1 / 1
thumbnail

Opis

Końcówka Serii
Square D LA molded case circuit breakers provide thermal magnetic protection. Their primary function is automatic opening of a circuit under overload or short circuit conditions or manual opening. LA circuit breakers contain thermal (overload) and magnetic (short circuit) sensing elements in each pole. Push-to-Trip allows the circuit breaker to be manually tripped without exposure to live parts. This Square D LA molded case circuit breaker is a 3 pole unit mount breaker, 300A and 600VAC. The thermal magnetic circuit breaker has an interrupting rating of 22kA for 600VAC and 10kA for 250VDC. LA breakers are UL 489, CSA, IEC certified.
Country of Origin
MX
Part Number
LAL36300
Tariff Code
8536200020
EAN
39121601
UPC
785901426783
UNSPSC
39121601
€791.12
net
€899.00
Darmowa wysyłka!
1
Metody płatności:
Najlepsza oferta od:
NLZaufany dostawca Automa.Net
Dostępność:
2 szt.
W magazynie
Zaktualizowano: 19-11-2024
Gwarancja:
24 miesiące
Szacowany czas dostawy:
28 listopada do Wielka Brytania
Stan produktu:
Po Regeneracji
Po Regeneracji - Produkt odnowiony, sprawdzony, wyczyszczony i naprawiony do pełnej sprawności przez producenta lub certyfikowanego technika. Produkt jest w doskonałym stanie i w pełni sprawny.
Informacje o wysyłce
Bezpieczny proces płatności
Zasady zwrotów i reklamacji
Zasady wysyłki
Gwarancja

Environment

Product Certifications
IEC || UL Listed || CSA

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1410004EN
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
N/A
Eu Rohs Directive
Compliant with Exemptions
Halogen Content Performance
Halogen free plastic parts product

Complementary

Terminal Identifier
AL400LA
Height
11 in
Tightening Torque
13-13 N.m 42-304 mm² (AWG 1...600 kcmil) || 13-13 N.m 42-127 mm² (AWG 1...250 kcmil)
Magnetic Tripping Current
3000-3000 A
Electrical Connection
lugs, load || lugs, line
Magnetic Hold Current
1500 A
Circuit Breaker Application
HACR rated
Mounting Mode
unit mount
Poles Description
3P
Line Rated Current
300 A
Width
6 in
Depth
5.84 in

Specifications

Trip Unit Technology
thermal-magnetic
Product Or Component Type
circuit breaker

Dokumenty

Data Sheet

Pobierz