Additional Information

Part Number
LC2D80U7
UNSPSC
39121529
Tariff Code
8536490065
Country of Origin
CZ

Specifications

Product Certifications
UL || CSA || RINA || GOST || CCC || DNV || LROS (Lloyds register of shipping) || GL || BV || UKCA
Interlocking Type
mechanical
[Uc] Control Circuit Voltage
240 V AC 50/60 Hz
[Ue] Rated Operational Voltage
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Power Dissipation Per Pole
12.5 W AC-1 || 5.1 W AC-3 || 5.1 W AC-3e
Average Impedance
0.8 mOhm - Ith 125 A 50 Hz power circuit
Auxiliary Contact Composition
1 NO + 1 NC
[Ith] Conventional Free Air Thermal Current
10 A 60 °C signalling circuit || 125 A 60 °C power circuit
Mounting Support
rail || plate
Control Circuit Type
AC 50/60 Hz
Standards
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
Safety Reliability Level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Contactor Application
resistive load || motor control
Rated Breaking Capacity
1100 A 440 V power circuit IEC 60947
Product Or Component Type
reversing contactor
Irms Rated Making Capacity
140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 1100 A 440 V power circuit IEC 60947
Product Name
TeSys Deca
Associated Fuse Rating
10 A gG signalling circuit IEC 60947-5-1 || 200 A gG <= 690 V type 1 power circuit || 160 A gG <= 690 V type 2 power circuit
[Uimp] Rated Impulse Withstand Voltage
8 kV IEC 60947
Connections - Terminals
control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid || control circuit screw clamp terminals 2 1-4 mm²solid || control circuit screw clamp terminals 1 1-2.5 mm²flexible with cable end || power circuit connector 1 4-50 mm²flexible without cable end || power circuit connector 2 4-25 mm²flexible without cable end || power circuit connector 1 4-50 mm²flexible with cable end || power circuit connector 2 4-16 mm²flexible with cable end || power circuit connector 1 4-50 mm²solid || power circuit connector 2 4-25 mm²solid
Range
TeSys
Pole Contact Composition
3 NO
Device Presentation
preassembled with reversing power busbar
Utilisation Category
AC-1 || AC-3 || AC-3e || AC-4
[Ie] Rated Operational Current
125 A 60 °C) <= 440 V AC AC-1 power circuit || 80 A 60 °C) <= 440 V AC AC-3 power circuit || 80 A 60 °C) <= 440 V AC AC-3e power circuit || 55 A 60 °C) <= 400 V AC AC-4 power circuit
Maximum Operating Rate
3600 cyc/h 60 °C
Tightening Torque
control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector flat Ø 6 to Ø 8 mm || power circuit 12 N.m connector hexagonal 4 mm
Electrical Durability
0.8 Mcycles 125 A AC-1 <= 440 V || 1.5 Mcycles 80 A AC-3 <= 440 V || 1.5 Mcycles 80 A AC-3e
Mechanical Durability
4 Mcycles
Poles Description
3P
Operating Time
20...35 ms closing || 6...20 ms opening
Overvoltage Category
III
Motor Power Kw
22 kW 220...230 V AC 50 Hz || 37 kW 380...400 V AC 50 Hz || 45 kW 415...440 V AC 50 Hz || 55 kW 500 V AC 50 Hz || 45 kW 660...690 V AC 50 Hz
Maximum Horse Power Rating
20 hp 200/208 V at AC 60 Hz for 3 phase || 7.5 hp 115 V at AC 60 Hz for 1 phase || 15 hp 230/240 V at AC 60 Hz for 1 phase || 25 hp 230/240 V at AC 60 Hz for 3 phase || 60 hp 460/480 V at AC 60 Hz for 3 phase || 60 hp 575/600 V at AC 60 Hz for 3 phase
[Ui] Rated Insulation Voltage
power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL || power circuit 1000 V IEC 60947-4-1
Device Short Name
LC2D
[Icw] Rated Short-Time Withstand Current
135 A 40 °C - 10 min power circuit || 320 A 40 °C - 1 min power circuit || 640 A 40 °C - 10 s power circuit || 990 A 40 °C - 1 s power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
Protective Cover
with

Contractual warranty

Warranty
18 months

Complementary

Non-Overlap Time
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Minimum Switching Current
5 mA signalling circuit
Control Circuit Voltage Limits
0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-55 °C operational AC 50 Hz || 0.85...1.1 Uc -40-55 °C operational AC 60 Hz || 1...1.1 Uc 55-70 °C operational AC 50/60 Hz
Insulation Resistance
> 10 MOhm signalling circuit
Inrush Power In Va
245-245 VA 60 Hz 0.75 20 °C) || 245-245 VA 50 Hz 0.75 20 °C)
Coil Technology
without built-in suppressor module
Minimum Switching Voltage
17 V signalling circuit
Signalling Circuit Frequency
25...400 Hz
Auxiliary Contacts Type
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Hold-In Power Consumption In Va
26-26 VA 60 Hz 0.3 20 °C) || 26-26 VA 50 Hz 0.3 20 °C)
Heat Dissipation
6-10 W 50/60 Hz

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP110205EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Toxic Heavy Metal Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Pro-active China RoHS declaration (out of China RoHS legal scope)
Eu Rohs Directive
Compliant

Environment

Mechanical Robustness
vibrations contactor open2 Gn, 5...300 Hz || shocks contactor open8 Gn for 11 ms || vibrations contactor closed3 Gn, 5...300 Hz || shocks contactor closed10 Gn for 11 ms
Ambient Air Temperature For Operation
-40-60 °C || 60-70 °C with derating
Height
127 mm
Climatic Withstand
IACS E10
Pollution Degree
3
Net Weight
3.2 kg
Flame Retardance
V1 conforming to UL 94
Ambient Air Temperature For Storage
-60-80 °C
Protective Treatment
TH IEC 60068-2-30
Ip Degree Of Protection
IP20 front face IEC 60529
Operating Altitude
0...9842.52 ft (0...3000 m)
Fire Resistance
850 °C IEC 60695-2-1
Width
182 mm
Depth
158 mm