Schneider Electric
ATS48C41YS316
1 / 1
- Part Number
- ATS48C41YS316
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Specifications
- Product Destination
- asynchronous motors
- Range Of Product
- Altistart 48
- Product Or Component Type
- soft starter
- Motor Power Kw
- 110 kW 230 V for standard applications || 160 kW 400 V for severe applications || 160 kW 440 V for severe applications || 220 kW 400 V for standard applications || 220 kW 440 V for standard applications || 220 kW 500 V for severe applications || 220 kW 525 V for severe applications || 250 kW 500 V for standard applications || 250 kW 525 V for standard applications || 250 kW 660 V for severe applications || 315 kW 690 V for severe applications || 355 kW 660 V for standard applications || 400 kW 690 V for standard applications || 90 kW 230 V for severe applications
- Utilisation Category
- AC-53A
- [Us] Rated Supply Voltage
- 208...690 V - 15...10 %
- Product Specific Application
- heavy duty industry and pumps
- Maximum Horse Power Rating
- 100 hp 208 V for severe applications || 125 hp 208 V for standard applications || 125 hp 230 V for severe applications || 150 hp 230 V for standard applications || 250 hp 460 V for severe applications || 300 hp 460 V for standard applications || 300 hp 575 V for severe applications || 350 hp 575 V for standard applications
- Device Short Name
- ATS48
- Supply Frequency
- 50...60 Hz - 5...5 %
Complementary
- Product Certifications
- DNV || GOST || C-tick || TCF || CSA || UL || NOM 117 || CCC || SEPRO
- Device Connection
- in the motor supply line || to the motor delta terminals
- Height
- 670 mm
- Standards
- EN/IEC 60947-4-2
- Analogue Output Type
- current output AO 0-20 mA or 4-20 mA 500 Ohm
- Marking
- CE
- Net Weight
- 51.4 kg
- Connector Type
- 1 RJ45
- Communication Data Link
- serial
- Function Available
- external bypass (optional)
- Discrete Output Number
- 2
- Communication Port Protocol
- Modbus
- Discrete Input Type
- PTC, 750 Ohm 25 °C || Stop, Run, LI3, LI4) logic, <= 8 mA 4300 Ohm
- Minimum Switching Current
- 10 mA 6 V DC relay outputs
- Physical Interface
- RS485 multidrop
- Discrete Input Number
- 5
- Operating Position
- vertical +/- 10 degree
- Width
- 400 mm
- Transmission Rate
- 4800, 9600 or 19200 bps
- Depth
- 300 mm
- Discrete Input Logic
- positive logic Stop, Run, LI3, LI4 < 5 V <= 2 mA > 11 V, >= 5 mA
- Protection Type
- phase failure line || thermal protection motor || thermal protection starter
- Discrete Output Type
- LO1) logic output 0 V common configurable || LO2) logic output 0 V common configurable || R1) relay outputs fault relay NO || R2) relay outputs end of starting relay NO || R3) relay outputs motor powered NO
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP111033EN
- Sustainable Offer Status
- Green Premium product
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- X
- Circularity Profile
- ENVEOLI111009EN
- Eu Rohs Directive
- Pro-active compliance (Product out of EU RoHS legal scope)
Environment
- Electromagnetic Compatibility
- conducted and radiated emissions level A IEC 60947-4-2 || damped oscillating waves level 3 IEC 61000-4-12 || electrostatic discharge level 3 IEC 61000-4-2 || immunity to electrical transients level 4 IEC 61000-4-4 || immunity to radiated radio-electrical interference level 3 IEC 61000-4-3 || voltage/current impulse level 3 IEC 61000-4-5
- Ambient Air Temperature For Operation
- 40-60 °C with current derating of 2 % per °C) || -10-40 °C without derating)
- Ambient Air Temperature For Storage
- -25-70 °C
- Relative Humidity
- 0-95 % without condensation or dripping water EN/IEC 60068-2-3
- Operating Altitude
- <= 3280.84 ft (1000 m) without derating || > 3280.84...6561.68 ft (> 1000...2000 m) with current derating of 2.2 % per additional 100 m
Documents
Data Sheet
DownloadOther Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther