Schneider Electric
ATV630U22S6X
1 / 1
Description
Active Mature
- Country of Origin
- ID
- Part Number
- ATV630U22S6X
- Tariff Code
- 8504404000
- EAN
- 39122001
- UNSPSC
- 39122001
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Environment
- Product Certifications
- TÜV || UL || CSA
- Power Dissipation In W
- natural convection 82 W 600 V 4 kHz || forced convection 31 W 600 V 4 kHz
- Standards
- UL 508C || IEC 61800-3 || IEC 61800-5-1 || IEC 61000-3-12 || IEC 60721-3 || IEC 61508 || IEC 13849-1
- Insulation Resistance
- > 1 MOhm 500 V DC for 1 minute to earth
- Shock Resistance
- 15 gn 11 ms IEC 60068-2-27
- Vibration Resistance
- 1.5 mm peak to peak 2-13 Hz)IEC 60068-2-6 || 1 gn 13-200 Hz)IEC 60068-2-6
- Noise Level
- 52 dB 86/188/EEC
- Regulation Loop
- adjustable PID regulator
- Operating Altitude
- <= 3280.84 ft (1000 m) without derating || 1000...4800 m with current derating 1 % per 100 m
- Overvoltage Category
- III
- Pollution Degree
- 2
- Electromagnetic Compatibility
- electrostatic discharge immunity test level 3 IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 IEC 61000-4-4 || 1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5 || conducted radio-frequency immunity test level 3 IEC 61000-4-6
- Ambient Air Temperature For Operation
- -15-50 °C without derating) || 50-60 °C with derating factor)
- Volume Of Cooling Air
- 103 m3/h
- Pollution Degree
- 2 IEC 61800-5-1
- Noise Level
- 56 dB
- Ambient Air Temperature For Storage
- -40-70 °C
- Relative Humidity
- 5-95 % without condensation IEC 60068-2-3
- Operating Position
- vertical +/- 10 degree
- Maximum Thdi
- <48 % with external line choke IEC 61000-3-12
Complementary
- Discrete Input Logic
- positive logic (source) DI1...DI8), < 5 V, > 11 V || negative logic (sink) DI1...DI8), > 16 V, < 10 V
- Analogue Output Type
- software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits || software-configurable current AQ1, AQ2 0...20 mA 10 bits || software-configurable current DQ-, DQ+ 30 V DC || software-configurable current DQ-, DQ+ 100 mA
- Discrete Output Type
- relay outputs R1A, R1B, R1C 250 V AC 3000 mA || relay outputs R1A, R1B, R1C 30 V DC 3000 mA || relay outputs R2A, R2C 250 V AC 5000 mA || relay outputs R2A, R2C 30 V DC 5000 mA || relay outputs R3A, R3C 250 V AC 5000 mA || relay outputs R3A, R3C 30 V DC 5000 mA
- Maximum Switching Current
- relay output R1, R2, R3 resistive, cos phi = 1 3 A 250 V AC || relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC || relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DC
- Exchange Mode
- half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
- Phase
- 3 phase
- Net Weight
- 5.5 kg
- Type Of Polarization
- no impedance
- Frequency Resolution
- display unit 0.1 Hz || analog input 0.012/50 Hz
- Relay Output Type
- configurable relay logic R1 fault relay NO/NC 100000 cycles || configurable relay logic R2 sequence relay NO 100000 cycles || configurable relay logic R3 sequence relay NO 100000 cycles
- Maximum Transient Current
- 4.6 A 60 s normal duty) || 4.7 A 60 s heavy duty)
- Analogue Input Number
- 3
- Motor Slip Compensation
- can be suppressed || adjustable || not available in permanent magnet motor law || automatic whatever the load
- Discrete Output Number
- 0
- Method Of Access
- slave Modbus TCP
- Discrete Input Number
- 8
- Local Signalling
- for local diagnostic 3 LEDs || for embedded communication status 3 LEDs (dual colour) || for communication module status 4 LEDs (dual colour) || for presence of voltage 1 LED (red)
- Linearity Error
- AI1, AI2, AI3 +/- 0.15 % of maximum value analog input || AO1, AO2 +/- 0.2 % analog output
- Number Of Addresses
- 1-247 Modbus serial
- Width
- 171 mm
- Transmission Rate
- 10, 100 Mbits || 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
- Depth
- 233 mm
- Analogue Input Type
- AI1, AI2, AI3 software-configurable voltage 0...10 V DC 31.5 kOhm 12 bits || AI1, AI2, AI3 software-configurable current 0...20 mA 250 Ohm 12 bits || AI2 voltage analog input - 10...10 V DC 31.5 kOhm 12 bits
- Sampling Duration
- 2 ms +/- 0.5 ms DI1...DI4) - discrete input || 5 ms +/- 1 ms DI5, DI6) - discrete input || 5 ms +/- 0.1 ms AI1, AI2, AI3) - analog input || 10 ms +/- 1 ms AO1) - analog output
- Electrical Connection
- control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 || motor screw terminal 6...10 mm² AWG 10...AWG 8 || line side screw terminal 6...10 mm² AWG 10...AWG 8
- Maximum Output Frequency
- 500 kHz
- Height
- 409 mm
- Acceleration And Deceleration Ramps
- S, U or customized || linear adjustable separately from 0.01...9999 s
- Transmission Frame
- RTU
- Relay Output Number
- 3
- Data Format
- 8 bits, configurable odd, even or no parity
- Accuracy
- +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input || +/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
- Connector Type
- RJ45 on the remote graphic terminal)Ethernet/Modbus TCP || RJ45 on the remote graphic terminal)Modbus serial
- Input Compatibility
- DI1...DI6 discrete input level 1 PLC IEC 61131-2 || DI5, DI6 discrete input level 1 PLC IEC 65A-68 || STOA, STOB discrete input level 1 PLC IEC 61131-2
- Permissible Temporary Current Boost
- 1.1 x In 60 s normal duty) || 1.5 x In 60 s heavy duty)
- Mounting Mode
- wall mount
- Analogue Output Number
- 2
- Physical Interface
- Ethernet || 2-wire RS 485
- Minimum Switching Current
- relay output R1, R2, R3 5 mA 24 V DC
- Refresh Time
- relay output R1, R2, R3)5 ms +/- 0.5 ms)
- Enclosure Mounting
- wall mounted
- Isolation
- between power and control terminals
- Output Voltage
- <= power supply voltage
- Quantity Per Set
- 1
- Braking To Standstill
- by DC injection
- Discrete Input Type
- DI7, DI8 programmable as pulse input 0-30 kHz, 24 V DC <= 30 V)
- Protection Type
- thermal protection motor || safe torque off motor || motor phase break motor || thermal protection drive || safe torque off drive || overheating drive || overcurrent between output phases and earth drive || overload of output voltage drive || short-circuit protection drive || motor phase break drive || overvoltages on the DC bus drive || line supply overvoltage drive || line supply undervoltage drive || line supply phase loss drive || overspeed drive || break on the control circuit drive
- Supply
- external supply for digital inputs 24 V DC 19-30 V), <1.25 mA overload and short-circuit protection || internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection || internal supply for digital inputs and STO 24 V DC 21-27 V), <200 mA overload and short-circuit protection
Specifications
- Prospective Line Isc
- 70 kA
- Product Destination
- asynchronous motors || synchronous motors
- Line Current
- 2.9 A 600 V normal duty) || 2.1 A 600 V heavy duty)
- Emc Filter
- without EMC filter
- Asynchronous Motor Control Profile
- constant torque standard || optimized torque mode || variable torque standard
- Variant
- standard version
- Product Or Component Type
- variable speed drive
- Apparent Power
- 3 kVA 600 V normal duty) || 2.2 kVA 600 V heavy duty)
- Switching Frequency
- 2...12 kHz adjustable || 4...12 kHz with derating factor
- Communication Port Protocol
- Modbus TCP || Modbus serial || Ethernet
- Product Specific Application
- process and utilities
- Safety Function
- STO (safe torque off) SIL 3
- Maximum Horse Power Rating
- 3 hp 600 V normal duty || 2 hp 600 V heavy duty
- Supply Frequency
- 50...60 Hz - 5...5 %
- Option Card
- slot A communication module, Profibus DP V1 || slot A communication module, PROFINET || slot A communication module, DeviceNet || slot A communication module, Modbus TCP/EtherNet/IP || slot A communication module, CANopen daisy chain RJ45 || slot A communication module, CANopen SUB-D 9 || slot A communication module, CANopen screw terminals || slot A/slot B digital and analog I/O extension module || slot A/slot B output relay extension module || slot A communication module, Ethernet IP/Modbus TCP/MD-Link || communication module, BACnet MS/TP || communication module, Ethernet Powerlink
- Degree Of Protection
- UL type 1 UL 508C
- Range Of Product
- Altivar Process ATV600
- Speed Drive Output Frequency
- 0.1-500 Hz
- Ip Degree Of Protection
- IP21IEC 61800-5-1 || IP21IEC 60529
- [Us] Rated Supply Voltage
- 600 V
- [Us] Rated Supply Voltage
- 600 V - 15...10 %
- Discrete Input Logic
- 16 preset speeds
- Type Of Cooling
- forced convection
- Continuous Output Current
- 4.2 A 4 kHz normal duty || 3.1 A 4 kHz heavy duty
- Nominal Switching Frequency
- 4 kHz
- Device Short Name
- ATV630
- Synchronous Motor Control Profile
- permanent magnet motor || synchronous reluctance motor
Offer Sustainability
- Mercury Free
- Yes
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- X
- Upgradeability
- Upgraded components available
- Rohs Exemption Information
- Yes
- Environmental Disclosure
- ENVPEP1707007EN
- Sustainable Offer Status
- Green Premium product
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Circularity Profile
- ENVEOLI1707007EN
- Eu Rohs Directive
- Pro-active compliance (Product out of EU RoHS legal scope)
Documents
Data Sheet
DownloadCAD Models
traceparts
DownloadOther Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther