Phoenix Contact
2905578
1 / 1
Description
3-way output signal conditioner for transmitting 0/4 ... 20 mA signals from the controller to a load located in the field with simultaneous 3-way electrical isolation between the input, output, and supply, with spring connection- Country of Origin
- DE
- Part Number
- 2905578
- Tariff Code
- 85437090
- EAN
- 4046356966283
- UPC
- 4046356966283
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Input data
- Number of inputs
- 1
- Current input signal
- 4 mA - 20 mA
- Current input signal
- 0 mA - 20 mA
- Max. input current
- 20 mA
- Input voltage limitation
- < 2 V (20 mA)
- Input resistance current input
- 50 Ω
Note
- Utilization restriction
- EMC: class A product, see manufacturer's declaration in the download area
Dimensions
- Width
- 6.2 mm
- Height
- 93.1 mm
- Depth
- 102.5 mm
Connection data
- Connection method
- Spring-cage connection
- Conductor cross section solid min.
- 0.2 mm²
- Conductor cross section solid max.
- 2.5 mm²
- Conductor cross section AWG min.
- 24
- Conductor cross section AWG max.
- 12
- Conductor cross section flexible min.
- 0.2 mm²
- Conductor cross section flexible max.
- 2.5 mm²
- Stripping length
- 8 mm
Output data
- Output name
- Current output
- Number of outputs
- 1
- Current output signal
- 4 mA - 20 mA
- Current output signal
- 0 mA - 20 mA
- Load/output load current output
- ≤ 800 Ω (at 20 mA)
- Ripple
- < 20 mVrms
- Transmission Behavior
- 1:1 to input signal
Ambient conditions
- Ambient temperature (operation)
- -20 °C - 60 °C
- Ambient temperature (storage/transport)
- -40 °C - 85 °C
Environmental Product Compliance
- China RoHS
- Environmentally Friendly Use Period = 50
- China RoHS
- For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
EMC data
- Designation
- Electromagnetic RF field
- Standards/regulations
- EN 61000-4-3
- Typical deviation from the measuring range final value
- 3 %
- Designation
- Fast transients (burst)
- Standards/regulations
- EN 61000-4-4
- Typical deviation from the measuring range final value
- 3 %
- Designation
- Conducted interferences
- Standards/regulations
- EN 61000-4-6
- Typical deviation from the measuring range final value
- 3 %
Standards and Regulations
- Electromagnetic compatibility
- Conformance with EMC directive
- Noise emission
- EN 61000-6-4
- Standards/regulations
- EN 61000-4-2
- Designation
- Electromagnetic RF field
- Standards/regulations
- EN 61000-4-3
- Standards/regulations
- EN 61000-4-4
- Standards/regulations
- EN 61000-4-5
- Designation
- Conducted interferences
- Standards/regulations
- EN 61000-4-6
- Electrical isolation
- Basic insulation according to EN 61010
- Conformance
- CE-compliant
- ATEX
- II 3 G Ex nA IIC T4 Gc X
- UL, USA/Canada
- UL 508 Listed
- UL, USA/Canada
- Class I, Div. 2, Groups A, B, C, D T4
- UL, USA/Canada
- Class I, Zone 2, Group IIC
- GL
- GL applied for
- Fire protection for rail vehicles (DIN EN 45545-2) R22
- HL 1 - HL 2
- Fire protection for rail vehicles (DIN EN 45545-2) R23
- HL 1 - HL 2
- Fire protection for rail vehicles (DIN EN 45545-2) R24
- HL 1 - HL 2
Power supply
- Nominal supply voltage
- 24 V DC
- Supply voltage range
- 19.2 V DC - 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
- Power consumption
- < 600 mW (at 24 V DC)
Other Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther