1 / 1
thumbnail

Opis

Końcówka Serii
The EM3500 series offer a three-phases DIN rail-mounted energy meters fitted for accurate cost allocation and sub-metering. EM35xx models are designed for use with Low Votage Current Transducers 1/3Volt or 1Volt output. Current input from 5A to 32000A, according to the LVCT configuration in the HMI, ANSI C12.20 0.2% accuracy, IEC 62053-22 class 0.2S. The data logging capability protects data in the event of a power failure. Modbus, pulse output, and phase alarms are all provided to suit a wide variety of applications. This model add a bi-directional monitoring feature designed expressly for renewable energy applications. Suitable for a 230V AC network, with a supply voltage range of 90V AC to 300V AC at 50Hz or 60Hz. Compliant with UL508, CSA 22.2 number 14-05 and EN 61010-1. Product dimensions are as follows: width 107 mm, depth 59 mm, height 91 mm.
Country of Origin
US
Part Number
METSEEM3555
Tariff Code
9028300000
EAN
39121108
UPC
785901488514
UNSPSC
39121108
  • Termin płatności do 90 dni od 500+ dostawców.
  • Rabaty na odsprzedaż do 40%!
Zarejestruj się
Wyślij zapytanie o cenę
1
Metody płatności:
Poproś o wycenę, a prześlemy Ci informacje o dostępności i cenie.

Complementary

Network Frequency
60 Hz || 50 Hz
Communication Port Support
screw terminal block RS485
[Ue] Rated Operational Voltage
90...347 V AC 50/60 Hz between phase and neutral UL || 156...600 V AC 50/60 Hz between phases UL || 90...300 V AC 50/60 Hz between phase and neutral CE || 125...300 V DC
Standards
CSA C22.2 No 14-05 || UL 508 || IEC 61010-1
Number Of Outputs
1 alarm output || 1 pulse
Mounting Support
DIN rail
Power Consumption In Va
5-5 VA 347 V AC between phase and neutral) || 5-5 VA 600 V AC between phases)
Product Certifications
CE IEC 61010 || cULus UL 508
Type Of Measurement
active and reactive power total || active and reactive power per phase || apparent power total || apparent power per phase || power factor total || power factor per phase || peak demand power || current || voltage || frequency
Communication Port Protocol
Modbus RTU 1200…38400 bps - 2-wire
Communication Service
total cumulated active energy || total cumulated energy
Ride-Through Time
100 ms 120 V AC
Display Digits
5
Communication Of Data
instantaneous and demand values || lifetime energy production
Tamperproof Of Settings
protected by access code
Measurement Current
5-32000 A
Information Displayed
status and alert || communication with system || input/output status || error || Tx activity || Rx activity || instant power per usage
Function Available
external synchronisation to communication || fixed or rolling block
Mounting Mode
clip-on || by screws
Local Signalling
Red LED threshold reached || Green flashing LED output signal
Power Consumption In W
3 W 300-300 V
Measurement Accuracy
power +/- 0.2 % || energy +/- 0.2 %
Technology Type
electronic
Buffer Size
16-bit 10
Poles Description
3P + N
Data Recording
energy consumption logs || time stamping
Analogue Input Type
split core current transducer 0.333 V or 1 V
Display Type
Backlit LCD
Device Application
partial meter || sub billing
Accuracy Class
class 0.2S power IEC 62053-22 || class 0.2S energy IEC 62053-22 || class 0.2S power ANSI C12.20 || class 0.2S energy ANSI C12.20
Rated Voltage
90-347 V

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
X
Eu Rohs Directive
Compliant with Exemptions

Specifications

Product Or Component Type
energy meter
Product Name
PowerLogic EM3500
Range
PowerLogic
Device Short Name
EM3555
Metering Type
peak demand power PM, QM, SM || current I1, I2, I3, Iavg || active, reactive, apparent energy (signed, four quadrant) || demand power P, Q, S || voltage U21, U32, U13, V1, V2, V3

Environment

Ambient Air Temperature For Operation
-30-70 °C
Height
91 mm
9 Mm Pitches
12
Color
dark grey
Ambient Air Temperature For Storage
-40-85 °C
Relative Humidity
0-95 %
Width
107 mm
Depth
59 mm

Dokumenty

Data Sheet

Pobierz