- Non-Overlap Time
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Minimum Switching Current
- 5 mA for signalling circuit
- Power Dissipation Per Pole
- 5.4 W AC-1 || 2.4 W AC-3 || 2.4 W AC-3e
- Average Impedance
- 1.5 mOhm - Ith 60 A 50 Hz for power circuit
- Auxiliary Contact Composition
- 1 NO + 1 NC
- [Ith] Conventional Free Air Thermal Current
- 60 A (at 60 °C) for power circuit || 10 A (at 60 °C) for signalling circuit
- Control Circuit Voltage Limits
- <= 0.1 Uc -40-70 °C drop-out AC/DC || 0.85...1.1 Uc -40-60 °C operational AC/DC || 1...1.1 Uc 60-70 °C operational AC/DC
- Mounting Support
- plate || rail
- Control Circuit Type
- AC/DC 50/60 Hz AC/DC electronic
- Safety Reliability Level
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Pollution Degree
- 3
- Hold-In Power Consumption In W
- 0.9-0.9 W 20 °C
- Insulation Resistance
- > 10 MOhm for signalling circuit
- Rated Breaking Capacity
- 800 A at 440 V for power circuit conforming to IEC 60947
- Irms Rated Making Capacity
- 800 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for signalling circuit conforming to IEC 60947-5-1 || 250 A DC for signalling circuit conforming to IEC 60947-5-1
- Associated Fuse Rating
- 80 A gG at <= 690 V coordination type 1 for power circuit || 80 A gG at <= 690 V coordination type 2 for power circuit || 10 A gG for signalling circuit conforming to IEC 60947-5-1
- Inrush Power In Va
- 23-23 VA 50/60 Hz (at 20 °C)
- [Uimp] Rated Impulse Withstand Voltage
- 6 kV IEC 60947
- Pole Contact Composition
- 3 NO
- Connections - Terminals
- power circuit: lugs-ring terminals - external diameter: 16.5 mm || control circuit: lugs-ring terminals - external diameter: 8 mm
- Coil Technology
- built-in bidirectional peak limiting
- Operating Time
- 55...65 ms closing || 20...80 ms opening
- Minimum Switching Voltage
- 17 V for signalling circuit
- Maximum Operating Rate
- 3600 cyc/h 60 °C
- Signalling Circuit Frequency
- 25...400 Hz
- Tightening Torque
- control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 6 N.m lugs-ring terminals hexagonal 10 mm M6 || power circuit 6 N.m lugs-ring terminals pozidriv No 2 M4 || control circuit 1.7 N.m lugs-ring terminals pozidriv No 2 M3.5
- Electrical Durability
- 2 Mcycles 35 A AC-3 <= 440 V || 0.7 Mcycles 60 A AC-1 <= 440 V || 2 Mcycles 35 A AC-3e <= 440 V
- Mechanical Durability
- 6 Mcycles
- Inrush Power In W
- 19-19 W 20 °C)
- Auxiliary Contacts Type
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Compatibility Code
- LC1D
- Hold-In Power Consumption In Va
- 1.4-1.4 VA 50/60 Hz (at 20 °C)
- Overvoltage Category
- III
- Maximum Horse Power Rating
- 3 hp at 115 V AC 60 Hz for 1 phase motors || 5 hp at 230/240 V AC 60 Hz for 1 phase motors || 10 hp at 200/208 V AC 60 Hz for 3 phase motors || 10 hp at 230/240 V AC 60 Hz for 3 phase motors || 30 hp at 460/480 V AC 60 Hz for 3 phase motors || 30 hp at 575/600 V AC 60 Hz for 3 phase motors
- Motor Power Kw
- 11 kW at 220...230 V AC 50 Hz (AC-3) || 18.5 kW at 380...400 V AC 50 Hz (AC-3) || 22 kW at 415 V AC 50 Hz (AC-3) || 22 kW at 440 V AC 50 Hz (AC-3) || 22 kW at 500 V AC 50 Hz (AC-3) || 30 kW at 660...690 V AC 50 Hz (AC-3) || 11 kW at 220...230 V AC 50 Hz (AC-3e) || 18.5 kW at 380...400 V AC 50 Hz (AC-3e) || 22 kW at 415 V AC 50 Hz (AC-3e) || 22 kW at 440 V AC 50 Hz (AC-3e) || 22 kW at 500 V AC 50 Hz (AC-3e) || 30 kW at 660...690 V AC 50 Hz (AC-3e)
- [Ui] Rated Insulation Voltage
- power circuit 690 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-1
- [Icw] Rated Short-Time Withstand Current
- 72 A 40 °C - 10 min for power circuit || 165 A 40 °C - 1 min for power circuit || 320 A 40 °C - 10 s for power circuit || 720 A 40 °C - 1 s for power circuit || 100 A - 1 s for signalling circuit || 120 A - 500 ms for signalling circuit || 140 A - 100 ms for signalling circuit
- Heat Dissipation
- 0.9-0.9 W at 50/60 Hz
- Protective Cover
- with