Schneider Electric

XMLK010B2C21TQ

Electronic pressure sensors, Pressure sensors XM, sensor XMLK, 0...10 bar, G 1/4 A, 4...20 mA, DIN, set of 25
XMLK010B2C21TQ
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Offer with manufacturer lead time
Ships in:1 - 2 business days
Best price:
Send request for price

Additional Information

Part Number
XMLK010B2C21TQ
UNSPSC
39122210
Tariff Code
9032200000
Country of Origin
CH

Specifications

Pressure Sensor Type
pressure transmitter
Type Of Output Signal
analogue
Range Of Product
Telemecanique Pressure sensors XM
Electrical Connection
1 male connector EN 175301-803-A (ex DIN43650) 4 pins
Pressure Sensor Size
10-10 bar
Product Or Component Type
electronic pressure sensors
Type Of Packing
group
Local Display
without
Pressure Sensor Name
XMLK
Current Consumption
< 20 mA
Fluid Connection Type
G 1/4A (male) DIN 3852-E
Analogue Output Function
4...20 mA, 2-wire
Controlled Fluid
air 0-80 °C) || fresh water 0-80 °C)
Quantity Per Set
set of 25
Electrical Circuit Type
control circuit
[Us] Rated Supply Voltage
24 V DC SELV 8-33 V)

Contractual warranty

Warranty
18 months

Complementary

Accuracy
0.1 % of the measuring range
Diameter
36 mm
[Uimp] Rated Impulse Withstand Voltage
0.5 kV
Repeat Accuracy
+/- 1 % of the measuring range
Drift Of The Zero Point
+/- 0.03 % of measuring range/°K
Electromagnetic Compatibility
electrostatic discharge immunity test EN/IEC 61000-4-2 8 kV air, 6 kV contact || susceptibility to electromagnetic fields EN/IEC 61000-4-3 10 V/m 80...1000 MHz || electrical fast transient/burst immunity test EN/IEC 61000-4-4 2 kV || 1.2/50 µs shock waves immunity test EN/IEC 61000-4-5 500 V 12 Ohm, 1 kV 42 Ohm || radiated RF fields EN/IEC 61000-4-6 10 V 0.15...80 MHz || immunity to magnetic fields EN/IEC 61000-4-8 30 A/m 50 Hz
Materials In Contact With Fluid
ceramic || nitrile (NBR) || stainless steel type AISI 303
Length
67.5 mm
Net Weight
0.11 kg
Mechanical Durability
10000000 cycles
Operating Position
any position
Measurement Accuracy
+/- 1 % of the measuring range
Protection Type
load short-circuit || reverse polarity
Drift Of The Sensitivity
+/- 0.04 % of measuring range/°K
Maximum Permissible Accidental Pressure
20 bar
Destruction Pressure
30 bar
Response Time On Output
< 5 ms
Pressure Setting Range
0-10 bar

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)

Environment

Product Certifications
UL 508 || EAC || RCM || CSA C22.2 No 14
Ambient Air Temperature For Operation
0-80 °C
Standards
EN/IEC 61326-2-3 || CE
Shock Resistance
25 gn 11 ms EN/IEC 60068-2-27
Vibration Resistance
20 gn 9-2000 Hz) EN/IEC 60068-2-6
Ip Degree Of Protection
IP65 conforming to EN/IEC 60529
Nema Degree Of Protection
NEMA 4
Ambient Air Temperature For Storage
-25-80 °C
Protective Treatment
TC