1 / 5
thumbnail
thumbnail
thumbnail
thumbnail
thumbnail

Opis

Końcówka Serii
PowerPacT J-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT J-Frame circuit breakers are available with either thermal magnetic or MicroLogic electronic trip protection units. This PowerPacT J-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 18kA at 600VAC. All PowerPacT J-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT J circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has lugs on both the line and load sides. This PowerPacT J, 175A, 3 pole, circuit breaker has a breaking capacity of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT J circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
Country of Origin
MX
Part Number
JGL36175
Tariff Code
8536200020
EAN
39121601
UPC
785901883746
UNSPSC
39121601
$785.00
net
1
Metody płatności:
Najlepsza oferta od:
USZaufany dostawca Automa.Net
Dostępność:
4 szt.
W magazynie
Zaktualizowano: 07-10-2024
Gwarancja:
24 miesiące
Szacowany czas dostawy:
Na zapytanie
Stan produktu:
Fabrycznie Nowe, Zapieczętowane
Fabrycznie Nowe, Zapieczętowane - Nowy, nieużywany, nieotwarty, nieuszkodzony przedmiot w oryginalnym opakowaniu zapieczętowanym przez producenta.
Bezpieczny proces płatności
Zasady zwrotu i refundacji
Zasady wysyłki
Gwarancja

Environment

Ambient Air Temperature For Operation
-2-70 °C
Standards
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Product Certifications
UL || CSA || NOM
Ip Degree Of Protection
front cover IP40
Pollution Degree
3 IEC 60947-1
Ambient Air Temperature For Storage
-50-85 °C
Quality Labels
CE
Operating Altitude
< 6561.68 ft (2000 m) without derating || 5000 m with derating

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP2206031EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI2206031EN
Eu Rohs Directive
Compliant with Exemptions

Complementary

Mounting Mode
unit mount lug)
Network Frequency
50/60 Hz
Terminal Identifier
AL175JD
[Ics] Rated Service Breaking Capacity
65 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 18 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
Trip Unit Technology
thermal-magnetic
Height
191 mm
[Ue] Rated Operational Voltage
600 V AC 50/60 Hz IEC 60947-3
Tightening Torque
25-25 N.m 25-95 mm² (AWG 4...AWG 4/0)
Mounting Support
lug
Breaking Capacity Code
G
Magnetic Tripping Current
1750-1750 A
Local Signalling
switched off (OFF) 1 trip indicator green)
Number Of Slots
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Electrical Connection
lugs, line || lugs, load
Mounting Height
4.5 in
Net Weight
2.4 kg
[Uimp] Rated Impulse Withstand Voltage
8 kV IEC 60947-2
Magnetic Hold Current
875 A
Control Type
toggle
Circuit Breaker Application
HACR rated
Wire Stripping Length
25 mm
Line Rated Current
175-175 A
Utilisation Category
category A
Long Time Pick-Up Adjustment Range
0.25...1 x In
Continuous Current Rating
80 %
Breaking Capacity
65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 20 kA 500 V DC UL 489
[Ui] Rated Insulation Voltage
750 V IEC 60947-2
Suitability For Isolation
yes IEC 60947-2
Communication Interface
Modbus || Ethernet
Poles Description
3P
Protection Type
overload protection || short-circuit protection
Awg Gauge
AWG 4...AWG 4/0 aluminium/copper terminal
Width
104 mm
Depth
86 mm
Phase Connection
BC

Specifications

Product Or Component Type
circuit breaker
Product Name
PowerPact J
Range
PowerPact
Device Application
distribution

Dokumenty

Data Sheet

Pobierz