- Power Consumption In W
- 1.5 W 240 V DC || 0.6 W 24 V DC
- Contacts Type And Composition
- 2 C/O timed contact, cadmium free || 1 C/O timed and instantaneous contact, cadmium free
- Discrete Output Type
- relay
- Setting Accuracy Of Time Delay
- +/- 1 % 1...999 h 25 °C || +/- 2 % 1...3600 s 25 °C || +/- 20 ms 100 ms...10 s 25 °C || +/- 30 ms 50...100 ms 25 °C
- Creepage Distance
- 4 kV/3 IEC 60664-1
- Maximum Delay Response
- 100 ms
- Insulation Resistance
- 100 MOhm 500 V DC IEC 60664-1
- Nominal Power
- 0.0002 mW
- Power Consumption In Va
- 3-3 VA 240 V AC
- Switching Capacity In Va
- 2000 VA
- Minimum Pulse Duration
- 100 ms with load in parallel || 60 ms no-load
- Maximum Switching Current
- 8 A
- Function Available
- A- Power on-delay relay-2 C/O || Ac- On-delay and off-delay relay w/ control signal-2 C/O || Ad- Pulse delayed relay w/ control signal-2 C/O || Ah- Pulse delayed relay (single cycle) w/ control signal-2 C/O || Ak- Asymmetrical on-delay and off -delay relay w/ control signal-2 C/O || At- Power on-delay relay w/ pause/summation (Y1)-2 C/O || B- Single interval relay w/ control signal-2 C/O || Bw- Double interval relay w/ control signal-2 C/O || C- Off-delay relay w/ control signal-2 C/O || D- Symmetrical flashing relay (starting pulse-off)-2 C/O || Di- Symmetrical flashing relay (starting pulse-on)-2 C/O || Dt- Symmetrical flashing relay (starting pulse-off) w/ pause/summation (Y1)-2 C/O || Dit- Symmetrical flashing relay (starting pulse-on) w/ pause/summation (Y1)-2 C/O || H- Interval relay-2 C/O || Ht- Interval relay w/ pause/summation (Y1)-2 C/O || Li- Asymmetrical flashing relay (starting pulse-on)-2 C/O || Lt- Asymmetrical fl ashing relay (starting pulse-off) w/ pause/summation (Y1)-2 C/O || Lit- Asymmetrical flashing relay (starting pulse-on) w/ pause/summation (Y1)-2 C/O || N- Safe-guard relay-2 C/O || O- Delayed Safe-guard relay-2 C/O || P- Pulse delayed relay w/ fixed pulse length-2 C/O || Pt- Pulse delayed relay w/ fixed pulse length and pause/summation-2 C/O || Qt- Star-delta relay (2 CO outputs w/ split common)-2 C/O || Qtt- Star-delta relay (2 CO outputs w/ split common) w/ pause/summation (Y1)-2 C/O || TI- Bistable relay w/ control signal on-2 C/O || Tt- Retriggerable bistable relay w/ control signal on-2 C/O || W- Interval relay w/ control signal off-2 C/O || L- Asymmetrical flashing relay (starting pulse-off)-2 C/O
- Operating Distance
- 10 mm
- Voltage Range
- 0.85...1.1 Un
- Local Signalling
- Un, green LED steady)power ON || R1, amber LED steady)relay energised || R2, amber LED steady)relay energised || pairing, green LED steady)communication status || Un, green LED fast blinking)diagnosis mode || R1, amber LED blinking)timing in progress || R2, amber LED blinking)timing in progress
- Net Weight
- 0.0904 kg
- [Uimp] Rated Impulse Withstand Voltage
- 5 kV 1.2/50 µs IEC 60664-1
- Voltage Drift
- +/- 0.2 %/V
- Reset Time
- 120 ms on de-energisation
- Maximum Switching Voltage
- 250 V
- Connections - Terminals
- screw terminals, 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
- [Us] Rated Supply Voltage
- 24...240 V AC/DC
- Temperature Drift
- +/- 0.05 %/°C
- Time Delay Range
- 0.05 s...999 h
- Minimum Switching Current
- 10 mA 5 V
- Overvoltage Category
- III IEC 60664-1
- Input Voltage
- <= 2.4 V
- Mounting Support
- 35 mm DIN rail conforming to IEC 60715
- Nominal Output Current
- 8 A
- Electrical Durability
- 100000 cycles for resistive load, 8 A at 250 V, AC
- Mechanical Durability
- 10000000 cycles
- Housing Material
- self-extinguishing
- Safety Reliability Data
- MTTFd = 227.5 years 100 % duty cycle continuous operating condition at 30 °C
- Mounting Position
- any position
- Width
- 22.5 mm
- Time Delay Type
- power on-delay || on-delay and off-delay || pulse delay || asymmetrical on-delay and off-delay || interval || off-delay || symmetrical flashing || safe-guard || star-delta || asymmetrical flashing || bistable
- Product Compatibility
- NFC enabled mobile device
- Tightening Torque
- 0.6-1 N.m IEC 60947-1 || 5.3-8.8 lbf.in IEC 60947-1
- Maximum Operating Frequency
- 13.56 MHz
- Supply Frequency
- 50...60 Hz +/- 5 %
- Repeat Accuracy
- +/- 0.2 % 10 s...999 h || +/- 0.5 % 100 ms...10 s || +/- 0.7 % 50...100 ms