1 / 1
thumbnail

Descripción

Activo maduro
GV3P18 is a TeSys GV motor circuit breaker from Schneider Electric. It ensures thermal-magnetic protection for motors 7.5kW@400V and high breaking capacity Icu 100kA. Start-stop control by rotary knob guaranteed for 50 000 cycles AC-3 415V. GV3P18 is a TeSys GV motor circuit breaker from Schneider Electric designed for motor applications 7.5kW@400V. It fulfills a thermal-magnetic protection with a thermal setting range 12-18A, magnetic tripping at 14xIn and high breaking capacity Icu 100kA@400V. Start-stop control by rotary knob guaranteed for 50 000 cycles AC-3 415V. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach). Complete motor protection in a single device , short-circuit, overload, disconnection. Associated with a TeSys contactor, it ensures a complete type 1 or type 2 Motor Starter solution. Compact, 55mm wide, for DIN-rail and panel mounting. Manual control with rotary knob for Start / Stop, padlockable. Possible mounting of auxiliary contacts front or side mounted (GVAE, GVAN, GVAD) for status and tripping signaling. For large industrial or building LV distribution networks thanks to a high 100kA breaking capacity. Power connections with EverLink BTR screw connectors providing constant tightening pressure. Can be associated with undervoltage or shunt tripping units (GVAU, GVAS) and power distribution busbars (GV3G).
Country of Origin
FR
Part Number
GV3P18
Tariff Code
85362010
EAN
3389119405362
UNSPSC
39121521
Métodos de pago:
Mejor oferta de:
DEProveedor de confianza de Automa.Net
Disponibilidad:
2 piezas
En stock
Actualizado en: 04-11-2024
Entrega Estimada:
Bajo pedido
Condición:
Usado
Usado - Un artículo usado previamente con posibles signos de desgaste cosmético. Está completamente operativo y funciona según lo previsto, aunque el embalaje original puede faltar.
Información de envío
Proceso de Pago Seguro
Políticas de Devolución y Reembolso
Políticas de Envío
Políticas de Garantía

Environment

Product Certifications
CCC || UL || CSA || EAC || ATEX || LROS (Lloyds register of shipping) || BV || ABS || DNV-GL || UKCA
Ik Degree Of Protection
IK09 enclosure
Mechanical Robustness
shocks 15 Gn for 11 ms contactor open || shocks 30 Gn for 11 ms contactor closed || vibrations 4 Gn, 5...300 Hz
Ambient Air Temperature For Operation
-20-60 °C
Standards
EN/IEC 60947-2 || EN/IEC 60947-4-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1
Climatic Withstand
IACS E10
Ambient Air Temperature For Storage
-40-80 °C
Ip Degree Of Protection
IP20 IEC 60529
Operating Altitude
9842.52 ft (3000 m)
Fire Resistance
960 °C IEC 60695-2-11

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP060901
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI060901
Eu Rohs Directive
Compliant with Exemptions

Complementary

Line Rated Current
18 A
[Ue] Rated Operational Voltage
690 V AC 50/60 Hz IEC 60947-2
Height
132 mm
Phase Failure Sensitivity
yes IEC 60947-4-1
Rated Duty
continuous IEC 60947-4-1
Network Type
AC
Magnetic Tripping Current
252-252 A
[Ith] Conventional Free Air Thermal Current
18 A IEC 60947-4-1
Motor Power Kw
7.5-7.5 kW 400/415 V AC 50/60 Hz || 9-9 kW 500 V AC 50/60 Hz || 15-15 kW 690 V AC 50/60 Hz
Utilisation Category
AC-3 IEC 60947-4-1
Net Weight
0.96 kg
Fixing Mode
35 mm symmetrical DIN rail clipped || panel screwed with 3 x M4 screws)
[Uimp] Rated Impulse Withstand Voltage
6 kV IEC 60947-2
[Ics] Rated Service Short-Circuit Breaking Capacity
100 % 230/240 V AC 50/60 Hz IEC 60947-2 || 100 % 400/415 V AC 50/60 Hz IEC 60947-2 || 100 % 440 V AC 50/60 Hz IEC 60947-2 || 50 % 500 V AC 50/60 Hz IEC 60947-2 || 50 % 690 V AC 50/60 Hz IEC 60947-2
Control Type
rotary handle
Power Dissipation Per Pole
8 W
Electrical Durability
50000 cycles AC-3 415 V In
[Ui] Rated Insulation Voltage
690 V AC 50/60 Hz IEC 60947-2
Breaking Capacity
100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 || 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 12 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 6 kA Icu 690 V AC 50/60 Hz IEC 60947-2
Suitability For Isolation
yes IEC 60947-1
Thermal Protection Adjustment Range
12-18 A IEC 60947-4-1
Tightening Torque
5 N.m screw clamp terminal
Mechanical Durability
50000 cycles
Poles Description
3P
Color
dark grey
Width
55 mm
Depth
136 mm
Network Frequency
50/60 Hz IEC 60947-4-1

Specifications

Product Or Component Type
motor circuit breaker
Product Name
TeSys GV3 || TeSys Deca
Range
TeSys Deca
Device Application
motor protection
Device Short Name
GV3P
Trip Unit Technology
thermal-magnetic

Modelos CAD

traceparts
traceparts
Descargar