- Mechanical Robustness
- vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 || vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 || shocks 15 gn 11 ms IEC 60068-2-27
- Line Rated Current
- 50 A
- [Ue] Rated Operational Voltage
- 690 V AC 50/60 Hz IEC 60947-2
- Height
- 155 mm
- Phase Failure Sensitivity
- yes IEC 60947-4-1
- Rated Duty
- continuous IEC 60947-4-1
- Magnetic Tripping Current
- 850-850 A
- [Ith] Conventional Free Air Thermal Current
- 115 A IEC 60947-4-1
- Motor Power Kw
- 11-11 kW 400...415 V AC 50/60 Hz || 15-15 kW 500 V AC 50/60 Hz || 18.5-18.5 kW 660...690 V AC 50/60 Hz || 15-15 kW 400...415 V AC 50/60 Hz || 18.5-18.5 kW 400...415 V AC 50/60 Hz || 22-22 kW 400...415 V AC 50/60 Hz || 18.5-18.5 kW 500 V AC 50/60 Hz || 22-22 kW 500 V AC 50/60 Hz || 30-30 kW 500 V AC 50/60 Hz || 22-22 kW 660...690 V AC 50/60 Hz || 30-30 kW 660...690 V AC 50/60 Hz || 37-37 kW 660...690 V AC 50/60 Hz || 45-45 kW 660...690 V AC 50/60 Hz
- Maximum Operating Rate
- 25 cyc/h
- Operating Position
- any position
- Connections - Terminals
- EverLink BTR screw connectors top) 1 1.5-70 mm² - solid || EverLink BTR screw connectors top) 1 1.5-50 mm² - flexible || EverLink BTR screw connectors bottom) 1 2.5-95 mm² - solid || EverLink BTR screw connectors bottom) 1 2.5-70 mm² - flexible
- Utilisation Category
- category A IEC 60947-2 || AC-3 IEC 60947-4-1
- Net Weight
- 1.45 kg
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV IEC 60947-2
- Control Type
- toggle
- Power Dissipation Per Pole
- 4.6 W
- Electrical Durability
- 20000 cycles AC-3 440 V In/2 || 10000 cycles AC-3 440 V In
- Breaking Capacity
- 120 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 || 70 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 30 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 18 kA Icu 525 V AC 50/60 Hz IEC 60947-2 || 100 kA 208Y/120 V AC 50/60 Hz UL 60947 || 100 kA 240 V AC 50/60 Hz UL 60947 || 65 kA 480Y/277 V AC 50/60 Hz UL 60947 || 10 kA Icu 660...690 V AC 50/60 Hz IEC 60947-2 || 25 kA 600Y/347 V AC 50/60 Hz UL 60947
- Suitability For Isolation
- yes IEC 60947-1
- [Ui] Rated Insulation Voltage
- 800 V AC 50/60 Hz IEC 60947-2
- Tightening Torque
- 9 N.m 16-95 mm² || 5 N.m 1.5-10 mm²
- Mechanical Durability
- 40000 cycles
- Poles Description
- 3P
- Color
- Gray RAL 7016)
- Width
- 81 mm
- Depth
- 116 mm