Distributed I/O device - FLS PB M12 DI 8 M12 - 2736123
2736123
  • Consigue plazos de pago de hasta 90 días de 500+ proveedores.
  • Descuentos de reventa de hasta el 40%!
Registrate
Enviar solicitud de precio
1
Formas de pago:
Oferta con plazo de entrega del fabricante
Entrega:1 - 2 días laborables
El mejor precio:
Enviar solicitud de precio

Additional Information

Part Number
2736123
UPC
4017918899585
Country of Origin
DE
ETIM
Group Code : EG000024
Group Description : PLC's
Class Description : Fieldbus, decentr. periphery - digital I/O module
Class Code : EC001599
Version : 7

Note

Utilization restriction
EMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width
60 mm
Height
161 mm
Depth
44.5 mm
Drill hole spacing
151 mm

Fieldline potentials

Voltage supply UL
24 V DC
Power supply at UL
max. 4 A
Current consumption from UL
typ. 35 mA
Current consumption from UL
max. 100 mA
Voltage supply US
24 V DC
Power supply at US
max. 4 A
Current consumption from US
typ. 5 mA (plus sensor current)
Current consumption from US
max. 700 mA

Digital inputs

Input name
Digital inputs
Description of the input
IEC 61131-2 type 1
Connection method
M12 connector
Connection technology
2, 3, 4-wire
Number of inputs
8
Protective circuit
Reverse polarity protection
Nominal input voltage UIN
24 V DC
Filter time
3 ms
Input voltage
24 V DC
Input voltage range "0" signal
-30 V DC - 5 V DC
Input voltage range "1" signal
13 V DC - 30 V DC

Ambient conditions

Ambient temperature (operation)
-25 °C - 60 °C
Ambient temperature (storage/transport)
-25 °C - 85 °C
Permissible humidity (storage/transport)
95 %
Air pressure (operation)
80 kPa - 106 kPa (up to 2000 m above sea level)
Air pressure (storage/transport)
70 kPa - 106 kPa (up to 3000 m above sea level)
Degree of protection
IP65/IP67

Environmental Product Compliance

REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 50 years
China RoHS
For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

Electrical isolation

Test section
24 V supply (bus logics) / Bus connection
Test section
24 V supply (bus logics) / FE 500 V AC 50 Hz 1 min.
Test section
24 V supply (bus logics) / Digital inputs (sensor supply) 500 V AC 50 Hz 1 min.
Test section
Bus connection / FE 500 V AC 50 Hz 1 min.
Test section
Bus connection / Digital inputs (sensor supply) 500 V AC 50 Hz 1 min.
Test section
FE / Digital inputs (sensor supply) 500 V AC 50 Hz 1 min.

Interfaces

Designation
PROFIBUS DP
Connection method
2x M12 connectors, B-coded
Designation connection point
Copper cable
Transmission speed
9.6 kbps - 12 Mbps (Automatic baud rate detection)
Transmission physics
PROFIBUS-DP-compliant copper cable
Address area assignment
1 - 99, can be set
Number of positions
5

Standards and Regulations

Mechanical tests
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 Load 30g, half sine wave, positive and negative per direction
Mechanical tests
Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g in each space direction
Connection in acc. with standard
CUL
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)

Power supply for module electronics

Connection method
M12 connector, (A-coded)
Designation
UL
Supply voltage
24 V DC
Supply voltage range
18 V DC - 30 V DC (including ripple)