1 / 1
thumbnail

Description

Active Mature
Country of Origin
CZ
Part Number
K1F006NX
Tariff Code
85365080
EAN
3389110794250
UNSPSC
39122217
Payment methods:
Best offer from:
GBTrusted Automa.Net Supplier
Availability:
1 pc.
In-Stock
Updated at: 30-04-2024
Estimated Delivery:
On Request
Condition:
New Factory Sealed
New Factory Sealed - A brand-new, unused, unopened, undamaged item in its original manufacturer-sealed packaging.
A total of 5 Parts In-Stock from 5 Distributors
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

Available Offers (4)

K1F006NX product image
Schneider Electric

K1F006NX

Condition:
New Surplus
Available:
1 pc.
In-Stock
Updated at: 08-11-2024
Offer from:
DETrusted Automa.Net Supplier
Estimated Delivery:
On Request
Warranty:
12 months
1
K1F006NX product image
Schneider Electric

K1F006NX

Condition:
New Surplus
Available:
1 pc.
In-Stock
Updated at: 08-11-2024
Offer from:
GBTrusted Automa.Net Supplier
Estimated Delivery:
On Request
Warranty:
12 months
1
K1F006NX product image
Schneider Electric

K1F006NX

Condition:
New Surplus
Available:
1 pc.
In-Stock
Updated at: 08-11-2024
Offer from:
FRTrusted Automa.Net Supplier
Estimated Delivery:
On Request
Warranty:
12 months
1
K1F006NX product image
Schneider Electric

K1F006NX

Condition:
New Surplus
Available:
1 pc.
In-Stock
Updated at: 09-11-2024
Offer from:
FRTrusted Automa.Net Supplier
Estimated Delivery:
On Request
Warranty:
24 months
1
Offer with manufacturer lead time
Ships in:On Request
Best price:
€9.66

Environment

Ambient Air Temperature For Operation
-25-55 °C
Vibration Resistance
5 gn 10-150 Hz)IEC 68-2-6
Shock Resistance
30 gn IEC 68-2-27
Product Certifications
CSA 240 V 1 hp 1 phase || CSA 240 V 3 hp 3 phase 2 || UL 240 V 1 hp 3 phase || UL 240 V 0.33 hp 1 phase 2
Standards
IEC 60947-3 power circuit || IEC 60947-5-1 control circuit || CENELEC EN 50013
Ambient Air Temperature For Storage
-40-70 °C
Protective Treatment
TC

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP071103EN_V1
Sustainable Offer Status
Green Premium product
Toxic Heavy Metal Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Nickel compounds, which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
X
Circularity Profile
N/A
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)

Complementary

Short-Circuit Protection
16 A cartridge fuse gG
Number Of Steps
6
[Ithe] Conventional Enclosed Thermal Current
10 A
Net Weight
0.218 kg
[Uimp] Rated Impulse Withstand Voltage
4 kV in isolating function || 6 kV IEC 947-1
Switching Angle
45 °
Electrical Connection
captive screw clamp terminals flexible 2 x 1.5 mm² || captive screw clamp terminals solid 1 x 2.5 mm²
Electrical Durability
1000000 cycles AC-15 || 1000000 cycles AC-21 || 500000 cycles AC-23 || 500000 cycles AC-3
Maximum Operating Rate
2.5 cyc/mn AC-21 || 2.5 cyc/mn AC-23 || 2.5 cyc/mn AC-3 || 8.333 cyc/mn AC-15
Short-Circuit Current
10000 A
[Ui] Rated Insulation Voltage
690 V 3)IEC 60947-1
Positive Opening
with
Contact Operation
slow-break
Mechanical Durability
1000000 cycles
Rated Operational Power In W
10500 W AC-21, 500 - 660 V 3 phase IEC 947-3 || 1100 W AC-3, 230 V 3 phase IEC 947-3 || 1500 W AC-23A, 230 V 3 phase IEC 947-3 || 1500 W AC-3, 400 V 1 phase IEC 947-3 || 1500 W AC-3, 400 V 3 phase IEC 947-3 || 1500 W AC-3, 500 V 3 phase IEC 947-3 || 1500 W AC-3, 690 V 3 phase IEC 947-3 || 2200 W AC-23A, 400 V 3 phase IEC 947-3 || 2200 W AC-23A, 500 V 3 phase IEC 947-3 || 2200 W AC-23A, 690 V 3 phase IEC 947-3 || 4800 W AC-21, 230 V 3 phase IEC 947-3 || 600 W AC-3, 230 V 1 phase IEC 947-3 || 8300 W AC-21, 400 V 3 phase IEC 947-3
[Ie] Rated Operational Current Ac
1.8 A 690 V AC-3 3 phase IEC 947-3 || 2.8 A 500 V AC-3 3 phase IEC 947-3 || 2.8 A 690 V AC-23A 3 phase IEC 947-3 || 3.3 A 400 V AC-3 3 phase IEC 947-3 || 3.8 A 500 V AC-23A 3 phase IEC 947-3 || 4.6 A 230 V AC-3 3 phase IEC 947-3 || 4.8 A 400 V AC-23A 3 phase IEC 947-3 || 5.6 A 230 V AC-23A 3 phase IEC 947-3 || 1 A 500 V AC-15 IEC 947-5-1 || 2 A 400 V AC-15 IEC 947-5-1 || 3 A 230 V AC-15 IEC 947-5-1

Specifications

Range Of Product
Harmony K
Fixing Mode
Ø 22 mm hole
Sub-Assembly Composition
contact blocks + fixing plate
Product Or Component Type
cam switch body
[Ith] Conventional Free Air Thermal Current
12 A
Cam Switch Function
stepping switch
Component Name
K1
Mounting Location
front
Switching Positions
right: 0° - 45° - 90° - 135° - 180° - 225°
Bezel Material
metal
Poles Description
1P
Off Position
without Off position