ABB

S204PR-K10

1 / 1
thumbnail

Description

S204PR-K10 MCB K-Char., 10kA, 10A, 4P, RTT UL 1077, Ring Cable Lug
Part Number
S204PR-K10
UNSPSC
39121603
ETIM
Group Code : EG000020
Group Description : Circuit breakers and fuses
Class Description : Miniature circuit breaker (MCB)
Class Code : EC000042
Version : 7
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Installation

Instructions and Manuals
2CDC002138D0201

Dimensions

Width in Number of Modular Spacings
4
Product Net Width
70 mm
Product Net Height
100 mm
Product Net Depth / Length
71 mm
Product Net Weight
0.56 kg
Pole Net Weight
0.125 kg
Built-In Depth (t2)
69 mm

Technical

Standards
CSA 22.2 No. 235IEC/EN 60947-2UL 1077
Tripping Characteristic
K
Rated Operational Voltage
acc. to IEC 60947-2 400 V AC
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 500 V
Rated Impulse Withstand Voltage (Uimp)
4 kVat 2000 m 5 kVat Sea Level 6.2 kV
Dielectric Test Voltage
50/60 Hz, 1 min: 2 kV
Rated Current (In)
10 A
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(400 V AC) 15 kA
Rated Service Short-Circuit Breaking Capacity (Ics)
(400 V AC) 11.2 kA
Rated Frequency (f)
50 / 60 Hz
Power Loss
7.28 Wat Rated Operating Conditions per Pole 1.82 W
Power Supply Connection
Arbitrary
Contact Position Indication
Red ON / Green OFF
Electrical Endurance
20000 AC cycle
Mechanical Endurance
20000 cycle
Number of Poles
4
Number of Protected Poles
4
Overvoltage Category
III
Tightening Torque
2.8 N·m
Screw Terminal Type
Ring-Tongue Terminal with Captive Screw
Actuator Marking
I / O
Actuator Material
Insulation Group II, Black, Sealable
Housing Material
Insulation Group I, RAL 7035
Options Provided
Ring tongue
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting Position
any
Recommended Screw Driver
Pozidriv 2
Accessories Available
Yes
Installation Size
acc. to DIN 43880 2
Terminal Type
Ring-Tongue Terminals

Classifications

ETIM 9
EC000042 - Miniature circuit breaker (MCB)
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
WEEE B2C / B2B
Business To Business
CN8
8536 20 10
EClass
V11.0 : 27141901
IDEA Granular Category Code (IGCC)
4897 >> Miniature circuit breakers
Object Classification Code
F

Environmental

Ambient Air Temperature
Operation -25 ... +55 °CStorage -40 ... +70 °C
Reference Ambient Air Temperature
20 °C
Degree of Protection
IP20Enclosure with Cover IP40
Pollution Degree
2
Environmental Conditions
28 cycleswith 55 °C / 90-96 %and 25 °C / 95-100 %
Resistance to Vibrations acc. to IEC 60068-2-6
5g, 20 cycles at 5 ... 150 ... 5 Hz with load 0.8 In
Resistance to Shock acc. to IEC 60068-2-27
25g 2 shocks 13 ms
RoHS Status
Following EU Directive 2011/65/EU
Environmental Information
2CDK400030D201

Technical UL/CSA

Maximum Operating Voltage UL/CSA
480Y / 277 V AC
Interrupting Rating acc. to UL1077
(480Y / 277 V AC) 10 kA
Connecting Capacity UL/CSA
Conductor 14-4 AWG
Tightening Torque UL/CSA
25 in·lb

Ordering

Minimum Order Quantity
1 piece
Package Level 1 Units
carton 2 piece
Package Level 1 Gross Weight
1.17 kg