- Non-Overlap Time
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Minimum Switching Current
- 5 mA for signalling circuit
- Power Dissipation Per Pole
- 24 W AC-1 || 13.5 W AC-3 || 13.5 W AC-3e
- Average Impedance
- 0.6 mOhm - Ith 200 A 50 Hz for power circuit
- Auxiliary Contact Composition
- 1 NO + 1 NC
- [Ith] Conventional Free Air Thermal Current
- 200 A (at 60 °C) for power circuit
- Control Circuit Voltage Limits
- 0.3...0.5 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.15 Uc -40-55 °C operational AC 50/60 Hz || 1...1.15 Uc 55-70 °C operational AC 50/60 Hz
- Mounting Support
- rail || plate
- Contact Compatibility
- M13
- Control Circuit Type
- AC 50/60 Hz
- Safety Reliability Level
- B10d = 684932 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 10000000 cycles contactor with mechanical load EN/ISO 13849-1
- Pollution Degree
- 3
- Insulation Resistance
- > 10 MOhm for signalling circuit
- Rated Breaking Capacity
- 1400 A at 440 V for power circuit conforming to IEC 60947
- Irms Rated Making Capacity
- 140 A AC for signalling circuit conforming to IEC 60947-5-1 || 250 A DC for signalling circuit conforming to IEC 60947-5-1 || 1660 A at 440 V for power circuit conforming to IEC 60947
- Associated Fuse Rating
- 10 A gG for signalling circuit conforming to IEC 60947-5-1 || 315 A gG at <= 690 V coordination type 1 for power circuit || 250 A gG at <= 690 V coordination type 2 for power circuit
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV IEC 60947
- Inrush Power In Va
- 280-350 VA 60 Hz cos phi 0.9 (at 20 °C) || 280-350 VA 50 Hz cos phi 0.9 (at 20 °C)
- Pole Contact Composition
- 3 NO
- Connections - Terminals
- control circuit: lugs-ring terminals - external diameter: 8 mm || power circuit: lugs-ring terminals - external diameter: 25 mm || power circuit: bars 1 - busbar cross section: 5 x 25 mm
- Coil Technology
- built-in bidirectional peak limiting diode suppressor
- Operating Time
- 20...35 ms closing || 40...75 ms opening
- Minimum Switching Voltage
- 17 V for signalling circuit
- Maximum Operating Rate
- 1200 cyc/h 60 °C
- Signalling Circuit Frequency
- 25...400 Hz
- Tightening Torque
- control circuit 1.2 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.2 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 12 N.m lugs-ring terminals hexagonal 13 mm M8 || power circuit 12 N.m bars hexagonal 13 mm M8 || control circuit 1.2 N.m lugs-ring terminals pozidriv No 2 M3.5
- Electrical Durability
- 0.85 Mcycles 150 A AC-3 <= 440 V || 1 Mcycles 200 A AC-1 <= 440 V || 0.85 Mcycles 150 A AC-3e <= 440 V
- Mechanical Durability
- 8 Mcycles
- Auxiliary Contacts Type
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Compatibility Code
- LC1D
- Hold-In Power Consumption In Va
- 2-18 VA 60 Hz cos phi 0.9 (at 20 °C) || 2-18 VA 50 Hz cos phi 0.9 (at 20 °C)
- Overvoltage Category
- III
- Maximum Horse Power Rating
- 40 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 50 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 100 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 125 hp at 575/600 V AC 50/60 Hz for 3 phase motors
- Motor Power Kw
- 40 kW at 220...230 V AC 50/60 Hz (AC-3) || 75 kW at 380...400 V AC 50/60 Hz (AC-3) || 80 kW at 415...440 V AC 50/60 Hz (AC-3) || 90 kW at 500 V AC 50/60 Hz (AC-3) || 100 kW at 660...690 V AC 50/60 Hz (AC-3) || 75 kW at 1000 V AC 50/60 Hz (AC-3) || 22 kW at 400 V AC 50/60 Hz (AC-4) || 40 kW at 220...230 V AC 50/60 Hz (AC-3e) || 75 kW at 380...400 V AC 50/60 Hz (AC-3e) || 80 kW at 415...440 V AC 50/60 Hz (AC-3e) || 90 kW at 500 V AC 50/60 Hz (AC-3e) || 100 kW at 660...690 V AC 50/60 Hz (AC-3e) || 75 kW at 1000 V AC 50/60 Hz (AC-3e)
- [Ui] Rated Insulation Voltage
- power circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
- [Icw] Rated Short-Time Withstand Current
- 250 A 40 °C - 10 min for power circuit || 580 A 40 °C - 1 min for power circuit || 1200 A 40 °C - 10 s for power circuit || 1400 A 40 °C - 1 s for power circuit || 100 A - 1 s for signalling circuit || 120 A - 500 ms for signalling circuit || 140 A - 100 ms for signalling circuit
- Heat Dissipation
- 3-4.5 W at 50/60 Hz
- Protective Cover
- with