The Easergy LV150 is an unmatched low voltage monitoring module designed for the public MV/LV substation. The main functions of LV150 are: transformer temperature monitoring, LV incomer power and quality monitoring, LV network voltage fault detection. It offers class 0.5 current and voltage, and class 1 energy system accuracy. The degree of protection is IP2x body and IP4x in the front. The degree of protection is IK07. It complies with CE certificat. The operating temperature is -40°C to + 70°C. The storage temperature is -40°C to + 85°C. It include 8 gigital inputs, and communication port ethernet 2 RJ45. The device dimensions are 45mm in width, 140mm in height, 140 in depth, and weight 0.46 kilograms.
Country of Origin
FR
Part Number
EMS59300
Tariff Code
9030390100
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1605007_V2
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
X
Circularity Profile
ENVEOLI1605007_V3
Eu Rohs Directive
Compliant with Exemptions

Complementary

Communication Port Support
2 ETHERNET RJ45
Measurement Voltage
: 0-30 V AC at 50/60 Hz (single or three phases)
Memory Capacity
4 MB
Protection Type
ANSI 47 : negative sequence overvoltage || ANSI 27 : undervoltage || ANSI 59 : overvoltage || ANSI 59N : neutral voltage displacement || ANSI 37 : phase undercurrent
Type Of Measurement
active and reactive energy || power factor || current || voltage || frequency || active and reactive power || apparent energy || apparent power
Product Or Component Type
low voltage and transformer monitoring
Measurement Current
5-5 A || 1-1 A
Number Of Inputs
8 digital IEC 61131-2 type 3
[Us] Rated Supply Voltage
12...48 V DC +/- 20 %
Communication Port Protocol
IEC 60870-5-104
Power Consumption In Va
2 VA
Software Function
assistance in commissioning and operating the installation || alarm || reports and diagrams || security/authority verification || Operating/Status report || event log
Control Type
illuminated push-button status:
Data Recording
sequence of event recording || sag and swell logs || counter || harmonics logs || event logs || demand values || min/max of instantaneous values || current value before fault
Analogue Input Type
current 0.01...35 A (impedance 0.001 Ohm)4 x
Type Of Measurement
current class 0.5 || voltage class 0.5 || energy class 1 IEC 61557-12
Synchronisation Time Between Inputs
1 ms
Power Quality Analysis
voltage sag and swell detection || voltage unbalance || individual harmonics || harmonic distortion || voltage magnitude

Environment

Product Certifications
CE
Ik Degree Of Protection
IK07 IEC 62262
Ambient Air Temperature For Operation
-40-70 °C
Height
140 mm
Standards
IEC 60255-27 || IEC 61557-12 || IEC 62586-1 || IEC 61000-4-30:class S || IEC 61850
Electromagnetic Compatibility
electrical fast transient/burst immunity test - test level: level 4 criteria A conforming to IEC 61000-4-4 || conducted RF disturbances - test level: level 3 criteria A conforming to IEC 61000-4-6 || conducted disturbance emission - test level: level 4 criteria A conforming to IEC 61000-4-16 || 100 kHz damped oscillating wave - test level: level 3 criteria A conforming to IEC 61000-4-12 || radiated radio-frequency electromagnetic field immunity test - test level: level 4 criteria A conforming to IEC 61000-4-3 || immunity to voltage dips criteria A conforming to IEC 61000-4-29 || electrostatic discharge - test level: level 4 criteria B conforming to IEC 61000-4-2 || surge immunity test - test level: level 3 criteria A conforming to IEC 61000-4-5 || magnetic field at power frequency - test level: level 5 criteria B conforming to IEC 61000-4-8 || conducted and radiated emissions class A conforming to EN 55022
Net Weight
0.46 kg
Fixing Mode
clip-in DIN rail)
Ambient Air Temperature For Storage
-40-85 °C
Relative Humidity
5-95 % IEC 60068-2-30
Ip Degree Of Protection
body IP2X IEC 60529 || front IP4X IEC 60529
Type Of Installation
indoor || outdoor in cabinet
Mechanical Robustness
vibrations 10-2000 Hz 1 gn 10 cycles IEC 60068-2-6 || bumps 10 gn 16 ms 1000 bumps non energized IEC 60068-2-29 || shocks 10 gn 11 ms 3 pulses in operation IEC 60068-2-27
Width
45 mm
Depth
140 mm
Operating Altitude
9842.52 ft (3000 m)

Specifications

Range Of Product
PowerLogic T300
Device Short Name
LV150

Documents

Data Sheet

Download