- Line Rated Current
- 18 A
- [Ue] Rated Operational Voltage
- 690 V AC 50/60 Hz IEC 60947-2
- Height
- 89 mm
- Rated Duty
- continuous IEC 60947-4-1
- Network Type
- AC
- Magnetic Tripping Current
- 400-400 A
- [Ith] Conventional Free Air Thermal Current
- 18 A IEC 60947-4-1
- Motor Power Kw
- 4-4 kW 220/230 V AC 50/60 Hz motor protection high peak current || 7.5-7.5 kW 400/415 V AC 50/60 Hz motor protection high peak current || 7.5-7.5 kW 440 V AC 50/60 Hz motor protection high peak current || 9-9 kW 440 V AC 50/60 Hz motor protection high peak current || 9-9 kW 500 V AC 50/60 Hz motor protection high peak current || 15-15 kW 690 V AC 50/60 Hz motor protection high peak current || 5-5 kW 230/240 V AC 50/60 Hz transformer protection || 6.3-6.3 kW 230/240 V AC 50/60 Hz transformer protection || 10-10 kW 400/415 V AC 50/60 Hz transformer protection || 10-10 kW 440 V AC 50/60 Hz transformer protection || 10-10 kW 500 V AC 50/60 Hz transformer protection || 12.5-12.5 kW 500 V AC 50/60 Hz transformer protection || 10-10 kW 690 V AC 50/60 Hz transformer protection
- Utilisation Category
- category A IEC 60947-2 || AC-3 IEC 60947-4-1 || AC-3e IEC 60947-4-1
- Fixing Mode
- 35 mm symmetrical DIN rail clipped || panel screwed with adaptor plate)
- [Uimp] Rated Impulse Withstand Voltage
- 6 kV IEC 60947-2
- Control Type
- toggle
- Power Dissipation Per Pole
- 2.5 W
- Electrical Durability
- 100000 cycles AC-3 415 V In || 100000 cycles AC-3e 415 V In
- [Ui] Rated Insulation Voltage
- 690 V AC 50/60 Hz IEC 60947-2
- Breaking Capacity
- 100 kA Icu 220/230 V AC 50/60 Hz IEC 60947-2 || 15 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 || 8 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 6 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 3 kA Icu 690 V AC 50/60 Hz IEC 60947-2
- Suitability For Isolation
- yes IEC 60947-1 § 7-1-6
- Thermal Protection Adjustment Range
- 13-18 A IEC 60947-4-1
- Tightening Torque
- 1.7 N.m screw clamp terminal
- Mechanical Durability
- 100000 cycles
- Poles Description
- 3P
- Width
- 45 mm
- Depth
- 78.5 mm
- Network Frequency
- 50/60 Hz IEC 60947-4-1