- Type Of Operating Handle
- direct frontal || external left side || external right side || external frontal
- Mounting Support
- plate || rail
- Connections - Terminals
- power circuit screw-clamp terminals 2.5-16 mm² flexible
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV
- Making Capacity
- 320 A 400 V AC-23B
- Short-Circuit Withstand
- 5.5 kA
- [Ui] Rated Insulation Voltage
- 800 V AC 50/60 Hz
- [Icm] Rated Short-Circuit Making Capacity
- 100 kA 400 V with protection by gG fuses
- Electrical Durability
- 1500 cycles AC-23A || 1500 cycles AC-23B || 300 cycles DC-23A || 300 cycles DC-23B
- Mechanical Durability
- 20000 cycles
- Tightening Torque
- power circuit 3-3 N.m screw-clamp terminals
- Rated Operational Power In W
- 15 kW 400 V || 18.5 kW 500 V || 25 kW 690 V
- Breaking Capacity
- 256 A 400 V AC-23B)