Schneider Electric
JDL36175
Circuit breaker, PowerPacT J, 175A, 3 pole, 600VAC, 14kA, lugs, thermal magnetic, 80%
- Consigue plazos de pago de hasta 90 días de 500+ proveedores.
- Descuentos de reventa de hasta el 40%!
$952.00
1
Formas de pago:
Un total de 2 Parts In-Stock de 1 Distributor
Condiciones del producto:
Additional Information
- Part Number
- JDL36175
- UPC
- 785901706663
- UNSPSC
- 39121601
- Tariff Code
- 8536200020
- Country of Origin
- MX
Environment
- Ambient Air Temperature For Operation
- -2-70 °C
- Standards
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Product Certifications
- UL || CSA || NOM
- Ip Degree Of Protection
- front cover IP40
- Pollution Degree
- 3 IEC 60947-1
- Ambient Air Temperature For Storage
- -50-85 °C
- Quality Labels
- CE
- Operating Altitude
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP2206031EN
- Sustainable Offer Status
- Green Premium product
- Pvc Free
- Yes
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI2206031EN
- Eu Rohs Directive
- Compliant with Exemptions
Complementary
- Mounting Mode
- unit mount lug)
- Network Frequency
- 50/60 Hz
- Terminal Identifier
- AL175JD
- [Ics] Rated Service Breaking Capacity
- 25 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 18 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 14 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Trip Unit Technology
- thermal-magnetic
- Height
- 191 mm
- [Ue] Rated Operational Voltage
- 600 V AC 50/60 Hz IEC 60947-3
- Tightening Torque
- 25-25 N.m 25-95 mm² (AWG 4...AWG 4/0)
- Mounting Support
- lug
- Breaking Capacity Code
- D
- Magnetic Tripping Current
- 1750-1750 A
- Local Signalling
- switched off (OFF) 1 trip indicator green)
- Number Of Slots
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Electrical Connection
- lugs, line || lugs, load
- Net Weight
- 2.4 kg
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV IEC 60947-2
- Magnetic Hold Current
- 875 A
- Control Type
- toggle
- Circuit Breaker Application
- HACR rated
- Wire Stripping Length
- 25 mm
- Line Rated Current
- 175-175 A
- Utilisation Category
- category A
- Long Time Pick-Up Adjustment Range
- 0.25...1 x In
- Continuous Current Rating
- 80 %
- Breaking Capacity
- 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz || 14 kA 600 V AC 50/60 Hz || 20 kA 250 V DC
- [Ui] Rated Insulation Voltage
- 750 V IEC 60947-2
- Suitability For Isolation
- yes IEC 60947-2
- Communication Interface
- Modbus || Ethernet
- Poles Description
- 3P
- Protection Type
- overload protection || short-circuit protection
- Awg Gauge
- AWG 4...AWG 4/0 aluminium/copper terminal
- Width
- 104 mm
- Depth
- 86 mm
Specifications
- Product Or Component Type
- circuit breaker
- Product Name
- PowerPact J
- Range
- PowerPact
- Device Application
- distribution
Documentos
Data Sheet
DescargarOtras categorías
ActuadoresBloquesCables, tuberías y manguerasCompresoresControlAcoplamientos y AccesoriosCilindros y PistonesElectrónicaFiltrosHVACPCs industriales y HMIsIluminaciónTécnica linealMotoresFuente de alimentaciónTransmisión de energíaBombas y VálvulasEnergías renovablesRobóticaSellos, anillos y conectoresSensores y dispositivos de mediciónHerramientas y AccesoriosCNCOtros