Schneider Electric
RM35JA32MW
1 / 6
Opis
Końcówka Serii
This Harmony RM35-JA relay allows monitoring of current control in single phase networks. This modular multi function single phase current control relay is ideal for monitoring of electrical values in industrial and building control panels. It applies to a wide type of industrial automation applications such as hoisting, packaging, lifts, textile, water. It has one of market medium form-factors with 35mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 3-pole DIN device. It also offers a sealable cover, simple and precise settings with screw trimmers. It provides automatic shutdown management and fault information to user for a quick fault identification and troubleshooting. multi function controller for wide choice selected in hard-wired logic automated systems, ideal for refurbishment of old installations without using a PLC. 0 0 0 0 0 0 0 0 0 0 0 0- Country of Origin
- ID
- Part Number
- RM35JA32MW
- Tariff Code
- 85364900
- EAN
- 3389119405225
- UNSPSC
- 39122331
€39.00
netDarmowa wysyłka!1
Metody płatności:
- Najlepsza oferta od:
- Zaufany dostawca Automa.Net
- Dostępność:
- 3 szt.W magazynieZaktualizowano: 09-11-2024
- Gwarancja:
- 12 miesięcy
- Szacowany czas dostawy:
- 12-25 listopada do Wielka Brytania
- Stan produktu:
- Nowy, Rynek wtórny
Nowy, Rynek wtórny - Nowy, nieużywany, nieuszkodzony przedmiot bez gwarancji producenta. Przedmiot może być dostarczony bez oryginalnego opakowania lub w zastępczym opakowaniu. Jeśli dostarczono, pudełko mogło zostać otwarte.
Informacje o wysyłce
Bezpieczny proces płatności
Zasady zwrotu i refundacji
Zasady wysyłki
Gwarancja
Environment
- Product Certifications
- GL || UL || GOST || C-tick || CSA
- Standards
- IEC 60255-6
- Immunity To Microbreaks
- 50 ms
- Non-Dissipating Shock Wave
- 4 kV IEC 60255-5 || 4 kV IEC 60664-1 || 4 kV IEC 61000-4-5
- Dielectric Test Voltage
- 2 kV AC 50 Hz, 1 min IEC 60255-5 || 2 kV AC 50 Hz, 1 min IEC 60664-1
- Electromagnetic Compatibility
- emission standard for industrial environments conforming to IEC 61000-6-4 || emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3 || immunity for industrial environments conforming to NF EN/IEC 61000-6-2
- Shock Resistance
- 15 gn 11 ms IEC 60255-21-1
- Ambient Air Temperature For Operation
- -20-50 °C
- Vibration Resistance
- 0.35 mm 5-57.6 Hz)IEC 60068-2-6 || 1 gn 57.6-150 Hz)IEC 60255-21-1
- Ip Degree Of Protection
- IP20 IEC 60529 terminals) || IP30 IEC 60529 casing)
- Pollution Degree
- 3 IEC 60664-1
- Ambient Air Temperature For Storage
- -40-70 °C
- Relative Humidity
- 95-95 % 55-55 °C IEC 60068-2-30
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP1504008EN
- Sustainable Offer Status
- Green Premium product
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- X
- Circularity Profile
- ENVEOLI1504008EN
- Eu Rohs Directive
- Pro-active compliance (Product out of EU RoHS legal scope)
Complementary
- [Us] Rated Supply Voltage
- 24...240 V AC/DC 50/60 Hz +/- 10 %
- Polarity
- no DC
- Safety Reliability Data
- MTTFd = 296.8 years || B10d = 270000
- Maximum Measuring Cycle
- 30 ms measurement cycle as true rms value
- Control Circuit Voltage Limits
- 15 % + 10 % Un
- Hysteresis
- 5-50 % threshold setting
- Insulation Resistance
- > 500 MOhm 500 V DC between supply and relay output IEC 60255-5 || > 500 MOhm 500 V DC between measurement and relay output IEC 60664-1 || > 1 MOhm 500 V DC between supply and measurement IEC 60255-5 || > 500 MOhm 500 V DC between supply and relay output IEC 60664-1 || > 500 MOhm 500 V DC between measurement and relay output IEC 60255-5 || > 1 MOhm 500 V DC between supply and measurement IEC 60664-1
- Measurement Error
- 0.05 %/°C with temperature variation || 1 by volt over the whole range with voltage variation
- Operating Rate
- <= 360 operations/hour full load
- Output Contacts
- 2 C/O
- Contacts Material
- cadmium free
- Marking
- CE : EMC 89/336/EEC || CE : 73/23/EEC
- Operating Position
- any position without derating
- Net Weight
- 0.13 kg
- Threshold Setting
- 10...100 %
- Maximum Switching Voltage
- 250 V AC/DC
- Reset Time
- 1500 ms time delay
- Connections - Terminals
- screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
- [Ui] Rated Insulation Voltage
- 250 V IEC 60664-1
- Overvoltage Category
- III IEC 60664-1
- Supply Voltage Limits
- 20.4-264 V AC/DC
- Mounting Support
- 35 mm symmetrical DIN rail conforming to IEC 60715
- Nominal Output Current
- 5 A
- Local Signalling
- for power ON LED (green) || for relay ON LED (yellow)
- Mechanical Durability
- 30000000 cycles
- Housing Material
- self-extinguishing plastic
- Resistance Across Terminals
- 0.005 Ohm E3-M terminals || 0.015 Ohm E2-M terminals || 0.05 Ohm E1-M terminals
- Control Circuit Frequency
- 40...70 Hz +/- 10 %
- Measurement Accuracy
- +/- 10 % of the full scale value
- Width
- 35 mm
- Tightening Torque
- 0.6-1 N.m IEC 60947-1
- Maximum Power Consumption In W
- 0.6 W DC
- Electrical Durability
- 100000 cycles
- Run-Up Delay At Power-Up
- 0.3 s
- Repeat Accuracy
- +/- 0.5 % input and measurement circuit || +/- 2 % time delay
Specifications
- Minimum Switching Current
- 10 mA 5 V DC
- Maximum Switching Current
- 5 A AC/DC
- Range Of Product
- Harmony Control Relays
- Measurement Range
- 0.15...1.5 A E1-M terminals || 0.5...5 A E2-M terminals || 1.5...15 A E3-M terminals || 150 mA...15 A current
- Switching Capacity In Va
- 1250 VA
- Product Or Component Type
- current control relay
- Utilisation Category
- AC-12 IEC 60947-5-1 || AC-13 IEC 60947-5-1 || AC-14 IEC 60947-5-1 || AC-15 IEC 60947-5-1 || DC-12 IEC 60947-5-1 || DC-13 IEC 60947-5-1 || DC-14 IEC 60947-5-1
- Relay Name
- RM35JA
- Contacts Type And Composition
- 2 C/O
- Relay Type
- current control relay
- Time Delay Type
- adjustable 1...20 s, 0 + 10 % on energisation Ti || adjustable 0.3...30 s, 0 + 10 % on crossing the threshold Tt
- Relay Monitored Parameters
- overcurrent or undercurrent detection
- Maximum Power Consumption In Va
- 3.5 VA AC
Modele CAD
traceparts
PobierzInne kategorie
SiłownikiBlokiKable, rury i wężeSprężarkiSterowanieŁączniki i osprzętCylindry i tłokiElektronikaFiltryHVACKomputery przemysłowe i interfejsy HMIOświetlenieTechnika liniowaSilnikiZasilaniePrzeniesienie napęduPompy i zaworyEnergia odnawialnaRobotykaUszczelki, pierścienie i złączaCzujniki i urządzenia pomiaroweNarzędzia i akcesoriaCNCInne