Weidmuller

2489740000

ACT20P-CI-VO-P
2489740000
2489740000
2489740000
2489740000
2489740000
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
A total of 2 Parts In-Stock from 9 Distributors
Offer with manufacturer lead time
Ships in:On Request
Best price:
€112.17

Additional Information

Part Number
2489740000

General Data

Accuracy
±0,1 % FSR max., 0,05 % FSR typ.
Configuration
none
Current consumption
≤60 mA (24V power supply, 20mA output)
Galvanic isolation
3-way isolator, between input ⁄ output ⁄ supply
Rail
TS 35
Step response time
≤ 0,5 ms
Temperature coefficient
80 ppm/K
Voltage supply
20…30 V DC

Dimensions And Weights

Width
12.5 mm
Width (inches)
0.492 inch
Height
127.1 mm
Height (inches)
5.004 inch
Depth
113.7 mm
Depth (inches)
4.476 inch
Weight
110 g
Net weight
120 g

Connection Data

Type of connection
PUSH IN
Wire connection cross section AWG, min.
AWG 26
Wire connection cross section AWG, max.
AWG 14
Wire cross-section, solid, min.
0.2 mm²
Wire cross-section, solid, max.
2.5 mm²
Wire connection cross-section, finely stranded, min.
0.2 mm²
Wire connection cross section, finely stranded, max.
2.5 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, min.
0.2 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, max.
2.5 mm²

Input

Number of inputs
1
Sensor supply
> 17 V DC at 20 mA
Input signal
2-/3-wire transmitter, Current source
Input current
0...20 mA, 4…20mA
Voltage drop
≤ 1 V

Classifications

ETIM 6.0
EC002653
ETIM 7.0
EC002653
EClass 9.0
27-21-01-20
EClass 9.1
27-21-01-90
EClass 10.0
27-21-01-20

Output

Number of outputs
1
Output voltage, note
0…10 V (if input: 0…20 mA), 2…10 V (if input: 4…20 mA)
Load impedance voltage
≥ 600 kΩ

Product Information

Product information
The fixed DC repeater ACT20P-CI-VO isolates analogue standard current signals from a power source or from a 2- or 3-wire sensor. An analogue input current signal is converted linear and galvanic isolated into an analogue output voltage signal. The power supply is galvanically isolated from input and output (3-way isolation). Features The active or passive mA current signal inputs are completely electrically isolated. Front LED indicates operation status. 3-way galvanic isolation between input, output and power supply

Environmental Product Compliance

REACH SVHC
Lead 7439-92-1

Insulation Coordination

EMC standards
EN 61326-1
Galvanic isolation
3-way isolator, between input ⁄ output ⁄ supply
Impulse withstand voltage
4 kV (1.2/50 µs)
Insulation voltage
2 kV inputs / outputs / power supply
Pollution severity
2
Surge voltage category
III

Temperatures

Humidity
5...95 %, no condensation
Operating temperature, max.
60 °C
Operating temperature, min.
-20 °C
Storage temperature, max.
85 °C
Storage temperature, min.
-40 °C
Operating temperature
-20 °C...60 °C
Storage temperature
-40 °C...85 °C