Schneider Electric
LC1D50A6RD
IEC contactor, TeSys D, nonreversing, 50A, 40HP at 480VAC, 3 phase, 3 pole, 3 NO, 440VDC coil, open style
- Termin płatności do 90 dni od 500+ dostawców.
- Rabaty na odsprzedaż do 40%!
Wyślij zapytanie o cenę
1
Metody płatności:
Stan produktu:
Oferta z czasem realizacji przez producenta
Wysyłka:Na zapytanie
Najlepsza cena:
Wyślij zapytanie o cenę
Additional Information
- Part Number
- LC1D50A6RD
- UNSPSC
- 39121529
- Tariff Code
- 8536490065
- Country of Origin
- FR
Specifications
- [Uc] Control Circuit Voltage
- 440 V DC
- [Ue] Rated Operational Voltage
- power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
- Range Of Product
- TeSys Deca
- Contactor Application
- motor control || resistive load
- Product Or Component Type
- contactor
- Range
- TeSys
- Utilisation Category
- AC-4 || AC-1 || AC-3 || AC-3e
- [Ie] Rated Operational Current
- 50 A 60 °C) <= 440 V AC AC-3 power circuit || 80 A 60 °C) <= 440 V AC AC-1 power circuit || 50 A 60 °C) <= 440 V AC AC-3e power circuit
- Poles Description
- 3P
- Device Short Name
- LC1D
Contractual warranty
- Warranty
- 18 months
Complementary
- Non-Overlap Time
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Minimum Switching Current
- 5 mA signalling circuit
- Power Dissipation Per Pole
- 3.7 W AC-3 || 9.6 W AC-1 || 3.7 W AC-3e
- Average Impedance
- 1.5 mOhm - Ith 80 A 50 Hz power circuit
- Auxiliary Contact Composition
- 1 NO + 1 NC
- [Ith] Conventional Free Air Thermal Current
- 10 A 60 °C signalling circuit || 80 A 60 °C power circuit
- Control Circuit Voltage Limits
- 0.1...0.3 Uc -40-70 °C drop-out DC || 0.75...1.25 Uc -40-60 °C operational DC || 1...1.25 Uc 60-70 °C operational DC
- Mounting Support
- rail || plate
- Contact Compatibility
- M4
- Control Circuit Type
- DC standard
- Safety Reliability Level
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Pollution Degree
- 3
- Hold-In Power Consumption In W
- 7.4-7.4 W 20 °C
- Insulation Resistance
- > 10 MOhm signalling circuit
- Rated Breaking Capacity
- 900 A 440 V power circuit IEC 60947
- Irms Rated Making Capacity
- 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 900 A 440 V power circuit IEC 60947
- Associated Fuse Rating
- 10 A gG signalling circuit IEC 60947-5-1 || 100 A gG <= 690 V type 1 power circuit || 100 A gG <= 690 V type 2 power circuit
- [Uimp] Rated Impulse Withstand Voltage
- 6 kV IEC 60947
- Pole Contact Composition
- 3 NO
- Connections - Terminals
- control circuit lugs-ring terminals 8 mm || power circuit lugs-ring terminals 16.5 mm
- Coil Technology
- built-in bidirectional peak limiting diode suppressor
- Time Constant
- 34 ms
- Operating Time
- 42.5...57.5 ms closing || 16...24 ms opening
- Minimum Switching Voltage
- 17 V signalling circuit
- Maximum Operating Rate
- 3600 cyc/h 60 °C
- Signalling Circuit Frequency
- 25...400 Hz
- Tightening Torque
- control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 6 N.m lugs-ring terminals hexagonal 10 mm M6 || control circuit 1.7 N.m lugs-ring terminals pozidriv No 2 M3.5
- Electrical Durability
- 1.45 Mcycles 50 A AC-3 <= 440 V || 0.5 Mcycles 80 A AC-1 <= 440 V || 1.45 Mcycles 50 A AC-3e <= 440 V
- Mechanical Durability
- 10 Mcycles
- Inrush Power In W
- 19-19 W 20 °C)
- Auxiliary Contacts Type
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Compatibility Code
- LC1D
- Overvoltage Category
- III
- Maximum Horse Power Rating
- 3 hp 115 V at AC 50/60 Hz for 1 phase || 7.5 hp 230/240 V at AC 50/60 Hz for 1 phase || 15 hp 200/208 V at AC 50/60 Hz for 3 phase || 15 hp 230/240 V at AC 50/60 Hz for 3 phase || 40 hp 460/480 V at AC 50/60 Hz for 3 phase || 40 hp 575/600 V at AC 50/60 Hz for 3 phase
- Motor Power Kw
- 15 kW 220...230 V AC 50/60 Hz AC-3) || 22 kW 380...400 V AC 50/60 Hz AC-3) || 30 kW 500 V AC 50/60 Hz AC-3) || 33 kW 660...690 V AC 50/60 Hz AC-3) || 25 kW 415 V AC 50/60 Hz AC-3) || 30 kW 440 V AC 50/60 Hz AC-3) || 11 kW 400 V AC 50/60 Hz AC-4) || 15 kW 220...230 V AC 50/60 Hz AC-3e) || 22 kW 380...400 V AC 50/60 Hz AC-3e) || 30 kW 500 V AC 50/60 Hz AC-3e) || 33 kW 660...690 V AC 50/60 Hz AC-3e) || 25 kW 415 V AC 50/60 Hz AC-3e) || 30 kW 440 V AC 50/60 Hz AC-3e)
- [Ui] Rated Insulation Voltage
- power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
- [Icw] Rated Short-Time Withstand Current
- 400 A 40 °C - 10 s power circuit || 810 A 40 °C - 1 s power circuit || 84 A 40 °C - 10 min power circuit || 208 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
- Protective Cover
- with
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP1503009EN
- Sustainable Offer Status
- Green Premium product
- Pvc Free
- Yes
- Reach Regulation
- Free of Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: Cancer - www.P65Warnings.ca.gov
- Reach Free Of Svhc
- Yes
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Circularity Profile
- ENVEOLI1503009EN
- Eu Rohs Directive
- Compliant
Environment
- Product Certifications
- GOST || BV || RINA || DNV || GL || LROS (Lloyds register of shipping) || CCC || CSA || UL
- Height
- 122 mm
- Standards
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
- Climatic Withstand
- IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
- Net Weight
- 0.93 kg
- Flame Retardance
- V1 conforming to UL 94
- Protective Treatment
- THIEC 60068-2-30
- Ip Degree Of Protection
- IP20 front face IEC 60529
- Mechanical Robustness
- vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 10 Gn for 11 ms)
- Operating Altitude
- 0...9842.52 ft (0...3000 m)
- Fire Resistance
- 850 °C IEC 60695-2-1
- Width
- 55 mm
- Depth
- 120 mm
- Permissible Ambient Air Temperature Around The Device
- -40-60 °C || 60-70 °C with derating
Dokumenty
Data Sheet
PobierzModele CAD
traceparts
PobierzInne kategorie
SiłownikiBlokiKable, rury i wężeSprężarkiSterowanieŁączniki i osprzętCylindry i tłokiElektronikaFiltryHVACKomputery przemysłowe i interfejsy HMIOświetlenieTechnika liniowaSilnikiZasilaniePrzeniesienie napęduPompy i zaworyEnergia odnawialnaRobotykaUszczelki, pierścienie i złączaCzujniki i urządzenia pomiaroweNarzędzia i akcesoriaCNCInne