Pressure sensors XM, pressure sensor XMP, 12 bar, G 3/8 female, 3 NC, without control type
XMPA12C2242
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Offer with manufacturer lead time
Ships in:1 - 2 business days
Best price:
Send request for price

Additional Information

Part Number
XMPA12C2242
UNSPSC
39122210
Tariff Code
9032200000
Country of Origin
CZ

Specifications

Contacts Type And Composition
3 NC snap action
Pressure Sensor Type
electromechanical pressure sensor
Range Of Product
Telemecanique Pressure sensors XM
Pressure Switch Type Of Operation
regulation between 2 thresholds
Cable Entry
2 entries incorporating Pg 13.5 plastic cable gland 9-13 mm NF C 68-300
Local Display
without
Pressure Sensor Name
XMP
Fluid Connection Type
G 3/8 (female) ISO 228
Electrical Connection
screw-clamp terminals minimum : 2 x 4 mm²
Pressure Sensor Size
12 bar
Sale Per Indivisible Quantity
1
Controlled Fluid
air 0-70 °C) || fresh water 0-70 °C) || sea water 0-70 °C)
Scale Type
adjustable differential
Electrical Circuit Type
power circuit

Contractual warranty

Warranty
18 months

Complementary

Repeat Accuracy
3.5 %
Pressure Actuator
diaphragm
Height
106 mm
Terminal Block Type
6 terminals
Terminals Description Iso N°1
(3-4)NC || (5-6)NC || (1-2)NC
Possible Differential Minimum At Low Setting
1 bar
Maximum Operating Rate
10 cyc/mn
Adjustable Range Of Switching Point On Falling Pressure
0.3-10.3 bar
Materials In Contact With Fluid
chromated zinc alloy || canvas covered nitrile
Electrical Durability
1000000 cycles 1.5 kW 10 cyc/mn 0.4 , 400 V AC 3 phase || 500000 cycles 3 kW 10 cyc/mn 0.4 , 400 V AC 3 phase || 600000 cycles 1.5 kW 10 cyc/mn 0.4 , 230 V AC 3 phase || 700000 cycles 2.2 kW 10 cyc/mn 0.4 , 400 V AC 3 phase
Net Weight
0.43 kg
[Uimp] Rated Impulse Withstand Voltage
6 kV EN/IEC 60947-1
Control Type
Without
[Ui] Rated Insulation Voltage
500 V EN/IEC 60947-1
Adjustment Range High Setting
1.3-12 bar
Setting
knurled knob and nut
Type Of Decompression Valve
without
Mechanical Durability
1000000 cycles
Operating Position
any position
Enclosure Material
PA impregnated with fibreglass
Possible Differential Minimum At High Setting
1.7 bar
Width
57 mm
Depth
98 mm
Possible Differential Maximum At High Setting
8.4 bar
Destruction Pressure
30 bar
Maximum Resistance Across Terminals
25 MOhm IEC 60255-7 category 3 || 25 MOhm NF C 93-050 method A

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP111130EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)

Environment

Product Certifications
EAC
Ambient Air Temperature For Operation
-25-70 °C
Standards
EN/IEC 60947-4-1 || CE
Vibration Resistance
3 gn 10-500 Hz)IEC 60068-2-6
Shock Resistance
50 gn IEC 60068-2-27
Ip Degree Of Protection
IP54 conforming to EN/IEC 60529
Ambient Air Temperature For Storage
-40-70 °C
Electrical Shock Protection Class
class I IEC 60536

Documents

Data Sheet

Download

Related products