1 / 1
thumbnail

Opis

Końcówka Serii
This Multi GFP product is a residual current circuit breaker (RCCB). It is a 4P circuit breaker with 40A In rated current, 260mA earth leakage sensitivity and A-SI type protection class. It protects persons against electric shock by direct contact. It also protects installations against fire risks. The tripping upon fault is indicated by a red mechanical status indicator on the front panel. The A-SI type offers enhanced immunity to electrical disturbances. This product is dedicated to original equipment manufacturers (OEM) and control panel builders in indisutrial and tertiary buildings. It is compliant with IEC/EN 61008-1 standard. The (Im/IΔm) rated breaking and making short circuit capacity is 1500A. The (Inc/IΔc) conditional rated short circuit current is 10kA. It has a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 440VAC. The Uimp rated impulse withstand voltage is 6kV. The frequency is 50Hz or 60Hz. It is DIN rail mountable. The width in 9mm pitches is 8. The product colour is light grey (RAL7035). The dimensions are (W) 72mm x (H) 81mm x (D) 60mm. The weight is 0.45kg. According to IEC 60529 standard, the degree of protection is IP20 and IP40 in enclosure. The operating temperature is from -25°C to 60°C. The storage temperature is from -40°C to 70°C.
Country of Origin
ES
Part Number
M9R84440
Tariff Code
85363030
EAN
3606481198549
UNSPSC
39121633
€191.89
net
1
Metody płatności:
Najlepsza oferta od:
DEZaufany dostawca Automa.Net
Dostępność:
11 szt.
W magazynie
Zaktualizowano: 09-11-2024
Szacowany czas dostawy:
Na zapytanie
Stan produktu:
Fabrycznie Nowe, Zapieczętowane
Fabrycznie Nowe, Zapieczętowane - Nowy, nieużywany, nieotwarty, nieuszkodzony przedmiot w oryginalnym opakowaniu zapieczętowanym przez producenta.
Łącznie 157 części w magazynie od 14 dostawców
Bezpieczny proces płatności
Zasady zwrotu i refundacji
Zasady wysyłki
Gwarancja

Dostępne Oferty (14)

M9R84440 product image
Schneider Electric

M9R84440

Stan produktu:
Fabrycznie Nowe, Zapieczętowane
Dostępność:
11 szt.
W magazynie
Zaktualizowano: 09-11-2024
Oferta od:
NLZaufany dostawca Automa.Net
Szacowany czas dostawy:
Na zapytanie
1
€202.31
net
M9R84440 product image
Schneider Electric

M9R84440

Stan produktu:
Fabrycznie Nowe, Zapieczętowane
Dostępność:
11 szt.
W magazynie
Zaktualizowano: 09-11-2024
Oferta od:
ITZaufany dostawca Automa.Net
Szacowany czas dostawy:
Na zapytanie
1
€276.00
net
M9R84440 product image
Schneider Electric

M9R84440

Stan produktu:
Fabrycznie Nowe, Zapieczętowane
Dostępność:
11 szt.
W magazynie
Zaktualizowano: 09-11-2024
Oferta od:
ESZaufany dostawca Automa.Net
Szacowany czas dostawy:
Na zapytanie
1
€288.28
net
M9R84440 product image
Schneider Electric

M9R84440

Stan produktu:
Fabrycznie Nowe, Zapieczętowane
Dostępność:
11 szt.
W magazynie
Zaktualizowano: 09-11-2024
Oferta od:
GBZaufany dostawca Automa.Net
Szacowany czas dostawy:
Na zapytanie
1
£312.66
net
M9R84440 product image
Schneider Electric

M9R84440

Stan produktu:
Fabrycznie Nowe, Zapieczętowane
Dostępność:
11 szt.
W magazynie
Zaktualizowano: 09-11-2024
Oferta od:
FRZaufany dostawca Automa.Net
Szacowany czas dostawy:
Na zapytanie
1
€405.98
net
Oferta z czasem realizacji przez producenta
Wysyłka:Na zapytanie
Najlepsza cena:
€66.44

Environment

Ambient Air Temperature For Operation
-25-60 °C
Tropicalisation
2 IEC 60068-1
Standards
EN/IEC 61008-1 || UL 1053
Product Certifications
IEC || UL || CCC
Electromagnetic Compatibility
8/20 µs impulse withstand, 3000 A EN/IEC 61008-1
Ip Degree Of Protection
IP20 conforming to IEC 60529 || IP40 (modular enclosure) conforming to IEC 60529
Pollution Degree
3
Ambient Air Temperature For Storage
-40-70 °C
Relative Humidity
95-95 % 55-55 °C

Specifications

Line Rated Current
40 A 40 °C EN/IEC 61008-1
Network Type
AC
Earth-Leakage Protection Class
type A-SI (Super Immunised)
Earth-Leakage Sensitivity
260 mA UL 1053 || 300 mA EN/IEC 61008-1
Product Or Component Type
residual current circuit breaker (RCCB)
Product Name
Multi9 GFP
Utilisation Category
AC-23A EN/IEC 61008-1
Range
Multi9
Earth-Leakage Protection Time Delay
instantaneous
Poles Description
4P
Neutral Position
left
Device Application
distribution
Device Short Name
GFP

Complementary

Network Frequency
50/60 Hz
Height
81 mm
Contact Position Indicator
yes
Locking Options Description
padlocking in OFF position
Mounting Support
DIN rail
9 Mm Pitches
8
Connections - Terminals
tunnel type terminals top or bottom) 1-25 mm² AWG 18...AWG 3) - flexible || tunnel type terminals top or bottom) 1-35 mm² AWG 18...AWG 2) - rigid || tunnel type terminals top or bottom) 1-25 mm² AWG 18...AWG 3) - flexible with ferrule
Net Weight
0.45 kg
Wire Stripping Length
14 mm for top or bottom connection
Control Type
toggle
Residual Current Tripping Technology
voltage independent
[Ui] Rated Insulation Voltage
440 V AC 50/60 Hz
Mounting Mode
clip-on
Rated Breaking And Making Capacity
Idm 1500 A EN/IEC 61008-1
Mechanical Durability
20000 cycles
Local Signalling
ON, OFF, fault trip
[Uimp] Rated Impulse Withstand Voltage
6 kVEN/IEC 61008-1
Color
Gray
Width
72 mm
Depth
60 mm
Tightening Torque
3.5-3.5 N.m top or bottom
Rated Conditional Short-Circuit Current
Inc 10 kA 100 A gG
[Ue] Rated Operational Voltage
415 V AC 50 Hz || 480Y/277 V AC 60 Hz

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP2301023EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
N/A
Eu Rohs Directive
Compliant with Exemptions