Trunk module - FB-ET - 2316048
2316048
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Offer with manufacturer lead time
Ships in:1 - 2 business days
Best price:
€155.50

Additional Information

Part Number
2316048
UPC
4046356466165
Country of Origin
US
ETIM
Group Code : EG000024
Group Description : PLC's
Class Description : Fieldbus, decentr. periphery - power supply/segment module
Class Code : EC001600
Version : 7

Note

Utilization restriction
EMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width
17.5 mm
Height
99.1 mm
Depth
70.4 mm

Ambient conditions

Ambient temperature (operation)
-40 °C - 85 °C
Ambient temperature (storage/transport)
-40 °C - 85 °C
Permissible humidity (operation)
10 % - 95 % (non-condensing)
Degree of protection
IP20

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
China RoHS
For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

Safety data

Input voltage Ui
17.5 V (for FB-2SP in a FNICO/FISCO ic system)
ATEX
Sira 08ATEX4302X; II 3G Ex nA IIC T4 Gc II 3G Ex ic IIC T4 Gc, FISCO ic II 3G Ex nL IIC T4 Gc, FNICO
IECEx
IECEx SIR 08.0109X; Ex nA IIC T4 Gc; Ex ic IIC T4 Gc, FISCO ic; Ex nL IIC T4 Gc, FNICO
CSA, USA/Canada
Class I, Division 2, Groups A,B,C,D; Ex nA IIC T4 Class I, Zone 2, AEx nA IIC T4

Interfaces

Interface 1
Foundation Fieldbus and PROFIBUS PA Segment
Connection method
Pluggable COMBICON screw connection for each spur
Termination resistor
100 Ω, external removable plug included
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Surge protection
Active if voltage exceeds 39 V (typ.) or 41 V (max.)
Voltage drop trunk line / outputs
≤ 0.2 V

Standards and Regulations

Type of test
Corrosive resistance in acc. to ANSI-ISA 71.04-1985 - Severity level G3
Designation
Standards/regulations
Standards/regulations
Ring wave noise immunity in acc. with IEC 61000-4-12
Standards/regulations
Dry heat in acc. with IEC 61131-2
Standards/regulations
Damp heat in acc. with IEC 61131-2
Standards/regulations
Shock and vibration in acc. with EN 61131-2 and EN 50178
Standards/regulations
IEC 61158-2
Standards/regulations
IEC 60529, IEC 61158-2
Standards/regulations
NE21
Standards/regulations
EN 61326, EN 60068-2-27, EN 60068-2-6
Standards/regulations
FF-846
Shock
15g, 11 ms
Vibration (operation)
1g, 10 Hz - 150 Hz
Conformance
CE-compliant, additionally EN 61326
Fieldbus Foundation
FF-846
ATEX
Sira 08ATEX4302X; II 3G Ex nA IIC T4 Gc II 3G Ex ic IIC T4 Gc, FISCO ic II 3G Ex nL IIC T4 Gc, FNICO
IECEx
IECEx SIR 08.0109X; Ex nA IIC T4 Gc; Ex ic IIC T4 Gc, FISCO ic; Ex nL IIC T4 Gc, FNICO
CSA, USA/Canada
Class I, Division 2, Groups A,B,C,D; Ex nA IIC T4 Class I, Zone 2, AEx nA IIC T4

Power supply

Nominal supply voltage
24 V DC (IIC)
Nominal supply voltage
32 V DC (IIB)
Supply voltage range
24 V DC - 32 V DC
Max. current consumption
12 mA (with terminator)
Typical current consumption
8 mA (without termination resistor)

CAD Models

Trace parts
Trace parts
Download