- [Us] Rated Supply Voltage
- 200...240 V AC
- Voltage Range
- 200...240 V phase to phase
- Safety Reliability Data
- B10d = 350000 || MTTFd = 388.1 years
- Minimum Switching Current
- 10 mA 5 V DC
- Maximum Measuring Cycle
- 150 ms measurement cycle as true rms value
- Switching Threshold Drift
- <= 0.05 % per degree centigrade depending permissible ambient air temperature || <= 1 % within the supply voltage range
- Maximum Switching Current
- 8 A AC
- Hysteresis
- 2-2 % fixed selectable
- Measurement Error
- < 1 % over the whole range with voltage variation || < 0.05 %/°C with temperature variation
- Status Led
- LED (Yellow) relay ON || LED (Green) power ON
- Power Consumption In Va
- 10-10 VA 240 V AC 60 Hz
- Output Contacts
- 2 C/O
- Contacts Material
- cadmium free
- Voltage Detection Threshold
- < 100 V AC
- Response Time
- <= 300 ms
- Setting Accuracy Of The Switching Threshold
- +/- 10 % of the full scale
- Utilisation Category
- AC-15 IEC 60947-5-1 || DC-13 IEC 60947-5-1 || AC-1 IEC 60947-4-1 || DC-1 IEC 60947-4-1
- Net Weight
- 0.09 kg
- Maximum Switching Voltage
- 250 V AC
- Insulation Resistance
- > 100 MOhm 500 V DC IEC 60255-27
- Reset Time
- 1500 ms at maximum voltage
- Connections - Terminals
- screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end || screw terminals, 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end
- Overvoltage Category
- III IEC 60664-1 || III UL 508
- Time Delay Drift
- <= 0.05 % per degree centigrade depending permissible ambient air temperature || <= 1 % within the supply voltage range
- Setting Accuracy Of Time Delay
- 10 P
- Supply Voltage Limits
- 160-288 V AC
- Mounting Support
- 35 mm DIN rail conforming to IEC 60715
- Nominal Output Current
- 8 A
- Mechanical Durability
- 10000000 cycles
- Housing Material
- self-extinguishing plastic
- Control Circuit Voltage Limits
- 20 % + 20 % Un
- Threshold Adjustment Voltage
- 2...20 % of Un selected
- Mounting Position
- any position
- Width
- 22.5 mm
- Tightening Torque
- 0.6-1 N.m IEC 60947-1
- Electrical Durability
- 100000 cycles
- Run-Up Delay At Power-Up
- 650 ms
- Supply Frequency
- 50...60 Hz +/- 10 %
- Repeat Accuracy
- +/- 0.5 % input and measurement circuit