RENF22R2MMW

multifunction relay, Harmony Timer Relays, 8A, 2CO, 0.05s to 999h asymmetrical on delay and off delay 24 to 240V AC DC
RENF22R2MMW
RENF22R2MMW
RENF22R2MMW
RENF22R2MMW
RENF22R2MMW
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1401008EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Nickel compounds, which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation
X
Circularity Profile
ENVEOLI1401008EN
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)

Complementary

Power Consumption In W
1.5 W 240 V DC || 0.6 W 24 V DC
Contacts Type And Composition
2 C/O timed contact, cadmium free || 1 C/O timed and instantaneous contact, cadmium free
Discrete Output Type
relay
Setting Accuracy Of Time Delay
+/- 1 % 1...999 h 25 °C || +/- 2 % 1...3600 s 25 °C || +/- 20 ms 100 ms...10 s 25 °C || +/- 30 ms 50...100 ms 25 °C
Creepage Distance
4 kV/3 IEC 60664-1
Maximum Delay Response
100 ms
Insulation Resistance
100 MOhm 500 V DC IEC 60664-1
Nominal Power
0.0002 mW
Power Consumption In Va
3-3 VA 240 V AC
Switching Capacity In Va
2000 VA
Minimum Pulse Duration
100 ms with load in parallel || 60 ms no-load
Maximum Switching Current
8 A
Function Available
A- Power on-delay relay-2 C/O || Ac- On-delay and off-delay relay w/ control signal-2 C/O || Ad- Pulse delayed relay w/ control signal-2 C/O || Ah- Pulse delayed relay (single cycle) w/ control signal-2 C/O || Ak- Asymmetrical on-delay and off -delay relay w/ control signal-2 C/O || At- Power on-delay relay w/ pause/summation (Y1)-2 C/O || B- Single interval relay w/ control signal-2 C/O || Bw- Double interval relay w/ control signal-2 C/O || C- Off-delay relay w/ control signal-2 C/O || D- Symmetrical flashing relay (starting pulse-off)-2 C/O || Di- Symmetrical flashing relay (starting pulse-on)-2 C/O || Dt- Symmetrical flashing relay (starting pulse-off) w/ pause/summation (Y1)-2 C/O || Dit- Symmetrical flashing relay (starting pulse-on) w/ pause/summation (Y1)-2 C/O || H- Interval relay-2 C/O || Ht- Interval relay w/ pause/summation (Y1)-2 C/O || Li- Asymmetrical flashing relay (starting pulse-on)-2 C/O || Lt- Asymmetrical fl ashing relay (starting pulse-off) w/ pause/summation (Y1)-2 C/O || Lit- Asymmetrical flashing relay (starting pulse-on) w/ pause/summation (Y1)-2 C/O || N- Safe-guard relay-2 C/O || O- Delayed Safe-guard relay-2 C/O || P- Pulse delayed relay w/ fixed pulse length-2 C/O || Pt- Pulse delayed relay w/ fixed pulse length and pause/summation-2 C/O || Qt- Star-delta relay (2 CO outputs w/ split common)-2 C/O || Qtt- Star-delta relay (2 CO outputs w/ split common) w/ pause/summation (Y1)-2 C/O || TI- Bistable relay w/ control signal on-2 C/O || Tt- Retriggerable bistable relay w/ control signal on-2 C/O || W- Interval relay w/ control signal off-2 C/O || L- Asymmetrical flashing relay (starting pulse-off)-2 C/O
Operating Distance
10 mm
Voltage Range
0.85...1.1 Un
Local Signalling
Un, green LED steady)power ON || R1, amber LED steady)relay energised || R2, amber LED steady)relay energised || pairing, green LED steady)communication status || Un, green LED fast blinking)diagnosis mode || R1, amber LED blinking)timing in progress || R2, amber LED blinking)timing in progress
Net Weight
0.0904 kg
[Uimp] Rated Impulse Withstand Voltage
5 kV 1.2/50 µs IEC 60664-1
Voltage Drift
+/- 0.2 %/V
Reset Time
120 ms on de-energisation
Maximum Switching Voltage
250 V
Connections - Terminals
screw terminals, 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
[Us] Rated Supply Voltage
24...240 V AC/DC
Temperature Drift
+/- 0.05 %/°C
Time Delay Range
0.05 s...999 h
Minimum Switching Current
10 mA 5 V
Overvoltage Category
III IEC 60664-1
Input Voltage
<= 2.4 V
Mounting Support
35 mm DIN rail conforming to IEC 60715
Nominal Output Current
8 A
Electrical Durability
100000 cycles for resistive load, 8 A at 250 V, AC
Mechanical Durability
10000000 cycles
Housing Material
self-extinguishing
Safety Reliability Data
MTTFd = 227.5 years 100 % duty cycle continuous operating condition at 30 °C
Mounting Position
any position
Width
22.5 mm
Time Delay Type
power on-delay || on-delay and off-delay || pulse delay || asymmetrical on-delay and off-delay || interval || off-delay || symmetrical flashing || safe-guard || star-delta || asymmetrical flashing || bistable
Product Compatibility
NFC enabled mobile device
Tightening Torque
0.6-1 N.m IEC 60947-1 || 5.3-8.8 lbf.in IEC 60947-1
Maximum Operating Frequency
13.56 MHz
Supply Frequency
50...60 Hz +/- 5 %
Repeat Accuracy
+/- 0.2 % 10 s...999 h || +/- 0.5 % 100 ms...10 s || +/- 0.7 % 50...100 ms

Environment

Product Certifications
CE || CSA || KC || UL || CCC || EAC || DNV-GL
Ambient Air Temperature For Operation
-20-60 °C
Standards
IEC 61000-6-1 || IEC 61000-6-2 || IEC 61000-6-4 || EN 61812-1 || IEC 61000-6-3
Immunity To Microbreaks
10 ms
Electromagnetic Compatibility
electrostatic discharge immunity test - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2 || electrostatic discharge immunity test - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2 || fast transients immunity test - test level: 1 kV level 3 (capacitive connecting clip) conforming to IEC 61000-4-4 || fast transients immunity test - test level: 2 kV level 3 (direct contact) conforming to IEC 61000-4-4 || surge immunity test - test level: 1 kV level 3 (differential mode) conforming to IEC 61000-4-5 || surge immunity test - test level: 2 kV level 3 (common mode) conforming to IEC 61000-4-5 || radiated radio-frequency electromagnetic field immunity test - test level: 10 V level 3 (0.15...80 MHz) conforming to IEC 61000-4-6 || electromagnetic field immunity test - test level: 10 V/m level 3 (80 MHz...1 GHz) conforming to IEC 61000-4-3 || immunity to microbreaks and voltage drops - test level: 30 % (500 ms) conforming to IEC 61000-4-11 || immunity to microbreaks and voltage drops - test level: 100 % (20 ms) conforming to IEC 61000-4-11 || radiated emission class B conforming to EN 55022 || conducted emission class A conforming to EN 55022 || electromagnetic field immunity test - test level: 3 V/m level 2 (1.4 GHz...2 GHz) conforming to IEC 61000-4-3 || electromagnetic field immunity test - test level: 1 V/m level 1 (2...2.7 GHz) conforming to IEC 61000-4-3
Dielectric Strength
2.5 kV 1 mA/1 minute 50 Hz between relay output and power supply with basic insulation || basic insulation
Shock Resistance
15 gn not operating 11 ms IEC 60068-2-27 || 5 gn in operation 11 ms IEC 60068-2-27
Vibration Resistance
20 m/s² 10-150 Hz)IEC 60068-2-6
Pollution Degree
3 IEC 60664-1
Directives
2014/35/EU - low voltage directive || 2014/53/EU - radio equipment directive || 2014/30/EU - electromagnetic compatibility
Ambient Air Temperature For Storage
-40-70 °C
Relative Humidity
95-95 % 25-55 °C
Ip Degree Of Protection
housing IP40 IEC 60529 || front face IP40 IEC 60529 || terminals IP20 IEC 60529

Specifications

Range Of Product
Harmony Timer Relays
Software Designation
Zelio NFC downloadable from Google Play store)
Product Or Component Type
multifunction relay
Operating System
Android
Software Version
V4.4 and above
Device Short Name
RENF22

Documents

Data Sheet

Download

CAD Models

Trace parts
Trace parts
Download

Related products