Motor starter, TeSys island, 80A at AC-1, 65A at AC-3, 30kW, 40hp, DOL type
TPRST065
  • Termin płatności do 90 dni od 500+ dostawców.
  • Rabaty na odsprzedaż do 40%!
Zarejestruj się
€125.02
1
Metody płatności:
Łącznie 28 części w magazynie od 20 dostawców
Oferta z czasem realizacji przez producenta
Wysyłka:1 - 2 Dni robocze
Najlepsza cena:
€151.43

Additional Information

Part Number
TPRST065
UNSPSC
39121521
Tariff Code
8536504000

Environment

Ambient Air Temperature For Operation
-10-50 °C without derating || 50-60 °C with current derating
Shock Resistance
15 gn 11 ms) IEC 60068-2-27
Vibration Resistance
1.5 mm peak to peak 3-13 Hz) IEC 60068-2-6 || 1 gn 13-200 Hz) IEC 60068-2-6
Electromagnetic Compatibility
electrostatic discharge immunity test, level 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 || radiated RF field immunity test, level 3, 10 V/m, conforming to EN/IEC 61000-4-3 || fast transient immunity test, level 4, 4 kV, conforming to EN/IEC 61000-4-4 || surge immunity test (differential mode), level 3, 2 kV, conforming to EN/IEC 61000-4-5 || surge immunity test (common mode), level 4, 4 kV, conforming to EN/IEC 61000-4-5 || conducted RF disturbance immunity test, 20 V, conforming to EN/IEC 61000-4-6
Pollution Degree
2
Ambient Air Temperature For Storage
-25-70 °C
Protective Treatment
TC
Relative Humidity
5-95 %
Ip Degree Of Protection
IP20
Operating Altitude
0...6561.68 ft (0...2000 m) without derating
Fire Resistance
960 °C UL 94 || 850 °C IEC 60695-2-1 || 650 °C IEC 60695-2-12

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1904009EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI1904009EN
Eu Rohs Directive
Compliant with Exemptions
Halogen Content Performance
Halogen free plastic parts product

Complementary

Mounting Mode
horizontal and vertical 35 mm symmetrical DIN rail)
Height
167 mm
Product Certifications
CSA || UL || EAC || CCC
Safety Reliability Level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Standards
EN/IEC 60947-1 || EN/IEC 60947-4-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1
Connections - Terminals
EverLink BTR screw connectors 1 1-35 mm² AWG 16...AWG 2)rigid || EverLink BTR screw connectors 2 1-25 mm² AWG 16...AWG 4)rigid || EverLink BTR screw connectors 1 1-35 mm² AWG 16...AWG 2)flexible without cable end || EverLink BTR screw connectors 2 1-25 mm² AWG 16...AWG 4)flexible without cable end || EverLink BTR screw connectors 1 1-35 mm² AWG 16...AWG 2)flexible with cable end || EverLink BTR screw connectors 2 1-25 mm² AWG 16...AWG 4)flexible with cable end
Net Weight
1.248 kg
Metering Type
time device ON || time device switch ON || number of faults || number of switching cycles || number of device power cycles || average current Iavg || average voltage Vavg || max current Imax || max voltage Vmax || active and reactive power with voltage module || active and reactive energy with voltage module || true power factor with voltage module
Maximum Operating Rate
3600 cyc/mn AC-3
Local Signalling
for DS (device status) 1 LED (green/red) || for LS (load status) 1 LED (green/red)
Electrical Durability
1.4 Mcycles 65 A AC-3 440 V || 0.5 Mcycles 80 A AC-1 440 V
Mechanical Durability
6 Mcycles
Operating Time
< 80 ms closing || < 80 ms opening
Width
55 mm
Depth
125 mm
Tightening Torque
5-5 N.m 1-25 mm² hexagonal 4 mm || 8-8 N.m 25-35 mm² hexagonal 4 mm
Protection Type
thermal overload protection || motor overheat || overcurrent || undercurrent || jam || long start || stall || rapid cycle lockout || phase sequence || rapid restart lockout || phase reversal || phase loss || phase unbalance || ground current

Specifications

Current Consumption
80 mA contactor sealed || 500 mA contactor closing
Power Dissipation In W
20.8 W at Ie AC-3
Power Dissipation Per Pole
6.3 W AC-3 - Ith 65 A || 9.6 W AC-1 - Ith 80 A
Average Impedance
1.5 mOhm - Ith 80 A 50 Hz
Reset
remotely or automatically
[Ith] Conventional Free Air Thermal Current
80 A (at 50 °C)
[Uc] Control Circuit Voltage
24 V DC supplied by the bus coupler
Rated Breaking Capacity
1000 A at 440 V conforming to IEC 60947
Product Or Component Type
motor starter
Irms Rated Making Capacity
1000 A at 440 V conforming to IEC 60947
Product Name
TeSys island
Thermal Overload Class
class 5…30
[Uimp] Rated Impulse Withstand Voltage
6 kV IEC 60947-1
Range
TeSys
Device Presentation
direct starter connected to an automation controller through a bus coupler || operational only when connected to a bus coupler
Motor Starter Type
direct on line
Utilisation Category
AC-1 || AC-2 || AC-3 || AC-4
Function Available
upstream voltage presence detection || electrical line and load protection || power and energy monitoring when connected with TPRVM voltage module
[Ie] Rated Operational Current
65 A (at <50 °C) at <= 440 V AC-3 || 80 A (at <50 °C) at <= 440 V AC-1
Overvoltage Category
III
Thermal Protection Adjustment Range
3.35-65 A
Product Compatibility
TPRBC bus coupler || TPRVM voltage interface module
[Ue] Rated Operational Voltage
<= 690 V AC 47...63 Hz
Maximum Horse Power Rating
5 hp at 120 V AC 60 Hz for 1 phase motors || 10 hp at 240 V AC 60 Hz for 1 phase motors || 20 hp at 208 V AC 60 Hz for 3 phase motors || 20 hp at 240 V AC 60 Hz for 3 phase motors || 40 hp at 480 V AC 60 Hz for 3 phase motors || 50 hp at 600 V AC 60 Hz for 3 phase motors
Motor Power Kw
18.5 kW at 230 V 50 Hz (AC-3) || 30 kW at 380...415 V 50 Hz (AC-3) || 30 kW at 440 V 50 Hz (AC-3) || 37 kW at 500 V 50 Hz (AC-3) || 37 kW at 690 V 50 Hz (AC-3)
[Ui] Rated Insulation Voltage
690 V IEC 60947-4-1 || 600 V UL 60947-4-1 || 600 V CSA C22.2 No 60947-4-1
Device Short Name
TPRST
Poles Description
3P 3 NO
[Icw] Rated Short-Time Withstand Current
900 A 40 °C - 1 s || 520 A 40 °C - 10 s || 260 A 40 °C - 1 min || 110 A 40 °C - 10 min

Dokumenty

Data Sheet

Pobierz

Modele CAD

Części śladowe
Części śladowe
Pobierz

Powiązane produkty