- [Uc] Control Circuit Voltage
- 110 V AC 50 Hz || 120 V AC 60 Hz
- [Icm] Rated Short-Circuit Making Capacity
- 60 A 120 V AC inductive control circuit UL 508 || 0.8 A 250 V DC resistive control circuit UL 508 || 30 A 240 V AC inductive control circuit UL 508 || 15 A 480 V AC inductive control circuit UL 508 || 12 A 600 V AC inductive control circuit UL 508 || 10 A <= 600 V AC resistive control circuit UL 508 || 1.1 A 125 V DC inductive control circuit UL 508 || 0.55 A 250 V DC inductive control circuit UL 508 || 0.2 A 301...600 V DC inductive control circuit UL 508 || 4 A 125 V DC inductive control circuit UL 508
- Height
- 3.5 in
- Control Circuit Voltage Limits
- operational 0.85...1.1 Uc AC 50/60 Hz
- Mounting Support
- panel
- Hold-In Power Consumption In Va
- 23-23 VA 60 Hz || 25-25 VA 50 Hz
- Electrical Connection
- screw clamp terminals
- Contacts Type And Composition
- 4 NO 4 standard contact cartridges
- Rated Breaking Capacity
- 6 A 120 V AC inductive control circuit UL 508 || 0.8 A 250 V DC resistive control circuit UL 508 || 3 A 240 V AC inductive control circuit UL 508 || 1.5 A 480 V AC inductive control circuit UL 508 || 1.2 A 600 V AC inductive control circuit UL 508 || 10 A <= 600 V AC resistive control circuit UL 508 || 1.1 A 125 V DC inductive control circuit UL 508 || 0.55 A 250 V DC inductive control circuit UL 508 || 0.2 A 301...600 V DC inductive control circuit UL 508 || 4 A 125 V DC resistive control circuit UL 508
- Operating Time
- 15 ms - pick-up || 16 ms - drop-out
- Awg Gauge
- AWG 18...AWG 12 copper
- Width
- 2.23 in
- Tightening Torque
- control circuit 1.02-1.36 N.m screw terminals
- Depth
- 3.95 in
- Inrush Power In Va
- 148-148 VA 60 Hz || 143-143 VA 50 Hz