- Maximum Switching Capacity
- 3750 VA || 420 W
- Safety Reliability Data
- B10d = 100000
- Operating Rate
- <= 1200 cycles/hour under load || <= 18000 cycles/hour no-load
- Protection Category
- RT I
- Test Levels
- level A group mounting
- Electrical Durability
- 100000 cycles resistive
- Contacts Material
- AgNi
- Average Coil Consumption In Va
- 1.6 60 Hz
- Shape Of Pin
- flat
- Reset Time
- 20 ms at nominal voltage
- Net Weight
- 0.026 kg
- Maximum Switching Voltage
- 250 V IEC
- Average Resistance
- 4430 Ohm at 20 °C +/- 15 %
- Device Presentation
- complete product
- Rated Operational Voltage Limits
- 96...132 V AC
- Pollution Degree
- 3
- [Ie] Rated Operational Current
- 15 A 277 V AC) UL || 15 A 28 V DC) UL || 15 A 250 V AC) NO IEC || 15 A 28 V DC) NO IEC || 7.5 A 250 V AC) NC IEC || 7.5 A 28 V DC) NC IEC
- [Ui] Rated Insulation Voltage
- 250 V IEC || 300 V CSA || 300 V UL
- Mechanical Durability
- 10000000 cycles
- Operating Position
- any position
- Operating Time
- 20 ms at nominal voltage
- Load Current
- 15 A 250 V AC || 15 A 28 V DC
- Drop-Out Voltage Threshold
- >= 0.15 Uc AC
- [Uimp] Rated Impulse Withstand Voltage
- 4 kV 1.2/50 µs
- Minimum Switching Capacity
- 170 mW 10 mA, 17 V