This Vigi C60 is a modular add-on residual current devices. It is a 2P and rated current is 63A. The earth leakage protection class is AC type with a sensitivity of 30mA and a voltage independent technology. This product protects against short circuit, cable overload, electrical shock by indirect contact and fire hazards. This product is compliant with EN/IEC 61009-1 and EN/IEC 61009-2-1 standard. The Ue rated operational voltage is 230VAC or 240VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 4kV. The pollution degree is 3. It can be mounted on DIN rail. The width in 9mm pitches is 4. The product color is light grey (RAL7035). The dimensions are (W) 36mm x (H) 87mm x (D) 74mm. The weight is 150g. The degree of protection is IP20 and IP40 in an enclosure. The operating temperature is -5°C to 60°C. The storage temperature is -40°C to 60°C.- Country of Origin
- FR
- Part Number
- M9V11263
- Tariff Code
- 85362090
- EAN
- 3606480684548
- UNSPSC
- 39121633
- Termin płatności do 90 dni od 500+ dostawców.
- Rabaty na odsprzedaż do 40%!
Wyślij zapytanie o cenę
1
Metody płatności:
Environment
- Ambient Air Temperature For Operation
- -5-60 °C
- Tropicalisation
- 2 IEC 60068-1
- Standards
- EN/IEC 61009-1 || EN/IEC 61009-2-1
- Electromagnetic Compatibility
- 8/20 µs impulse withstand, 250 A EN/IEC 61009-1
- Ip Degree Of Protection
- IP20 conforming to IEC 60529 || IP40 (modular enclosure) conforming to IEC 60529
- Pollution Degree
- 3 IEC 61009
- Ambient Air Temperature For Storage
- -40-60 °C
- Relative Humidity
- 95-95 % 55-55 °C
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP1409017EN
- Sustainable Offer Status
- Green Premium product
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- N/A
- Eu Rohs Directive
- Compliant with Exemptions
- Halogen Content Performance
- Halogen free plastic parts product
Complementary
- Height
- 87 mm
- Mounting Support
- DIN rail
- Connections - Terminals
- tunnel type terminal bottom) 1-35 mm² - rigid || tunnel type terminal bottom) 1-25 mm² - flexible || tunnel type terminal bottom) 1-25 mm² - flexible with ferrule
- Net Weight
- 150 g
- Wire Stripping Length
- 14 mm for bottom connection
- Electrical Connection To Mcb
- by screws
- Residual Current Tripping Technology
- voltage independent
- [Ui] Rated Insulation Voltage
- 500 V AC 50 Hz EN/IEC 61009-1
- Mounting Mode
- clip-on
- Local Signalling
- fault indication
- [Uimp] Rated Impulse Withstand Voltage
- 4 kVEN/IEC 61009-1
- Color
- Gray
- Width
- 36 mm
- Depth
- 74 mm
- Tightening Torque
- 3.5-3.5 N.m bottom
Specifications
- Network Frequency
- 50 Hz
- Line Rated Current
- 63 A EN/IEC 61009-1
- Network Type
- AC
- Range Compatibility
- Multi9 Multi9 C60 C60N || Multi9 Multi9 C60 C60L || Multi9 Multi9 C60 C60H || Multi9 Multi9 C60 C60CTRL
- 9 Mm Pitches
- 4
- Earth-Leakage Protection Class
- type AC
- Earth-Leakage Sensitivity
- 30 mA EN/IEC 61009-1
- Product Or Component Type
- add-on residual current devices
- Range
- Multi9
- Earth-Leakage Protection Time Delay
- instantaneous
- Poles Description
- 2P
- Device Short Name
- Vigi C60
- [Ue] Rated Operational Voltage
- 230/240 V AC 50 Hz
Inne kategorie
SiłownikiBlokiKable, rury i wężeSprężarkiSterowanieŁączniki i osprzętCylindry i tłokiElektronikaFiltryHVACKomputery przemysłowe i interfejsy HMIOświetlenieTechnika liniowaSilnikiZasilaniePrzeniesienie napęduPompy i zaworyEnergia odnawialnaRobotykaUszczelki, pierścienie i złączaCzujniki i urządzenia pomiaroweNarzędzia i akcesoriaCNCInne