Phoenix Contact 2924032

Output signal conditioner - MACX MCR-EX-SL-IDSI-I-SP - 2924032

(5 offers)
Image of the product 2924032
A total of  5 Offer On-request from 4 Distributors
Ex i output signal conditioner, HART. Isolates and transmits 0/4 - 20 mA signals with intrinsic safety to a load (I/P converters, regulating valves, displays) in the Ex area. Open-circuit detection, SIL 2 in accordance with IEC 61508, spring-cage connection. Replacement item: 2908062 MACX MCR-EX-IDS-I-I-SP.

Suppliers

On Request Parts

These parts are not in the warehouse and will be quoted with manufacturer lead time. Send inquiry for supplier details.
On Request Updated 20/08/2024
  • Quantity: New Sealed: 0 pcs.
Register to See Company
Country: United States
On Request Updated 20/08/2024
  • Quantity: New Surplus: 0 pcs. Used: 0 pcs.
On Request Updated 20/08/2024
  • Quantity: New Sealed: 0 pcs.
Register to See Company
Country: Czech Republic
On Request Updated 20/08/2024
  • Quantity: New Sealed: 0 pcs.

Additional information

Part Number 2924032
UPC 4046356337342
Country of origin DE
ETIM Group code: EG000026
Group description: Sensors
Class code: EC002653
Class description: Isolation amplifier
Version: 7

Input data

Current input signal 0 mA - 20 mA
Current input signal 4 mA - 20 mA
Input impedance > 100 kΩ (If there is a line fault)
Voltage drop 5.4 V (20 mA)

Dimensions

Width 12.5 mm
Height 116.9 mm
Depth 113.7 mm

Connection data

Connection method Push-in connection
Stripping length 8 mm
Conductor cross section solid 0.2 mm² - 1.5 mm²
Conductor cross section flexible 0.2 mm² - 1.5 mm²
Conductor cross section AWG 24 - 16

Output data

Signal output Current output
Current output signal 0 mA - 20 mA (intrinsically safe)
Current output signal 4 mA - 20 mA (intrinsically safe)
Transmission Behavior 1:1 to input signal
Load/output load current output < 800 Ω (20 mA)
Load/output load current output < 730 Ω (22.5 mA)
Output ripple < 20 mVrms

Data communication (bypass)

HART function Yes
Protocols supported HART

Ambient conditions

Ambient temperature (operation) -20 °C - 60 °C (Any mounting position)
Ambient temperature (storage/transport) -40 °C - 80 °C
Maximum altitude ≤ 2000 m
Permissible humidity (operation) 10 % - 95 % (non-condensing)
Degree of protection IP20 (not assessed by UL)
Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal deviations.

Environmental Product Compliance

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
China RoHS For details about hazardous substances go to tab 'Downloads', Category 'Manufacturer's declaration'

EMC data

Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
Designation Fast transients (burst)
Standards/regulations EN 61000-4-4
Typical deviation from the measuring range final value 1 %
Designation Conducted interferences
Standards/regulations EN 61000-4-6

Safety data

Max. output voltage Uo 27.7 V
Max. output current Io 92 mA
Max. output power Po 633 mW
Group IIC
Max. external inductivity Lo 2 mH
Max. external capacitance Co 85 nF
Group IIB
Max. external inductivity Lo 4 mH
Max. external capacitance Co 663 nF
Safety-related maximum voltage Um 253 V AC (125 V DC)

Safety characteristic data

Integrity requirement IEC 61508 - Low demand
Equipment type Type A
Safety Integrity Level (SIL) 2
Safe Failure Fraction (SFF) 94.68 %
ΛSU 4.965 x 10-⁷ (496.5 FIT)
ΛSD 0
ΛDU 2.79 x 10-⁸ (27.9 FIT)
ΛDD 0
Probability of a hazardous failure on demand (PFDAVG) 1.22 x 10-⁴ (1 year)
Probability of a hazardous failure on demand (PFDAVG) 6.1 x 10-⁴ (5 years)
Probability of a hazardous failure on demand (PFDAVG) 12.2 x 10-⁴ (10 years)
Diagnostic coverage (DC) DCS=0 %, DCD=0 %
Integrity requirement IEC 61508 - High demand
Probability of a hazardous failure per hour (PFHD) 2,79 x 10-⁸

Standards and Regulations

Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
Standards/regulations EN 61000-4-4
Designation Conducted interferences
Standards/regulations EN 61000-4-6
Conformance CE-compliant, additionally EN 61326
ATEX II (1) G [Ex ia Ga] IIC/IIB
ATEX II (1) D [Ex ia Da] IIIC
ATEX II 3(1) G Ex nA [ia Ga] IIC/IIB T4 Gc
IECEx [Ex ia Ga] IIC/IIB
IECEx [Ex ia Da] IIIC
IECEx Ex nA [ia Ga] IIC/IIB T4 Gc
UL, USA/Canada Class I Div 2; IS for Class I, II, III Div 1
DNV GL-Temperature B
DNV GL-Humidity B
DNV GL-Vibration A
DNV GL-EMC B
DNV GL-Enclosure Required protection according to the Rules shall be provided upon installation on board
Group IIC
Group IIB

Power supply

Nominal supply voltage 24 V DC
Supply voltage range 19.2 V DC - 30 V DC (24 V DC -20%...+25%)
Max. current consumption < 46 mA (at 24 V DC / 20 mA)
Power dissipation < 1.1 W (at 24 V DC / 20 mA)