Schneider Electric
RM22UB34
voltage control relay, Harmony Control Relays, 8A, 2CO, 80…300V AC DC, 110…240V AC DC
- Termin płatności do 90 dni od 500+ dostawców.
- Rabaty na odsprzedaż do 40%!
£39.20
1
Metody płatności:
Łącznie 126 części w magazynie od 24 dostawców
Stan produktu:
Oferta z czasem realizacji przez producenta
Wysyłka:Na zapytanie
Najlepsza cena:
€50.29
Additional Information
- Part Number
- RM22UB34
- UNSPSC
- 39122329
- Tariff Code
- 8536490080
- Country of Origin
- ID
Specifications
- Minimum Switching Current
- 10 mA 5 V DC
- Maximum Switching Current
- 8 A AC
- Range Of Product
- Harmony Control Relays
- Measurement Range
- 80...300 V voltage AC/DC 50/60 Hz
- Power Consumption In Va
- 5-5 VA AC
- Switching Capacity In Va
- 2000 VA
- Product Or Component Type
- voltage control relay
- Phase
- 1 phase
- Utilisation Category
- AC-15 IEC 60947-5-1 || DC-13 IEC 60947-5-1 || AC-1 IEC 60947-4-1 || DC-1 IEC 60947-4-1
- Relay Name
- RM22UA
- Contacts Type And Composition
- 2 C/O
- Relay Type
- voltage control relay
- Time Delay Type
- adjustable 0.1...30 s, +/- 10 % of the full scale value on crossing the threshold Tt
- Relay Monitored Parameters
- overvoltage and undervoltage detection
- Supply Circuit Type
- AC/DC
Complementary
- [Us] Rated Supply Voltage
- 110...240 V AC/DC 50/60 Hz
- Safety Reliability Data
- MTTFd = 433.7 years || B10d = 400000
- Maximum Measuring Cycle
- 250 ms measurement cycle as true rms value
- Hysteresis
- 5-50 % adjustable threshold setting
- Insulation Resistance
- > 100 MOhm 500 V DC
- Measurement Error
- < 1 % over the whole range with voltage variation || 0.2 %/°C with temperature variation
- Output Contacts
- 2 C/O
- Contacts Material
- cadmium free
- Immunity To Microbreaks
- 20 ms
- Response Time
- <= 500 ms
- Net Weight
- 0.09 kg
- Maximum Switching Voltage
- 250 V AC
- Reset Time
- 1500 ms at maximum voltage
- Run-Up Delay At Power-Up
- 600 ms
- Connections - Terminals
- screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end || screw terminals, 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end
- Functionality
- overvoltage and undervoltage detection
- Overvoltage Category
- III IEC 60664-1
- Supply Voltage Limits
- 60-280 V AC
- Mounting Support
- 35 mm DIN rail conforming to IEC 60715
- Nominal Output Current
- 8 A
- Mechanical Durability
- 10000000 cycles
- Compatibility Code
- RM22
- Housing Material
- self-extinguishing plastic
- Width
- 22.5 mm
- Tightening Torque
- 0.6-1 N.m IEC 60947-1
- Maximum Power Consumption In W
- 2 W DC
- Electrical Durability
- 100000 cycles
- Repeat Accuracy
- +/- 0.5 % input and measurement circuit || +/- 2 % time delay
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP1504008EN
- Sustainable Offer Status
- Green Premium product
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- X
- Circularity Profile
- ENVEOLI1504008EN
- Eu Rohs Directive
- Pro-active compliance (Product out of EU RoHS legal scope)
Environment
- Product Certifications
- CCC || CE || CSA || EAC || UL || GL || RCM
- Standards
- IEC 60255-1
- Dielectric Test Voltage
- 2.5 kV AC 50 Hz, 1 min IEC 60255-27
- Electromagnetic Compatibility
- immunity for residential, commercial and light-industrial environments conforming to IEC 61000-6-1 || immunity for industrial environments conforming to IEC 61000-6-2 || emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3 || emission standard for industrial environments conforming to IEC 61000-6-4 || electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2 || electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test - test level: 10 V/m level 3 conforming to IEC 61000-4-3 || electrical fast transient/burst immunity test - test level: 4 kV level 4 (direct) conforming to IEC 61000-4-4 || electrical fast transient/burst immunity test - test level: 2 kV level 4 (capacitive coupling) conforming to IEC 61000-4-4 || surge immunity test - test level: 4 kV level 4 (common mode) conforming to IEC 61000-4-5 || surge immunity test - test level: 2 kV level 4 (differential mode) conforming to IEC 61000-4-5 || conducted and radiated emissions class B group 1 conforming to CISPR 11 || conducted and radiated emissions class B conforming to CISPR 22
- Shock Resistance
- 15 gn 11 ms) not in operation IEC 60068-2-27 || 5 gn 11 ms) in operation IEC 60068-2-27
- Ambient Air Temperature For Operation
- -20-50 °C 60 Hz || -20-60 °C 50 Hz
- Vibration Resistance
- 0.075 mm 10-58.1 Hz) not in operation IEC 60068-2-6 || 1 gn 10-58.1 Hz) not in operation IEC 60068-2-6 || 0.035 mm 58.1-150 Hz) in operation IEC 60068-2-6 || 0.5 gn 58.1-150 Hz) in operation IEC 60068-2-6
- Ip Degree Of Protection
- IP20 IEC 60529 terminals) || IP40 IEC 60529 housing) || IP50 IEC 60529 front panel)
- Pollution Degree
- 3 IEC 60664-1
- Ambient Air Temperature For Storage
- -40-70 °C
- Relative Humidity
- 93-97 % 25-55 °C IEC 60068-2-30
Dokumenty
Data Sheet
PobierzModele CAD
traceparts
PobierzInne kategorie
SiłownikiBlokiKable, rury i wężeSprężarkiSterowanieŁączniki i osprzętCylindry i tłokiElektronikaFiltryHVACKomputery przemysłowe i interfejsy HMIOświetlenieTechnika liniowaSilnikiZasilaniePrzeniesienie napęduPompy i zaworyEnergia odnawialnaRobotykaUszczelki, pierścienie i złączaCzujniki i urządzenia pomiaroweNarzędzia i akcesoriaCNCInne