- Standards
- IEC/EN 60947-2
- Tripping Characteristic
- UC-C
- Rated Operational Voltage
- acc. to IEC 60947-2 220 V DCacc. to IEC 60947-2 230 V AC
- Rated Insulation Voltage (Ui)
- acc. to IEC/EN 60664-1 440 V
- Rated Impulse Withstand Voltage (Uimp)
- 4 kV
- Input Voltage Type
- AC/DC
- Rated Current (In)
- 6 A
- Rated Operational Current (Ie)
- 6 A
- Rated Short-Circuit Capacity
- (AC) 10 kA(230 / 400 V AC) 10 kA
- Rated Ultimate Short-Circuit Breaking Capacity (Icu)
- (220 V DC) 10 kA(110 V DC) 20 kA
- Rated Service Short-Circuit Breaking Capacity (Ics)
- (220 V DC) 10 kA(110 V DC) 10 kA
- Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)
- 50 %
- Frequency (f)
- 50 ... 60 Hz
- Rated Frequency (f)
- 50 ... 60 Hz
- Power Loss
- 2.4 W
- Power Supply Connection
- Arbitrary
- Contact Position Indication
- Red ON / Green OFF
- Energy Limiting Class
- 3
- Electrical Endurance
- 10000 cycle
- Mechanical Endurance
- 10000 cycle
- Number of Poles
- 1
- Number of Protected Poles
- 1
- Overvoltage Category
- III
- Tightening Torque
- 2.8 N·m
- Trip Class
- UC-C
- Release Type
- C
- Screw Terminal Type
- Failsafe Bi-directional Cylinder-lift Terminal
- Actuator Marking
- I / O
- Mounting Position
- Any
- Recommended Screw Driver
- Pozidriv 2
- Accessories Available
- Yes
- Connecting Capacity
- Flexible with Ferrule 0.75 ... 25 mm²Flexible 0.75 ... 25 mm²Rigid 0.75 ... 35 mm²Stranded 0.75 ... 35 mm²
- Terminal Type
- Screw Terminals