Schneider Electric
GV4AU286
1 / 1
Opis
Końcówka Serii
TeSys GV electrical trip unit, MN undervoltage release, 277V AC 60Hz, for motor circuit breakers GV4. Opening of the the circuit breaker is ensured when the control voltage drops below 0.35 Uc, and possible between 0.35-0.7 Uc. Closing of the circuit breaker is possible when the control voltage is in limits 0.85-1.1 Uc. To be plugged inside the circuit breaker, connection by spring terminals. Multi standards certified (IEC, UL, CSA), Green Premium compliant (RoHS/REACh).- Country of Origin
- FR
- Part Number
- GV4AU286
- Tariff Code
- 85363010
- EAN
- 3606485444857
- UNSPSC
- 39121010
- Termin płatności do 90 dni od 500+ dostawców.
- Rabaty na odsprzedaż do 40%!
Wyślij zapytanie o cenę
1
Metody płatności:
Specifications
- [Uc] Control Circuit Voltage
- 277 V AC 60 Hz
- Range Compatibility
- TeSys (TeSys GV4) || TeSys (TeSys BV4)
- Product Or Component Type
- voltage release
- Range
- TeSys
- Voltage Release Type
- undervoltage release
- Device Application
- control
- Device Short Name
- MN
Complementary
- Maximum Inrush Power In Va
- 7 VA
- Connections - Terminals
- spring terminals 1 0.5-1.5 mm² flexible without cable end
- Wire Stripping Length
- 8 mm
- [Ui] Rated Insulation Voltage
- 277 V IEC 60947-1
- Mounting Mode
- internal mounting
- Mechanical Durability
- 20000 cycles
- Maximum Hold-In Power Consumption In Va
- 7 VA
- Threshold Tripping Voltage
- < 0.35 Un failsafe opening || 0.35...0.7 Un possible opening || 0.85...1.1 Un enabled closing
- Operating Time
- < 50 ms
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Eu Rohs Directive
- Compliant
Environment
- Quantity Per Set
- set of 1
Modele CAD
traceparts