IEC contactor, TeSys Deca, nonreversing, 80A resistive, 4 pole, 2 NO and 2 NC, 230VAC 50/60Hz coil, open style
LC1D65008P7
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
£244.20
1
Payment methods:
A total of 25 Parts In-Stock from 24 Distributors

Additional Information

Part Number
LC1D65008P7
UNSPSC
39121529
Tariff Code
8536490065
Country of Origin
CZ

Environment

Product Certifications
DNV || GL || LROS (Lloyds register of shipping) || BV || GOST || CCC || RINA || CSA || UL
Height
127 mm
Standards
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
Climatic Withstand
IACS E10 exposure to damp heat
Net Weight
1.45 kg
Flame Retardance
V1 conforming to UL 94
Protective Treatment
THIEC 60068-2-30
Ip Degree Of Protection
IP20 front face IEC 60529
Mechanical Robustness
shocks contactor open 8 Gn for 11 ms) || shocks contactor closed 10 Gn for 11 ms) || vibrations contactor opened 2 Gn, 5...300 Hz) || vibrations contactor closed 3 Gn, 5...300 Hz)
Operating Altitude
0...9842.52 ft (0...3000 m)
Fire Resistance
850 °C IEC 60695-2-1
Width
85 mm
Depth
125 mm
Permissible Ambient Air Temperature Around The Device
-40-60 °C || 60-70 °C with derating

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP110205EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Toxic Heavy Metal Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Pro-active China RoHS declaration (out of China RoHS legal scope)
Circularity Profile
N/A
Eu Rohs Directive
Compliant

Complementary

Power Dissipation Per Pole
9.6 W AC-1
Average Impedance
1.5 mOhm - Ith 80 A 50 Hz for power circuit
[Ith] Conventional Free Air Thermal Current
80 A (at 60 °C) for power circuit
Control Circuit Voltage Limits
0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz
Mounting Support
rail || plate
Contact Compatibility
M1
Control Circuit Type
AC 50/60 Hz
Safety Reliability Level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Pollution Degree
3
Rated Breaking Capacity
1000 A at 440 V for power circuit conforming to IEC 60947
Irms Rated Making Capacity
1000 A at 440 V for power circuit conforming to IEC 60947
Associated Fuse Rating
125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit
Inrush Power In Va
140-140 VA 60 Hz cos phi 0.75 (at 20 °C) || 160-160 VA 50 Hz cos phi 0.75 (at 20 °C)
[Uimp] Rated Impulse Withstand Voltage
6 kV IEC 60947
Pole Contact Composition
2 NO + 2 NC
Connections - Terminals
control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end || power circuit: screw clamp terminals 1 1-35 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 2 1-25 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 1 1-35 mm² - cable stiffness: flexible with cable end || power circuit: screw clamp terminals 2 1-25 mm² - cable stiffness: flexible with cable end || power circuit: screw clamp terminals 1 1-35 mm² - cable stiffness: solid without cable end || power circuit: screw clamp terminals 2 1-25 mm² - cable stiffness: solid without cable end
Coil Technology
without built-in suppressor module
Operating Time
4...19 ms opening || 12...26 ms closing
Maximum Operating Rate
3600 cyc/h 60 °C
Tightening Torque
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m screw clamp terminals 25-35 mm² hexagonal 4 mm || power circuit 5 N.m screw clamp terminals 1-25 mm² hexagonal 4 mm || control circuit 1.7 N.m screw clamp terminals pozidriv No 2
Electrical Durability
1.4 Mcycles 80 A AC-1 <= 440 V
Mechanical Durability
6 Mcycles
Compatibility Code
LC1D
Hold-In Power Consumption In Va
13-13 VA 60 Hz cos phi 0.3 (at 20 °C) || 15-15 VA 50 Hz cos phi 0.3 (at 20 °C)
Overvoltage Category
III
[Ui] Rated Insulation Voltage
power circuit 600 V CSA || power circuit 600 V UL || power circuit 690 V IEC 60947-4-1
[Icw] Rated Short-Time Withstand Current
640 A 40 °C - 10 s for power circuit || 900 A 40 °C - 1 s for power circuit || 110 A 40 °C - 10 min for power circuit || 260 A 40 °C - 1 min for power circuit
Heat Dissipation
4-5 W at 50/60 Hz
Protective Cover
without

Specifications

[Uc] Control Circuit Voltage
230 V AC 50/60 Hz
[Ue] Rated Operational Voltage
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Range Of Product
TeSys Deca
Contactor Application
resistive load
Product Or Component Type
contactor
Range
TeSys
Utilisation Category
AC-1
[Ie] Rated Operational Current
80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
Poles Description
4P
Device Short Name
LC1D

Documents

Data Sheet

Download

CAD Models

Trace parts
Trace parts
Download

Related products