circuit
Protective Cover
with

CAD Models

traceparts
traceparts
Herunterladen