Input data

Sensor types (RTD) that can be used
Sensors (2-, 3-, 4-wire)
Temperature measuring range
-200 °C - 850 °C (Range depending on the sensor type)
Input signal range
0 Ω - 2000 Ω
Max. permissible overall conductor resistance
50 Ω (Per cable)
Sensor input current
200 µA - 1 mA
Measuring range span
min. 50 K

Note

Utilization restriction
EMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width
12.5 mm
Height
116.9 mm
Depth
113.7 mm

Connection data

Connection method
Push-in connection
Stripping length
8 mm
Conductor cross section solid
0.2 mm² - 1.5 mm²
Conductor cross section flexible
0.2 mm² - 1.5 mm²
Conductor cross section AWG
24 - 16

Output data

Signal output
Current output
Configurable/programmable
Yes
Current output signal
0 mA - 20 mA
Current output signal
4 mA - 20 mA
Load/output load current output
≤ 500 Ω
Output ripple (current)
< 50 µAPP
Behavior in the event of a sensor error
As per NE 43 or can be freely defined
Configurable/programmable
no

Ambient conditions

Ambient temperature (operation)
-20 °C - 60 °C (Any mounting position)
Ambient temperature (storage/transport)
-40 °C - 80 °C
Maximum altitude
≤ 2000 m
Permissible humidity (operation)
5 % - 95 % (non-condensing)
Degree of protection
IP20 (not assessed by UL)
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be minimal deviations.

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
China RoHS
For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

EMC data

Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6

Safety data

Max. output voltage Uo
6 V
Max. output current Io
6.3 mA
Max. output power Po
9.4 mW
Group
IIC
Max. external inductivity Lo
100 mH
Max. external capacitance Co
1.4 µF
Additional text
mixed circuit
Max. external inductivity Lo
10 mH
Max. external capacitance Co
1.9 µF
Max. external inductivity Lo
1 mH
Max. external capacitance Co
2.7 µF
Group
IIB
Max. external capacitance Co
6.9 µF
Max. external capacitance Co
9.4 µF
Max. external capacitance Co
15 µF
Group
IIA
Max. external capacitance Co
10 µF
Max. external capacitance Co
13 µF
Max. external capacitance Co
21 µF
Safety-related maximum voltage Um
253 V AC (125 V DC)

Safety characteristic data

Integrity requirement
IEC 61508 - Low demand
Architecture
Single-channel, 1oo1
Equipment type
Type B
Safe Failure Fraction (SFF)
91.3 %
MTBF
119 Years
ΛSD
4.61 x 10-⁷ (461 FIT)
ΛDU
3.23 x 10-⁷ (323 FIT)
ΛDD
3.18 x 10-⁸ (31.8 FIT)
Probability of a hazardous failure on demand (PFDAVG)
1.3 x 10-⁴ (1 year)
Probability of a hazardous failure on demand (PFDAVG)
2.6 x 10-⁴ (2 years)
Probability of a hazardous failure on demand (PFDAVG)
3.91 x 10-⁴ (3 years)
Probability of a hazardous failure on demand (PFDAVG)
6.51 x 10-⁴ (5 years)
Probability of a hazardous failure on demand (PFDAVG)
9.11 x 10-⁴ (7 years)
Probability of a hazardous failure on demand (PFDAVG)
1.04 x 10-³ (8 years)
Diagnostic coverage (DC)
90.2 %
Integrity requirement
IEC 61508 - High demand
ΛSU
1.5 x 10-⁷ (150 FIT)
Probability of a hazardous failure per hour (PFHD)
3,23 x 10-⁸

Standards and Regulations

Noise emission
EN 61000-6-4
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Standards/regulations
EN 61000-4-4
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Conformance
CE-compliant, additionally EN 61326
ATEX
II (1) G [Ex ia Ga] IIC/IIB
ATEX
II (1) D [Ex ia Da] IIIC
ATEX
II 3(1) G Ex nA ic [ia Ga] IIC T4 Gc X
IECEx
[Ex ia Ga] IIC
IECEx
[Ex ia Da] IIIC
IECEx
Ex nA ic [ia Ga] IIC T4 Gc
UL, USA/Canada
Class I Div 2; IS for Class I, II, III Div 1
Group
IIC
Group
IIB

Power supply

Nominal supply voltage
24 V DC
Supply voltage range
19.2 V DC - 30 V DC (24 V DC -20%...+25%)
Power dissipation
< 1 W