DC/DC converter, protective coating - QUINT-PS/24DC/24DC/ 5/CO - 2320542
2320542
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:

Additional Information

Part Number
2320542
UPC
4046356765930
Country of Origin
CN
ETIM
Group Code : EG000017
Group Description : Low-voltage Industrial Components
Class Description : Power supply transformer
Class Code : EC002046
Version : 7

Input data

Nominal input voltage range
24 V DC
Input voltage range
18 V DC - 32 V DC
Extended input voltage range in operation
14 V DC - 18 V DC (Derating)
Current consumption
7 A (24 V, IBOOST)
Inrush current
typ. 15 A
Mains buffering time
typ. 10 ms (24 V DC)
Input fuse
15 A (device protection)
Recommended breaker for input protection
10 A - 16 A (Characteristics B, C, D, K)
Type of protection
Transient surge protection
Protective circuit/component
Varistor

Standards

EMC requirements for noise immunity
EN 61000-6-1
EMC requirements for noise immunity
EN 61000-6-2
EMC requirements for noise emission
EN 61000-6-3
EMC requirements for noise emission
EN 61000-6-4
Standard - Electrical safety
EN 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage
EN 60950-1 (SELV)
Standard – Safety extra-low voltage
EN 60204-1 (PELV)
Standard - Safe isolation
DIN VDE 0100-410
Rail applications
EN 50121-4
Rail applications
EN 50155

Dimensions

Width
32 mm
Height
130 mm
Depth
125 mm
Width with alternative assembly
122 mm
Height with alternative assembly
130 mm
Depth with alternative assembly
35 mm
Installation distance right/left
0 mm / 0 mm (≤ 70 °C)
Installation distance left/right (active)
15 mm / 15 mm (≤ 70 °C)
Installation distance top/bottom
50 mm / 50 mm (≤ 70 °C)
Installation distance top/bottom (active)
50 mm / 50 mm (≤ 70 °C)

Output data

Nominal output voltage
24 V DC ±1 %
Setting range of the output voltage (USet)
18 V DC - 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN)
5 A (-25 °C - 60 °C)
POWER BOOST (IBoost)
6.25 A (-25°C - 40°C permanent, UOUT = 24 V DC )
Selective Fuse Breaking (ISFB)
30 A (12 ms)
Derating
60 °C - 70 °C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
yes
Feedback voltage resistance
35 V DC
Protection against overvoltage at the output (OVP)
< 35 V DC
Max. capacitive load
unlimited
Active current limitation
Approximately 7.2 A
Control deviation
< 1 % (change in load, static 10 % - 90 %)
Control deviation
< 2 % (change in load, dynamic 10 % - 90 %)
Control deviation
< 0.1 % (change in input voltage ±10 %)
Residual ripple
< 20 mVPP
Peak switching voltages nominal load
< 10 mVPP (20 MHz)
Maximum power dissipation in no-load condition
2.4 W
Power loss nominal load max.
11.4 W

Connection data, input

Connection method
Pluggable screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Stripping length
8 mm
Screw thread
M3

Connection data, output

Connection method
Pluggable screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Stripping length
7 mm
Screw thread
M3

Ambient conditions

Degree of protection
IP20
Ambient temperature (operation)
-25 °C - 70 °C (> 60 °C derating, 2.5 %/K, startup at -40°C type-tested)
Ambient temperature (start-up type tested)
-40 °C
Ambient temperature (storage/transport)
-40 °C - 85 °C
Max. permissible relative humidity (operation)
100 % (at 25 °C, non-condensing)
Climatic class
3K3 (in acc. with EN 60721)
Degree of pollution
2

Connection data for signaling

Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Screw thread
M3

Conformance/approvals

UL approvals
UL/C-UL listed UL 508
UL approvals
UL/C-UL Recognized UL 60950-1
UL approvals
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
Shipbuilding approval
DNV GL (EMC B)

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 25;
China RoHS
For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

EMC data

Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Electrostatic discharge
EN 61000-4-2
Contact discharge
8 kV (Test Level 4)
Discharge in air
15 kV (Test Level 4)
Electromagnetic HF field
EN 61000-4-3
Frequency range
80 MHz - 1 GHz
Frequency range
1 GHz - 2 GHz
Frequency range
2 GHz - 3 GHz
Test field strength
10 V/m
Comments
Criterion A
Fast transients (burst)
EN 61000-4-4
Input
2 kV (Test Level 3 - asymmetrical)
Output
2 kV (Test Level 3 - asymmetrical)
Signal
2 kV (Test Level 4 - asymmetrical)
Surge voltage load (surge)
EN 61000-4-5
Input
1 kV (Test Level 2 - symmetrical)
Output
1 kV (Test Level 2 - symmetrical)
Signal
1 kV (Test Level 2 - asymmetrical)
I/O/S
asymmetrical
Frequency range
0.15 MHz - 80 MHz
Voltage
10 V (Test Level 3)
Criterion A
Normal operating behavior within the specified limits.
Criterion B
Temporary impairment to operational behavior that is corrected by the device itself.