- Network Frequency
- 47...63 Hz
- Power Dissipation
- <= 8 W || 6 W
- Height
- 141.5 mm
- Operating Rate
- 3000 cyc/h 0.5 A inductive
- Terminals Description Plc N°2
- (3)OUT_DIS#3 || (6)OUT_DIS#6 || (1N)PW || (2)OUT_DIS#2 || (1L1)PW || (8)OUT_DIS#8 || (7)OUT_DIS#7 || (1)OUT_DIS#1 || (4)OUT_DIS#4 || (5)OUT_DIS#5 || TB_1
- Terminals Description Plc N°1
- (8)IN_DIS#8 || (5)IN_DIS#5 || (9)IN_DIS#9 || (4)IN_DIS#4 || (10)IN_DIS#10 || (3)IN_DIS#3 || (L1)PW || (N)PW || (6)IN_DIS#6 || (7)IN_DIS#7 || (1)IN_DIS#1 || TB || (2)IN_DIS#2
- Maximum Voltage Drop
- <1.5 V 0.5 A at state 1 output circuit
- Isolation Between Channels And Bus
- 1780 V AC
- Current Consumption
- 160 mA 120 V AC
- Current State 1 Guaranteed
- >= 6 mA
- Marking
- CE
- Current State 0 Guaranteed
- <= 2.6 mA
- Input Voltage Limits
- 74...132 V
- Response Time
- 1/2 x 1/f from state 0 to state 1 on input || 1/2 x 1/f from state 0 to state 1 on output || 1/2 x 1/f from state 1 to state 0 on input || 1/2 x 1/f from state 1 to state 0 on output
- Net Weight
- 0.22 kg
- Voltage State 0 Guaranteed
- < 20 V
- Maximum Leakage Current
- 1.3 mA 120 V output circuit)
- Voltage State 1 Guaranteed
- > 74 V
- Input Resistance
- 4 kOhm
- Protection Type
- internal 2 x 2.5 A slow-blow fuses
- Width
- 125 mm
- Depth
- 47.5 mm
- Discrete Output Current
- 2 A per group || 4 A per module || 30 mA...0.5 A per point
- [Us] Rated Supply Voltage
- 120 V AC