1 / 1
thumbnail

Descripción

Activo maduro
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 4 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactor has four normally open power contacts. Power contacts have a 40A resistive load rating. Contactor is supplied with a low consumption 24 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.58 inches tall, 1.77 inches wide and 4.21 inches deep. It weighs 0.94 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
Country of Origin
ID
Part Number
LC1DT406BL
Tariff Code
8536490065
EAN
39121529
UNSPSC
39121529
Métodos de pago:
Mejor oferta de:
DEProveedor de confianza de Automa.Net
Disponibilidad:
1 pieza
En stock
Actualizado en: 08-11-2024
Garantía:
12 meses
Entrega Estimada:
Bajo pedido
Condición:
Nuevos excedentes
Nuevos excedentes - Un artículo nuevo, sin usar, sin daños y sin garantía del fabricante. El artículo puede venir sin embalaje original o en embalaje de reemplazo. Si se proporciona, es posible que la caja haya sido abierta.
Proceso de Pago Seguro
Políticas de Devolución y Reembolso
Políticas de Envío
Políticas de Garantía

Environment

Product Certifications
GL || RINA || BV || UL || CSA || CCC || LROS (Lloyds register of shipping) || DNV || GOST
Height
91 mm
Standards
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Climatic Withstand
IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
Net Weight
0.425 kg
Flame Retardance
V1 conforming to UL 94
Protective Treatment
THIEC 60068-2-30
Ip Degree Of Protection
IP20 front face IEC 60529
Mechanical Robustness
vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 8 Gn for 11 ms)
Operating Altitude
0...9842.52 ft (0...3000 m)
Fire Resistance
850 °C IEC 60695-2-1
Width
45 mm
Depth
107 mm
Permissible Ambient Air Temperature Around The Device
-40-60 °C || 60-70 °C with derating

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP110229EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Toxic Heavy Metal Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Pro-active China RoHS declaration (out of China RoHS legal scope)
Circularity Profile
ENVEOLI110229EN
Eu Rohs Directive
Compliant

Complementary

Non-Overlap Time
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Minimum Switching Current
5 mA for signalling circuit
Power Dissipation Per Pole
3.2 W AC-1
Average Impedance
2 mOhm - Ith 40 A 50 Hz for power circuit
Auxiliary Contact Composition
1 NO + 1 NC
[Ith] Conventional Free Air Thermal Current
10 A (at 60 °C) for signalling circuit || 40 A (at 60 °C) for power circuit
Control Circuit Voltage Limits
0.1...0.3 Uc -40-70 °C drop-out DC || 0.8...1.25 Uc -40-60 °C operational DC || 1...1.25 Uc 60-70 °C operational DC
Mounting Support
rail || plate
Contact Compatibility
M5
Control Circuit Type
DC low consumption
Safety Reliability Level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Pollution Degree
3
Hold-In Power Consumption In W
2.4-2.4 W 20 °C
Insulation Resistance
> 10 MOhm for signalling circuit
Rated Breaking Capacity
450 A at 440 V for power circuit conforming to IEC 60947
Irms Rated Making Capacity
140 A AC for signalling circuit conforming to IEC 60947-5-1 || 250 A DC for signalling circuit conforming to IEC 60947-5-1 || 450 A at 440 V for power circuit conforming to IEC 60947
Associated Fuse Rating
10 A gG for signalling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 40 A gG at <= 690 V coordination type 2 for power circuit
[Uimp] Rated Impulse Withstand Voltage
6 kV IEC 60947
Pole Contact Composition
4 NO
Connections - Terminals
control circuit: lugs-ring terminals - external diameter: 8 mm || power circuit: lugs-ring terminals - external diameter: 8 mm
Coil Technology
built-in bidirectional peak limiting diode suppressor
Time Constant
40 ms
Operating Time
77 ±15 % ms closing || 25 ±20 % ms opening
Minimum Switching Voltage
17 V for signalling circuit
Maximum Operating Rate
3600 cyc/h 60 °C
Signalling Circuit Frequency
25...400 Hz
Tightening Torque
control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || control circuit 1.7 N.m lugs-ring terminals pozidriv No 2 M3.5 || power circuit 1.8 N.m lugs-ring terminals flat Ø 6 mm M3.5 || power circuit 1.8 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 1.8 N.m lugs-ring terminals pozidriv No 2 M3.5
Electrical Durability
1.4 Mcycles 40 A AC-1 <= 440 V
Mechanical Durability
30 Mcycles
Inrush Power In W
2.4-2.4 W 20 °C)
Auxiliary Contacts Type
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Compatibility Code
LC1D
Overvoltage Category
III
[Ui] Rated Insulation Voltage
power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
[Icw] Rated Short-Time Withstand Current
50 A 40 °C - 10 min for power circuit || 120 A 40 °C - 1 min for power circuit || 240 A 40 °C - 10 s for power circuit || 380 A 40 °C - 1 s for power circuit || 100 A - 1 s for signalling circuit || 120 A - 500 ms for signalling circuit || 140 A - 100 ms for signalling circuit
Protective Cover
with

Specifications

[Uc] Control Circuit Voltage
24 V DC
[Ue] Rated Operational Voltage
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Range Of Product
TeSys Deca
Contactor Application
resistive load
Product Or Component Type
contactor
Range
TeSys || TeSys Deca
Utilisation Category
AC-1 || AC-3 || AC-3e || AC-4
[Ie] Rated Operational Current
40 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
Poles Description
4P
Device Short Name
LC1D

Documentos

Data Sheet

Descargar

Modelos CAD

traceparts
traceparts
Descargar