Eaton X48M28F75CUEENONLS45

Eaton Harmonic mitigating transformer, PV 480V, Taps: 2 at +2.5% /4 at -2.5%, SV 208Y/120V, 115°C rise, 75 kVA, Copper windings, EE, NONLS45

Image of the product X48M28F75CUEENONLS45
Eaton Harmonic mitigating transformer, PV 480V, Taps: 2 at +2.5% /4 at -2.5%, SV 208Y/120V, 115°C rise, 75 kVA, Copper windings, EE, NONLS45

Additional information

Part Number X48M28F75CUEENONLS45
UPC 786680052873

Specifications

Special features Electrostatically shielded
Frame 916A
Tap size 2 at +2.5% FCAN, 4 at -2.5% FCBN
Phase Three-phase
Weathershield WS19
Modification 1 Low sound 45 dB
Primary voltage 480 V
Phase shift 0 °
Wiring connection 200X
Secondary Voltage 208 Y/120 V
Type Dry Type Distribution Transformer
Frequency rating 60 Hz
Coil material Copper
Temperature rise 115 °C rise
Volt ampere rating 75 kVA

General

UPC 786680052873
Product Length/Depth 23.42 in
Product Height 48.56 in
Product Width 28.22 in
Product Weight 984 lb
Warranty Eaton Selling Policy 25-000, one (1) year from the date of installation of the Product or eighteen (18) months from the date of shipment of the Product, whichever occurs first.
Compliances NEMA TP-1 Compliant
Certifications UL Listed
Catalog Notes NEMA TP-1 efficient, Low sound equal to 45 dB