Schneider Electric

METSEEM3560A

PowerLogic EM3500 DIN rail meter - BACnet - flexible transducer
METSEEM3560A
  • Consigue plazos de pago de hasta 90 días de 500+ proveedores.
  • Descuentos de reventa de hasta el 40%!
Registrate
Enviar solicitud de precio
1
Formas de pago:
Solicite un presupuesto y le enviaremos información sobre disponibilidad y precio.

Additional Information

Part Number
METSEEM3560A
UNSPSC
39121032
Tariff Code
9028300000
Country of Origin
US

Specifications

Product Or Component Type
energy meter
Product Name
PowerLogic EM3500
Range
PowerLogic
Device Short Name
EM3560A
Metering Type
peak demand power PM, QM, SM || current I1, I2, I3, Iavg || demand power P, Q, S || voltage U21, U32, U13, V1, V2, V3

Complementary

Network Frequency
50 Hz || 60 Hz
Communication Port Support
screw terminal block RS485
[Ue] Rated Operational Voltage
90...347 V AC 50/60 Hz between phase and neutral UL || 156...600 V AC 50/60 Hz between phases UL || 90...300 V AC 50/60 Hz between phase and neutral CE || 125...300 V DC
Standards
IEC 61010-1 || UL 508 || CSA C22.2 No 14-05
Number Of Outputs
1 alarm output
Mounting Support
DIN rail
Power Consumption In Va
5-5 VA 347 V AC between phase and neutral) || 5-5 VA 600 V AC between phases)
Product Certifications
CE IEC 61010 || cULus UL 508
Type Of Measurement
active and reactive power total || active and reactive power per phase || apparent power total || apparent power per phase || power factor total || power factor per phase || peak demand power || current || voltage || frequency
Communication Port Protocol
BACnet MS/TP 9600 bauds...115200 bauds (automatic detection) - 2-wire
Communication Service
total cumulated energy || total cumulated active energy
Ride-Through Time
100 ms 120 V AC
Display Digits
5
Number Of Inputs
1 pulse
Tamperproof Of Settings
protected by access code
Measurement Current
20-5000 A
Information Displayed
status and alert || communication with system || input/output status || error || Tx activity || Rx activity || instant power per usage
Function Available
external synchronisation to communication || fixed or rolling block
Mounting Mode
by screws || clip-on
Local Signalling
Red LED threshold reached || Green flashing LED output signal
Power Consumption In W
3 W 300-300 V
Measurement Accuracy
power +/- 0.5 % || energy +/- 0.5 %
Technology Type
electronic
Buffer Size
32-bit 3
Poles Description
3P + N
Data Recording
energy consumption logs
Analogue Input Type
Rogowski coil 50...5000 A
Display Type
Backlit LCD
Device Application
sub billing || partial meter
Accuracy Class
class 0.5S power IEC 62053-22 || class 0.5S energy IEC 62053-22 || class 0.5S power ANSI C12.20 || class 0.5S energy ANSI C12.20
Rated Voltage
90-347 V

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Eu Rohs Directive
Compliant with Exemptions

Environment

Ambient Air Temperature For Operation
-30-70 °C
Height
91 mm
9 Mm Pitches
12
Color
dark grey
Ambient Air Temperature For Storage
-40-85 °C
Relative Humidity
0-95 %
Width
107 mm
Depth
59 mm

Documentos

Data Sheet

Descargar

Productos relacionados