Ratings / Performance

Rated supply voltage
24 to 240VAC 50/60 Hz
Rated supply voltage
24 to 240VDC ripple: 20% max.
Operating voltage range
85% to 110% of rated supply voltage
Input signals
Start
Input method
Voltage input
Voltage input
High (logic) level: 20.4 to 264 VAC/DC
Voltage input
Low (logic) level: 0 to 2.4 VAC/DC
Minimum input signal width
50 ms min. (Start input)
Power consumption ( Relay ON )
6.6VA(at 240 VAC)
Power consumption ( Relay ON )
1.2W(at 24 VDC)
Power consumption ( Relay OFF )
(at 240 VAC)
Power consumption ( Relay OFF )
(at 24 VDC)
Reset voltage
10% max. of rated supply voltage
Number of time ranges
8
Time ranges
0.1s~1.2s / 1s~12s / 10s~120s / 1min~12min / 10min~120min / 1h~12h / 10h~120h / 100h~1200h
Operating mode
ON delay, Flicker OFF start, Flicker ON start, Signal ON/OFF delay, Signal OFF delay, Interval, Signal ON/OFF delay, One shot output
Control output (Type)
Relay output (DPDT)
Control output (Contact output)
Switching capacities (resistive load (cos (phi) = 1)): 250VAC 5A / 30VDC 5A
Control output (Contact output)
Switching capacities (resistive load (cos (phi) = 1)): 250VAC 5A / 125VDC 0.15A
Control output (Contact output)
Switching capacities (resistive load (cos (phi) = 1)): 250VAC 5A / 125VDC 0.1A
Control output (Contact output)
Minimum applicable load: 10 mA at 5 VDC (failure level: P)
Ambient temperature
Operating: -20 to 55°C
Ambient temperature
Storage: -40 to 70°C
Ambient humidity
Operating: 25~85%
Accuracy of operating time
+/- 1% max.(FS)
Accuracy of operating time
(+/- 1% +/- 10 ms max. in a range of 1.2 s)
Setting error
-10 to 10% +/- 0.05 s max. (FS)
Influence of voltage
+/- 0.5% FS max. (+/- 0.5% +/- 10 ms max. in a range of 1.2 s)
Influence of temperature
+/- 2% FS max. (+/- 2% +/- 10 ms max. in a range of 1.2 s)
Insulation resistance
100 MΩ (at 500 VDC)
Dielectric strength
between current carrying metal parts and non-current carrying metal parts: 2000 VAC, 50/60 Hz for 1 min
Dielectric strength
between control output terminals and operating circuit: 2000 VAC, 50/60 Hz for 1 min
Dielectric strength
between non-continuous contacts: 1000 VAC, 50/60 Hz for 1 min
Impulse withstand voltage
between power terminals: 5 kV
Impulse withstand voltage
between exposed non-current-carrying metal parts: 5 kV
Noise immunity
+/- 1.5 kV (between power terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 us, 1-ns rise)
Static immunity
Mulfunction: 4 kV Destruction: 8 kV
Vibration resistance (Destruction)
10 to 55 Hz, 0.75 mm single amplitude each in X, Y, and Z directions for 2 hours
Vibration resistance (Malfunction)
10 to 55 Hz, 0.5 mm single amplitude each in X, Y, and Z directions for 10 min
Shock resistance (Destruction)
1000 m/s**2, 3 times each 6 directions
Shock resistance (Malfunction)
100 m/s**2, 3 times each 6 directions
Mechanical life expectancy (relayoutput)
10000000 operations min. (under no load at 1800 operations/h)
Electrical life expectancy (relay output)
100000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h)
Degree of protection
IP30(Terminal Block: IP20)
Weight (Main)
Approx. 120 g