1 / 1
thumbnail

Descrizione

Attivo maturo
TeSys LR9G 225A thermal overload relay is compatible with TeSys Giga high power contactor, push-in control connection. It provides phase imbalance, phase failure, in-built ground-fault and single-phase loads protections. It is available for manual and auto reset options and LED indicator for Motor ON and pre-trip alarm. Tripping classes is selectable from class 5E to class 30E to suit different application needs from fast tripping, general purpose and high inertia loads. It is suitable for independent mounting or direct mounting with LC1G contactors. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature without derating up to 3000m altitude. Multi standards certified (CE,CB,CCC,cULus,EAC,KC,RCM,Marine) and Green Premium compliant (RoHs/Reach). Unique QR code provides quick access to complete product data.
Country of Origin
CN
Part Number
LR9G225
Tariff Code
85364900
EAN
3606481912541
UNSPSC
39122330
£281.49
net
1
Metodi di pagamento:
Migliore offerta da:
GBFornitore Automa.Net di fiducia
Disponibilità:
8 pz.
Disponibile
Aggiornato il: 04-11-2024
Consegna stimata:
Su richiesta
Condizione:
Nuovo sigillato in fabbrica
Nuovo sigillato in fabbrica - Un articolo nuovo di zecca, inutilizzato, non aperto, non danneggiato, nella sua confezione originale sigillata dal produttore.
Un totale di 199 Parts In-Stock da 22 Distributors
Processo di Pagamento Sicuro
Politiche di Reso e Rimborso
Politiche di Spedizione
Politiche di Garanzia

Offerte Disponibili (22)

LR9G225 product image
Schneider Electric

LR9G225

Condizione:
Nuove eccedenze
Disponibile:
5 pz.
Disponibile
Aggiornato il: 04-11-2024
Offerta da:
CNFornitore Automa.Net di fiducia
Consegna stimata:
Su richiesta
Garanzia:
12 mesi
1
LR9G225 product image
Schneider Electric

LR9G225

Condizione:
Nuove eccedenze
Disponibile:
8 pz.
Disponibile
Aggiornato il: 04-11-2024
Offerta da:
ITFornitore Automa.Net di fiducia
Consegna stimata:
Su richiesta
Garanzia:
12 mesi
1
Offerta con tempi di consegna del produttore
Spedizione in:Su richiesta
Miglior prezzo:
€127.57

Complementary

Product Certifications
CB Scheme || CCC || cULus || UKCA || ATEX || EU-RO-MR by DNV-GL || EAC
Network Frequency
30...60 Hz || 100 Hz
[Uc] Control Circuit Voltage
24...500 V AC 50/60 Hz || 24...250 V DC
[Ith] Conventional Free Air Thermal Current
5 A
Tightening Torque
18 N.m
Reset
automatic reset || manual
Standards
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || JIS C8201-5-1
[Ue] Rated Operational Voltage
1000 V AC 50/60 Hz
Electromagnetic Compatibility
EMC immunity conforming to IEC 60947-4-1 || emission tests criteria A conforming to IEC 60947-4-1 || immunity to radiated radio-electrical interference - test level: 20 V/m conforming to EN/IEC 61000-4-3 || voltage dips and interruptions immunity test conforming to SEMI F47
Protection Type
ground fault protection 0-1 s - alarm circuit IEC 60947-4-1 || ground fault protection 0-1 s - alarm circuit UL 60947-4-1 || phase loss 0-4 s - alarm circuit || phase imbalance 0-5 s - alarm circuit IEC 60947-4-1 || phase imbalance 0-5 s - alarm circuit UL 60947-4-1
[Uimp] Rated Impulse Withstand Voltage
8 kV
Connections - Terminals
power circuit: bar - busbar cross section: 25 x 6 mm || power circuit: lugs-ring terminals 1 185-185 mm² || control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end || control circuit: push-in 1 0.25-2.5 mm² - cable stiffness: flexible with cable end || control circuit: push-in 2 0.5-1.0 mm² with cable end
Contacts Type And Composition
1 NO + 1 NC
Surge Withstand
4 kV
Tripping Threshold
1.125 +/- 0.07 In IEC 60947-4-1
Mounting Support
direct on contactor || plate
Mechanical Durability
7000 cycles
Local Signalling
LED || trip indicator
Overvoltage Category
III

Specifications

Network Type
AC
Thermal Protection Adjustment Range
57-225 A
Relay Application
motor protection
Product Or Component Type
electronic thermal overload relay
Product Name
TeSys LRG
Thermal Overload Class
class 5E...30E IEC 60947-4-1
Range
TeSys
Device Short Name
LR9G

Environment

Height
107 mm
Ambient Air Temperature For Operation
-25-60 °C
Net Weight
0.9 kg
Ambient Air Temperature For Storage
-60-80 °C
Protective Treatment
TH
Ip Degree Of Protection
IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
Mechanical Robustness
vibrations 5-300 Hz 6 gn contactor open || shocks 15 gn 11 ms contactor closed
Color
dark grey
Width
105 mm
Depth
126 mm
Ambient Air Transport Temperature
-25-60 °C
Permissible Ambient Air Temperature Around The Device
-40-60 °C at Uc

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP2105014
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Nickel (Metallic), which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation
X
Circularity Profile
ENVEOLI2105014
Eu Rohs Directive
Compliant with Exemptions
Halogen Content Performance
Halogen free plastic parts product

Modelli CAD

traceparts
traceparts
Scaricare